ML19210B242
| ML19210B242 | |
| Person / Time | |
|---|---|
| Site: | Crane |
| Issue date: | 08/17/1973 |
| From: | Anthony Giambusso US ATOMIC ENERGY COMMISSION (AEC) |
| To: | John Miller METROPOLITAN EDISON CO. |
| References | |
| NUDOCS 7911040192 | |
| Download: ML19210B242 (2) | |
Text
4 DISTRI.
, Local PDR Docket File AUG 1 7 1973 WR-4 Rdg RP Rdg RCDeYoung PWR Branch Chiefs RWKlecker Docket No. 50-289 RMBernero EIGoulbourne ACRS (16)
Metropolitan Edison Company ATTN: Mr. John G. Miller Vice President P. O. Box 542 Reading, Pennsylvania Gentlemen:
AEC Eegulatory Operations personnal have been following tendon stressing operations on the reactor building of Three Mile Island, Unit 1.
They have noted to you their concern about the recessions measured on the upper bearing plates of the vertical tendons.
We understand that your procedure is written to allow recessions up to 0.25 inches and that you have measured recessiona approaching 60 percent of that value. In response to our concern your staff has suggested a meeting with us to discuss the basis of your specification of 0.25 inches maximum recession and your arguments to support its validity.
Because of our recent experience with this phenomenon in the Calvert Cliffs case (Docket Nos. 50-317/318) we strongly urge you to remove soms of these bearing plates for post-tensioning examination of the concrete beneath. We reco==nand that you explore those plates which have shown the greatest recession and have the resulta-of that a - 4 nation available before we meet. We are aware tMt you have the necessary equipment on site at this time and feel that prompt removal and examination of these suspect plates will be the nost expeditious resolution of our concern in this matter.
Sincerely.
Original Signed By A. Giambusso A. Giambusso, Deputy Director for Reactor Projects Directorate of Licensing 1585 065 cc: See next page I
orrgs,
WR......
. L'Q/PWR-4 RO
..... L.: AD/PWRs.
..L. :.D..D SC encer GReinmuth,,,,; RCD Y6ung__
AGiambusso SURNAME >
8/,
/73,8/ M
/73 8/ /4
/73 1, /M
/73 8/,,/j,,/73, oATE >
Form AEC-Sta (Rev. 9-53) AEC. 0240
..o
.43-to-s t ess-i eis-eE 17 91104 0 /p g
,.e.
John G. Miller 2-cc: Gerald Charnoff Shaw, Pittman, Potts &
Trowbridge 910 17th Street, NW Washington, D. C.
20006 3
1585 066 0FFICE >
SURNAM >
DATE >
Ferra AEC-51s (Rev.9 53) AECM 0240
- o so-to-stes-t ea s-4:s