~ e.

[

g RfC f

g UNITED STATES y

g NUCLEAR REGULATORY COMMISSION 3

p WASHINGTON, D. C. 20555 k*...,/

October 29, 1979 Docket No. 50-255 Mr. David Bixel

' Nuclear Licensing Administrator Consumers Power Company 212 West Michigan Avenue Jackson, Michigan 49201

Dear Mr. Bixel:

'RE: REQUEST FOR ADDITIONAL INFORMATION SYSTEMATIC EVALUATION PROGRAM STRUCTURAL TOPICS PALISADES PLANT To continue our review of the Systematic Evaluation Program structural topics, we request that you provide the information described in the enclosure for each of the identified topics.

Your response is requested within 30 days so that we can maintain our review schedule.

Sincerely, uC Dennis L. Ziemann hief Operating Reactors Branch #2 Division of Operating Reactors

Enclosure:

Request for Additional Information cc w/er. closure:

See next page t

een G

1126 030

.7911140 / M g

Mr. David Bixel October 29, 1979 cc w/ enclosure:

M. I. Miller, Esquire Isham, Lincoln & Beale Suite 4200 One First National Plaza Chicago, Illinois 60670 Mr. Paul A. Perry, Segretary

- Consumers Power Company 212 West Michigan Avenue Jackson, Michigan 49201 Judd L. Bacon, Esquire Consumers Power Company 212 West Michigan Avenue

. Jackson, Michigan 49201 Myron M. Cherry, Esquire Suite 4501 One IBM Plaza

. Chicago, Illinois 60611 Ms. Mary P. Sinclair Great Lakes Energy Alliance 5711 Summerset Drive Midland, Michigan 48640 Charles Bechhoefer, Esq., Chairman Atomic Safety and Licensing Board Panel U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Dr. George C. Anderson Department of Oceanography University of Washington Seattle, Washington 98195

+

Dr. M. Stanley Livingston 1005 Calle Largo Santa Fe, New Mexico 87501 Kalamazoo Public Library 315 South Rose Street Kalamazoo, Michigan 49006 K M C, Inc.

ATTN:

Richard E. Schaffstall 1747 Pennsylvania Avenue, N. W.

Suite 1050 Washington, D. C.

20006 1326 031

PALISADES REQUEST FOR ADDITIONAL INFORMATION STRUCTURAL TOPICS a

Additional information 'is needed for the following structural topics:

III-2 Wind and Tornado Loads For each safety-related structure, describe the procedures to transfer tornado data into design pressure.

III-7.8 Design Codes, Desion Criteria and Load Combinations 1.

With regard to the design of the prestressed concrete containment, provide the design specification and any design reports. This information should include those requested in items two, through five below.

2.

List the codes and standards (include edition date) used for design and construction of steel members of each safety-related structure.

3.

List all loads considered in the design of safety-related structures including any missile or pipe break effects.

4.

Provide the design and/or actual material properties (fg and fi) used for steel and concrete elements.

For concrete, also provide the age specified and any admixtures used.

5.

Provide representative stress levels (conpression, tension and shear) at critical location of each safety-related structures (e.g. base of containment internal structures) for each of the load combinations considered in the design.

III-7.C Delamination of Prestressed Concrete Containment Structures Describe the construction procedures for the prestressed containment shell including the tendon tensioning sequence.

Provide any inspection reports for the containment that may have assessed the likelihood of delamination occurring in the shell wall or dome.

If such inspections were made but not documented, describe the results of these inspections.

III-7.0 Containment Structural Integrity Tests Provide any reports that describe the procedures and results of the containment structural integrity test.

1326 032L October 29, 1979

.