ML19208B673
| ML19208B673 | |
| Person / Time | |
|---|---|
| Site: | Trojan File:Portland General Electric icon.png |
| Issue date: | 09/10/1979 |
| From: | Engelken R NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V) |
| To: | Goodwin C PORTLAND GENERAL ELECTRIC CO. |
| References | |
| NUDOCS 7909210166 | |
| Download: ML19208B673 (1) | |
Text
s#* "Guq
/I ( G
/
d UNITED STATES
[ [ f.(f('%,
NUCLEAR REGULATORY COMMISSION
,g G-
'M =
REGION V 0,,
,d
[
1990 N. CALIFORNIA BOULEVARD
%, ' a
g' SUITE 202, WALNUT CREEK PLAZA o
WALNUT CREEK CALIFORNIA 94596 September 10, 1979 Docket flo. 50-344 Portland General Electric Company 121 S. W. Salcon Street Portland, Oregon 97204 Attention: Mr. Charles Goodwin, Jr.
Assistant Vice President Gentlemen:
The enclosed Circular No. 79-18 is forwarded to you for information.
flo written response is required. Should you have any questions related to your understanding of the recommendations on this matter, please contact this office.
Sincerely, b-sycWk R. H. Engelken Director
Enclosure:
IE Circular No. 79-18 cc w/ enclosure:
C. P. Yundt, PGE F. C. Gaidos, PGE 3dU.$.iR 7909210 /[6
Accession No: 7908200385 SSINS No. 6830 UNITED STATES NUCLEAR REGULATORY C0!NISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 September 10, 1979 IE Circular No. 79-18 PROPER INSTALLATION OF TARGET ROCK SAFETY-RELIEF VALVES Description of Circumstances:
As a result of NRC monitoring of operating experiences involving the Target Rock safety-relief valve, two potential problems have been identified. One potential problem is that the performance of the valve has been found to be impaired by either excessive or insufficient insulation around the valve body when installed in its service environment.
The other potential problem is that improper assembly of the modified valve can result in inoperability of the remote air actuator.
The Target Rock safety-relief valve is a dual purpose valve in that overpressure response is provided by pilot valve action and automatic depressurization (ADS) is provided by a renote air actuator. Valve operation has been found to be affected by the amount of insulation placed around the valve body. A previous IE Bulletin No. 76-06 was issued on July 21, 1976 as a result of operating experiences where excessive insulation was installed on the valve.
The excessive insulation caused excessive heat to be retained producing a higher temperature environment for the elastomeric diaphragm which resulted in accelerated deterioration of the elastomer.- Failure of the elastomeric diaphragm, makes the valve inoperable in the power-operation mode (i.e. manual and ADS).
Subsequently, a silicone-nomex diaphragm was developed by the manufacturer to provide a longer life in high temoerature environments.
In addition, the IE Bulletin explicitly required that insulation be installed in accordance with the manufacturer's recommendations.
A recent licensee event report from the Monticello facility identified a potential problem resulting from insufficient insulation (i.e. just opposite of the condition addressed by IE Bulletin 76-06).
During the performance of special testing of the response to safety-relief valve operation, a valve was discovered to be exceeding its design delay time for opening.
Subsequent inspection and testing of the valve revealed that insufficient insulation may cause condensation to accumulate in the pressure venting ports which then results in delaying the opening of the main disk. This slower response time is significant with respect to primary <
.I response analyses. Although the reportc A< A O U
3M DUPLICATE DOCUMENT three-stage Target Rock safety-relief vi of insulation are similarly applicable i Entire document previously entered valves.
into system under:
The second potential problem was recenti ANo 790 $ 200365 The licensee event report indicated that design two-stage valve resulted in preve No. of pages:
N
..