Text
'
.e 4
DISTRIBUTION:
NRC PDR April 11,75 Local PDR Docket ORB $3 Rdg Docket No. 50-289 KRGoller TJCarter GLear DJaffe Metropolitan Edison Company SATeets ATTN: Mr. R. C. Arnold OELD Vice President - Generation OISE (3)
P. O. Box 542 ACRS (14)
Reading, Pennsylvania 19603 Gray file extra cps Gentle:nen:
We have reviewed your January 30, 1975 application for license amendment which contained Limiting Conditions for Operation (LCO) and Surveillance Requirements (SR) for installed filter systems. With regard to these proposed technical specifications, we have identified three major areas in which they do not conform to the guidance furnished in our Ictter dated December 6, 1974. These items are as follows:
1.
When the LCO's for the Emergency Control Room Air Treatment System and the Reactor Building Purge Air Treatment System cannot be satisfied, the reactor is to be in cold shutdown after a specified period of time. You had proposed that the reactor Le placed in hot shutdown.
2.
Thi tests and sample analysis for the Auxiliary and Fuel HandMag Exhaust Air Treatment System are to be performed after 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of operation. You had proposed that tests and sample analysis be performed at least once per refueling interval.
3.
The laboratory carbon sample analysis is to be performed at a relativ&
humidity of greater than, or equal to, 95'h.
You had proposed.that the analysis be performed at a relative humidity of greater than, or equal to, 60%.
Within fifteen (15) days following receipt of this letter, please provide a discussion explaining, for each of the above cited items, why conformance with our guidance could not be achieved.
Sincerely,
/S/'
1490 266 George Lear, Chief Operating Reactors Branch #3 g y',
Di'licier censin;;
ORB ORB #3
,v o r,...,
GLear M--
DJaffe:
_ l_.
7
.u.....,
U 4/ (O /75 4/ j.
/75
[
r ac.m m,....m n:x om
- u.......,...vi.o,..............
o
lir. R. C. Arnold cc:
G. F. Trowbridge, Esquire Shaw, Pittman, Potts, Trowbridge 6 Madden Barr Building 910 17th Street, N. W.
Washington, D. C.
20005 GPU Service Corporation Richard W. Heward, Project Manager Thomas M. Crimins, Jr., Safety and Licensing Manager 260 Cherry Hill Road Parsippany, New Jersey 07054 Pennsylvania Electric Company Vice President, Technical 1001 Broad Street Johnstown, Pennsylvania 15907 Mr. Weldon B. Arehart, Chaiman Board of Supervisors of Londonberry Township 2148 Foxiana Road
. Middletown, Pennsylvania 1/057 Miss Mary V. Southard, Chairman Citizens for a Safe Environment P. O. Box 405 Harrisburg, Pennsylvania 17108 Government Publications Section State Library of Pennsylvania Box 1601 (Education Building)
Harristurg, Pennsylvania 17126 1490 267 orrecE P svRNaua >
DATE h
~~
Torm AEC 318 (Rev. 9 53) AICM 0240 W v, S. soVERNMENT PRINTING oPPICEI 1974 828-188