APPENDIX A NOTICE OF VIOLATION Duquesne Light Company Docket No. 50-334 Based on the results of an NRC inspection conducted on April 16-24, 1979, it appears that one of your activities was not conducted in full compliance with the conditions of your NRC License No. DPR-66 as discussed below.
This item is an infraction.
Technical Specification 4.7.8.1.c states, in part, "Each Supplementary Leak Collection and Release System exhaust air filte r train shall be demonstrated OPERABLE:... c. At least once per eighteen months by:
- 2. Verifying that the air flow distribation to each HEPA filter and charcoal absorber is within + 20% of the averaged flow per unit.
Technical Specification 6.S.l.c states, in part, "Uritten procedures shall be established, implemented and maintained covering... c. Sur-veillance and test activities of safety related eq'Jipment.
Contrary to the above, the verification required by Technical Speci-fication 4.7.8.1.c.2 has not been performed since August 1975 and procedures to perform that verification have not been established or maintained as part of the licensee's surveillance test program.