Tech Spec Change Request 21 Supporting Licensee Request to Change DPR-50,App a Re Radioactive Matls
ML19210A613
Person / Time
Site: Three Mile Island Constellation icon.png
Issue date: 09/25/1975
From: Arnold R
METROPOLITAN EDISON CO.
To:
Shared Package
ML19210A611 List:
References
NUDOCS 7910300648
Download: ML19210A613 (10)


Text

, -

METROPOLITAN EDISON COMPANY JERSEY CENTRAL POWER & LIGHT COMPANY AND PENNSYLVANIA ELECTRIC COMPANY THREE MILE ISLAND NUCLEAR STATION UNIT 1 Operating License No. DPR-50 Docket No. 50-289 Technical Specification Change Request No. 21 This Technical Specification Change Request is submitted in support of Licensee's request to change Appendix A of the Technical Specifications and page 2 of the Operating License for Three Mile Island Nuclear Station Unit 1. As a part of this request, proposed replacement pages are also included.

OMPANY METROPO ITAN,GDISON

(

BY >

Vice Presfdent-Generation Sworn and subscribed to me this 25th lay of September,1975.

_C b M 1 Notary Publie jg}

F'CHArtD !. RUTH Mc*3rt F:.:' - :fa.: mer; 'ca , Ser!.s Co.

?v Camm.ss,ca Coes '.a;w: r23,1973 7910800b9g

teth2intz /

5: - _ ,,,

/

/

METROPOLITAN EDISON COMPANY sues:ounvorcesewueucunune courmnon ,l POST OFFICE BOX 542 READING, PENNSYLVANI A 19603 TELEPHONE 215 - 929-3601 September 25, 1975 GQL 1536 Mr. Charles P. Hoy, Chairman Board of County Commissioners of Dauphin County P. O. Box 1295 Harrisburg, Pennsylvania 17120

Dear Mr. lioy:

Enclosed please find one copy of Technical Specification Change Request No. 21 to Appendix A of the Technical Specifications and page 2 of the Operating License for Three Mile Island Nuclear Station Unit 1.

This request was filed with the U. S. Nuclear Regulatory Commission on September 25, 1975.

Very truly yours,

/s/ R. C. Arnold R. C. Arnold Vice President RCA:CWS:rk File 20.1.1/7.7.4.3.6.1 1492 164

=- ---

METROPOLITAN EDISON COMPANY sectiou-m aewum ,. .u. ,y, n- ,

POST OFFICE BOX 542 READING, PENNSYLVANI A 19603 TELEPHONE 215 - 929.J601 September 25, 1975 GQL 1536 Mr. Weldon B. Arehart, Chairman Board of Supervisors of Londonderry Township R.D. #1, Geyers Church Road Middletown, Pennsylvania 17057

Dear Mr. Arehart:

Enclosed please find one copy of Technical Specification Change Request No. 21 to Appendix A of the Technical Specifications and page 2 of the Operating License for Three Mile Island Nuclear Station Unit 1.

This request was filed with the U. S. Nuclear Regulatory Commission on September 25, 1975.

Very truly yours,

/s/ R. C. Arnold R. C. Arnold Vice President RCA:CWS:rk File 20.1.1/ 7. 7.4. 3. 6.1 1492 165

3.9 RADIOACTIVE MATERIALS This section has been included in the Environmental Technical Specifications.

3.10 MISCELLANEOUS RADIOACTIVE MATERIALS SOUR CS Anulicability Applies to byproduct, source, and special nuclear redioactive material sources.

Ob.iective '

To assure that leakage from byproduct, source, and special nuclear radioactive material sources does not exceed allevable limits.

Snecification, 3.10.1 The source leakage test performed pursuant to Specification 4.13 shall be capable of detecting the presence of 0.005 pCi of radioactive material on the test sa=ple. If the test reveals the presence of 0.005 pCi or more of recovable contacination, it chall it=ediately be withdrawn from use, decontaminated, and repaired, or be disposed of in accordance with Coc=ission regulations. These quantities of byproduct =aterial that exceed the quantities listed in 10CFR 30.71 Schedule B are to be leak tested in accordance with Specification 4.13. All other sources (including alpha emitters) containing greater than 0.1 microcuries are also to be leak tested in accordance with Specification 4.13.

3.10.2 A co=plete inventory of licensed radioactive materials in possession shall be maintained current at all times.

Bases Ingestion or inhalation of source caterial may give rise to total body or organ irradiation. These specifications assure that leakage from radioactive caterial sources does not exceed allovable limits. In the unlikely event that those quantities of radioactive by-product raterials of interest to this specification which are exempt from leakage testing are ingested or inhaled, they represent less than one maximum per=issible body burden for total body irradiation. The limits for all other sources (including alpha esitters) are based apen 10 CFR 70.39(c) limits for plutoniu=.

Pages 3 kT to 3-54 Deleted 3_g 1492 166

- 2 -

f. The license 9s have satisfied the applicable provisions of 10 CFR Part 1k0, " Financial Protection Require =ents and Inde=nity Agree =ents," of the Co==ission's regulations ;
g. The issuance of this operating license vill not be inimical to the co= mon defense and security or to the health and safety of the public;
h. After weighing the enviro = ental, economic, technical, and other benefits of the facility against environ = ental costs and considering available alternatives, the issuance of Facility Operating License No. DPR-50 is in accordance with 10 CFR Part 50, Appendix D, of the Co==ission's regulations and all applicable require =ents of said Appendix D have been satisfied; and
1. The receipt, possession, and use of source, byproduct and special nuclear =aterial as authorized by this license rill be in accordance with the Co==ission's regulations in 10 CFR Parts 30, ho and 70, including 10 CFR Section 30.33, ko.32, 70.23 and 70.31.
2. Facility Operating License No. DPR-50 is hereby issued to the Metropolitan Edison Company, Jersey Central Power and Light Co=pany and Pennsylvania Electric Co=pany to read as follows:
a. This license applies to the Three Mile Island Nuclear Station, Unit 1, a pressurized water reactor and associated equipment (the facility),

owned by the licensees and operated by Metropolitan Edison Company.

The facility is located in Dauphin County, Pennsylvania and is described in the " Final Safety Analysis Report" as supplemented and a= ended (A=end:ents 1 through kT) and the Environ = ental Report as supplemented and a= ended (Amend =ents 1 and 2).

b. Subject to the conditions and rec tire =ents incorporated herein, the Co==ission hereby ll:enses:

(1) Metropolitan Edison Company, pursuant to Section 10hb of the Act and 10 CFR Part 50, " Licensing of Production and Utilization Facilities," to possess, use, and operate the facility; and Jersey Central Power and Light Cc=pany and Pennsylvania Electric Co=pany to possess the facility in accordance with the procedures and li=itations set forth in this license; (2) Metropolitan Edison Co=pany, pursuant to the Act and 10 CFR Parts 30, ho and To to receive, possess and use at any time any byproduct, source and special nuclear =aterial as reactor fue! ,

sealed neutron sources for reactor startup, sealed sources fo?

reactor instrumentation and radiation =onitoring equip =ent calibration, and as fission detectors in amounts as required in accordance with li=itations for storage and arounts required for reactor operatica, as described in the Final Safety Analysis Report ,

as supple =ented and a= ended.

1492 167

METROPOLITAN EDISON COMPANY (MET-ED)

THREE MILE ISLAND NUCLEAR STATION, UNIT 1 (TMI-1)

OPERATING LICENSE NO. DPR-50 Docket No. 50-289

1. Technical Specification Change Reouest No. 21 The Licensee requests that the following changes be made to the Operating License and Appendix A of the Technical Specifications.

Proposed changed pages are attached.

a. For the TMI-1 Operating License, page 2, part 2.b. (2), change the last two lines to read " calibration, and as fission detectors in the amounts as required in accordance with limitations for storage and amounts required for reactor operation, as described in the Final Safety Analysis Report, as supplemented and amended."
b. On page 3-46, Specification 3.10.1, Delete the last sentence and add "Those quantities of by-product material that exceed the quantities listed in 10 CFR 30.71 Schedule 3 are to be leak tested in accordance with the schedule shown in Specification 4.13. All other sources (including alpha emitters) containing greater than 0.1 microcuries are also to be leak tested in accordance with Specification 4.13."
c. On page 3-46, 3.10, add Bases Ingestion or inhalation of source material may give rise to total body or organ irradiation. These specifications assure that leakage from radioactive material sources does not exceed allowable limits.

In the unlikely event that those quantities of radioactive by-product materials of interest to this specification which are exempt from leakage testing are ingested or inhaled, they represent less than one maximum permissible body burdan for total body irradiation.

The limits for all other sources (including alpha emitters) are based upon 10 CFR 70.39 (c) limits for plutonium.

2. hason for Proposed Chayn .;

The proposed change was requested by Mr. George Lear of the NRC in his letter of January 8,1975. The change makes these specifications consistent with the current standardized Technical Specifications.

3. Safety Analysis Justifying Change As additional requirements are imposed, the change provides further protection of the health and safety of the public. No unreviewed safety questions are involved.

1492 168