Responds to Requesting NRC Concurrence W/Util Use of Arc Welding Electrodes E7018 in Unheated Containers for 14-h Periods When Issued for Use on Plain Carbon Steel Weldments.Procedure Is Acceptable for Qualified Electrodes
ML19209A572
Person / Time
Site: Grand Gulf  
Issue date: 09/07/1979
From: Stolz J
Office of Nuclear Reactor Regulation
To: Stampley N
MISSISSIPPI POWER & LIGHT CO.
References
NUDOCS 7910050011
Download: ML19209A572 (2)


Text

1MJ jf ~ "M Wr - - g

fgaency4, UNITED STATES 1

f \\* NUCLEAR REGULATORY COMMISSION 3 WASHINGTON D. C. 20555 O, $ ,f

  • g ' \\

j' SEP 7 1979 Docket Nos: 50-416 and 50-417 Mr. N. L. Stampley, Vice President Production and Engineering Mississippi Power & Light Company P. O. Box 1640 Jackson, Mississippi 39205

Dear Mr. Stampley:

SUBJECT:

MOISTURE CONTROL FOR E7018 ARC-WELDING ELECTRODES (GRAND GULF NUCLEAR STATION, UNITS 1 AND 2) Your letter dated August 23, 1979 requested ou concurrence with your use of E7018 arc-welding electrodes in unheated containers for periods of up to 14 hours when issued for use on plain carbon steel weldments. You state that your request is based on your review of the original test data contained in the report entitled " Qualification of an Alternative Electrode Control Program for AWS Dl.1 for the Arizona Nuclear Power Project, Palo Verde Units 1, 2 and 3," dated March 15, 1978. We have completed our review of the information contained and referenced in your letter and conclude that the use of E7018 arc-welding electrodes in unheated containers for periods of up to 14 hours when issued for use on plain carbon steel weldments is acceptable. It should be noted, however, that our acceptance is limited to those E7018 arc-welding electrodes that have been appropriately qualified by testing as described in the alternative electrode control program for the Palo Verde Nuclear Generating Station. Sincerely, a w h)JohnF.Stolz, hief Light Water Reactors Branch No. 1 r Division of Project Management cc: See next page 1108 239 7010050 O N*

t Mr. N. L. Stampley cc: Mr. Robert B. McGehee, Attorney Wise, Carter, Child, Steen & Caraway P. O. Box 651 Jackson, Mississippi 39205 Troy B. Conner, Jr., Esq. Conner, Moore & Corber 1747 Pennsylvania Avenue, N. W. Washington, D. C. 20006 Mr. Adrian Zaccaria, Project Engineer Grand Gulf Nuclear Station Bechtel Power Corporation Gaithersburg, Maryland 20760 f: i108 240}}