NARRATIVE Sl%".ARY OF Pl. ANT OPERATIONS 10-1 to Plant ooerated at approximately 100% full power.
Performed 10-9-79 routine surveillance and preventive maintenance items.
10-10-79 (1320)
Started plant shutdown from 890 MWe at 1 Mile / minute due to non-conpletion of pipe support work on the "A" Nuclear Service Cooling Water System (1600)
Reactor at 86% power 6753 MWe)
(2045)
Reactor at 43% power (s350 MWe) and decreasing at 1 MWe/ minute to a Hot Shutdown (2313)
Opened OCB's 220 and 230. Unit off line.
(2315)
Tripped Turbine and reduced reactor power to 14%
10-11-79 (2346)
Reactor at 11% power.
(0107)
Reactor at 10-8 amps.
(0119)
Reactor placed in Hot Shutdown.
10-12-79 (1102)
Reactor critical.
(1105)
Reactor at 10-8,mp,,
, 1950)
Started increasing to $10% for turbine roll.
(
(2105)
Reactor at s10% power.
(2110)
Latched main turbine. Unable to get intercept Valve #1 open.
10-13-79 (1358)
Reactor at 10% power, tripped turbine.
Reactor still at 10%.
(1650)
Started turbine roll.
(1814)
While putting excitation on maid unit, it tripped on overexcitation and caused reactor trip.
(1857)
Reactor critical.
-8 (1908)
Reactor at 10 amps.
(1925)
Reactor at 1% power.
(2029)
Reactor at 10% power.
(2129)
Closed OCB's 220 and 230. Unit on line.
i 3 ()
7911200 k
10-14-79 (0000)
Feactor at 47
(%397 MVe).
(0035)
Reactor at SO: (%400 MWe)
(0650)
Reactor at 72% (%620 MWe).
Started 5-hour hold.
(1150)
Raising power to 92%.
(1356)
Reactor at 87% (%810 MWe) - Started 2-hour hold.
(1600)
Increasing to 100% full power.
(1746)
Reactor at 100% full power (%910 MWe).
10-15 to 10-31-79 Plant operated at approximately 100% full power.
Performed routine surveillance and preventive maintenance items.
PERSONNEL CHANGES REOUIRING REPORTING No personnel changes that require reporting in accordance with Technical Specifications Figure 6.9-2 were made in October, 1979.
MAJOR ITEMS OF SAFETY-RELATED MAINTENANCE 1.
Continued inspection / testing of pipe supports; repaired or replaced as necessary to meet the new criteria covered in Bulletin 79-02.
SUMMARY
OF CHANGES MADE IN ACCORDANCE WITH 10 CFR 50.59(bl No changes, tests or experiments were completed in October, 1979, Ohich constituted a change in a safety analysis report description.
l'l 7' :/ 'l JlI 1
I i
REFUELING I?.70TJ'.ATIO:' ?.EQUEST Rancho Seco Unit 1 1.
Nace of Facility:
2.
Scheduled date for next refueling shutdoer:
Januarv, 1980 March, 1980
'3.
Scheduled date for restart following refueling: _
4: Technical Specification change or other license ar.cnd=cnt required:
a) Change to Rod Inder. vs. Power Level Curve (TS 3.5.2) b) Change to Core I balance vs. Pouer Level Curve (TS 3.5.2)
' c) Tilt Limits (TS 3'5.2) d) Safety Equipment Testing (TS 3.3.3)
December. 1979 5.
Scheduicd date(s) for submitting proposed licensing action:
None 6.
Important licensing considerations associated with refueling:
~
7.
Number of fuel assen.blies:
a) In the core:
177 112 In the Spent Fuel Fool:
b) 379 8.
Present licensed spent' fuel capacity:
9.
frojected date of the last refueling that can be discharged 1987 to the Spent Fuel Pool:
'7C' 312 e
AVERAGE D \\lLY UNI T POh ER LEVEL
~
DOCKET NO.
IJNIT Rancho Seco Unit 1 DATE 70-10-11
\\~) J '" " \\
n l
TELEPliONE (916) 452-3211 MONTil October DAY AVERAGE DAILY POW ER LEVEL DAY AVERAGE DAILY POWER LEVE!.
(MWe Net)
(MWe Ne:)
849 861 g7 2
946 18 865 3
853 39 860 4
857 867 20 5
861 21 869 6
861 22 865 7
003 863 23 8
864 24 9
860 860 25 10 AR7 26 866 11 0
27 866 12 0
28 865 13 0
29 865 14 Asn 30 867 15 858 33 866 16 858 INS 3CCTIONS On tha formt. h5t the acr;c J.: y t.r:t power laelin MWe Net for each day in the repoinn; m..nrh. Compute to the nes est wheie meganatt.
e (9/77 )
M &99mW_
__ w.mese.e.me eme e - ene=
=+
OPERATLNG DATA REPORT DOCKET NO.
50-312 DATE 79-10-31 i
CO3IPLETED I!Y 9
W.
Colombo l[id h f3
,.l 76Jr] h,o.
TELEPHONE I41 AW-1211 OPERATING ST \\TUS
- l. Unit Name:
%ncho Seco l'nie 1
- 2. Reporting Fenod: October, 1979
- 3. Licensed Ther nal Power e3thri:
2772
- 4. Nr.episte Ratin; tGross alwer 061
- 5. Design Electrical Rating (Net ?.lWei:
918
- 6. Maximum Dependable Copacity iGrou.\\lWe::
917
- 7. Maximum Dependable Cacacity iNet 31We):
073
- 8. If Change, Occur in Capacity Rat:c3s fitems Number 3 Throu;h 7) Since Last Report. Gise Reasons:
9/s
- 9. Power Level To which Restricted. If Anv (Net 31We):
N/^
10.' Reasons For Restrictions, If Any:
N/A This Month Yr.to.Dat:
Cumulatise
-11. Hours !n Reporting Period 745 7,296 39,793
- 12. Number Of Hours Reactor Was Crities!
- D O'"J
- 13. Resetor Resene Shutdown Hours 33.7 1,557.7 3,975.1
- 14. HoarsG.enerator Oa Line 6 74. 7 5,399.6 23,562.8
- 15. Unit Resene Shutdown Hours 0
1.199.3 1.210.2
- 16. Gross The. mal Ener;y G.nerated \\lWH) 1.847,705 14,753,805 59,826.961
- 17. Gran Electrical Ener;> Generated iathHi 590,650 4,808.359 20,071,159 IS. Net Efeetrical Energy Generated i3th Hi 559.602 4.560.773 18.9so.AA3
- 19. Unit Senice Factor 90.6 74.0 59.2
- 20. Unit Assilabi!ity Factor 90.6 90.4 62.3
- 21. Unit Capacit> Factor IUning MDC Neti 86.0 71.6 54.6
- 22. Unit Ca,,a,:it> Faetor iUsing DER Nets 81.8 68.1 51.9
- 23. Unic Forced Outiu Rate 9.4 5.9 33.2
- 24. ShutJown> Sehe.!aled Oser Nest o \\!onths IT)pc. Date Jcd Dur.: tion of Eachi:
RA#ueline i,ni,,v..
1000 - ri,, v, e f e, n, n n r n y f -, e n 1,.
An 4,ve Snubber insocction/cht.ncine of undervoltace setoointst Mid Yeve-ber - due,H nn 3 days.
- 25. If Shut Down \\t End Of Re;.:rt Period. Estimated Date of St_rtup:
N/A
- 26. Units in Tor Status iPrior to Commercia! Ogyrations:
Foreca :
Achiesed INITIAL CRITICAL.iii.
N/A e
N/A INITI \\L FLFCTR! CITY N/A N/A COMMLRCIAL UPER \\ fl0N N/A N/A h
s
O D
m g/ ha
!j 7r DOCKET NO. 50-312 i
UNITSilUTDOWNS AND POWER REDUCTIONS i j jj UNIT NA%IE Rancho Seco linit 1 C,,
.n
'D D ATE 79-10-11 COMPLEIEl> liv p t?
c.a m wn REPORT MONTit October TELEPilONE (916) 452-1711 "L
C C
'e
- EU Licer.sce E-t
'd%
Cause A Corsective No.
Date 5j 3$d Event (i
f'8 Action so f
E j ;f, =
Repori e mu O
Prevent Recurrence H
g c5 I
13 79-10-10 F
7.3 D
1 79-014/03 L-0 CJ SUPORT Non-completion of pipe support work on Nuclear Service Cooling Water System.
Unit brought to llot Shutdown per Technical Specification limitations and work was completed.
6 2
3 4
F: Forced Reaum Method:
Exhibit G. Instructions s
S: Scheduled A-I: qui ment Failure (Explain)
' l-Manual for Preparation of Data c_w II.M.sintenance or Test 2 Manual Scram.
Enity Sheets for Licensee a
C Itcfueling 3-Automatic Sciam.
Event Report (LI:RI File (NUREG.
D Itc3;ulatory Restriction 4-Other (Explain) 01611 g
I' t)pesaior Tsaining & License Examination F. Adnunist raine 5
g G-Operationa! Eiror (Explain)
Exlubit I -Same Source (9/77)
Il Oiher (Explain)