Safety Evaluation Supporting Amend Requests for Deletion of Reactor Trip on Turbine Trip Below 50% Power.Evaluation Based on Encl Review of Lawrence Livermore Lab Technical Evaluation Rept
ML19208B572
Person / Time
Site: Farley 
Issue date: 08/21/1979
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML19208B570 List:
References
NUDOCS 7909210023
Download: ML19208B572 (2)


Text

.

SAFETY EVALUATION REPORT FARLEY UNIT 1 DELETION OF REACTOR TRIP ON TURBINE TRIP BELOW 50 PERCENT POWER TAC 11053 AUGUST 1979 Prepared By: Plant Systems Branch Division of Operating Reactors M bl30 1

7 909210 Ob

~. - -

1.0 INTRODUCTION

By letter dated November 15, 1978 the Alabama Pcwer Company submitted a license amendmnt request for the deletion of reactor trip on turbine trip below 50 percent power.

2.0 EVALUATION The enclosed Technical Evaluation Report was prepared for us by the Lawrence Livermore Laboratory as part of our technical assistance program.

3.0 CONCLUSION

S Based on our review of our consultant's enclosed Technical Evaluation Report, we agree with their findings that: (1) the licensee's analyses shows that the requested Technical Specification changes do not degrade the other reactor safety systems or change their mode of operation; and (2) since the system has the design capability to accept a 50 percent load rejection, a reactor trip is not necessary because of a turbine trip until at or above 50 percent power. The proposed license amendment request dated November 15,1978 is, therefore, acceptable to us.

4.0 REFERENCE Lawrence Livennore Laboratory Technical Evaluation Report, August 1979.