Ack Receipt of Re Design Info on Fire Protection Mods.Foam Sys & wet-pipe Sprinkler Sys Is Acceptable If Foam Sys Is Activated Prior to Sprinkler Sys & If Baffle Is Between Heads to Assure Proper Distribution of Spray
ML19207C257
Person / Time
Site: Cooper 
Issue date: 08/10/1979
From: Ippolito T
Office of Nuclear Reactor Regulation
To: Pilant J
NEBRASKA PUBLIC POWER DISTRICT
References
NUDOCS 7909100564
Download: ML19207C257 (2)


Text

TCdd]'

I G l\\ !

,,(pa aro k vy UNITED STATES y) c(

g NUCLEAR REGULATORY COMMISSION y

WASHINGTON. D. C. 20555 August 10, 1979 Docket No. 50-298 Mr. J. M. Pilant, Director Licensing & Quality Assurance Nebraska Public Power District P. O. Box 499 Columbus, Nebraska 68601

Dear Mr. Pilant:

By your letter dated June 28, 1979 you provided design information on specific fire protection modifications for Cooper Nuclear Station. We have reviewed your submittal and have reached the following conclusions:

1.

Sprinkler Protection for Cable Chase in Turbine Generator Building (SER item 3.6)

Acceptable as proposed 2.

Fire Pump Discharge Header Isolation Valve (SER item 3.27)

Acceptable as proposed 3.

Fixed Foam Fire Protection and Wet Pipe Sprinkler System for Diesel-Driven Fire Pump (SER item 3.3.1)

The detection system should be designed to assure that the foam system is activated prior to actuation of the backup sprinkler system.

If the heads for the sprinkler system are to be located only 2.5 feet apart, then a baffle should be placed between the heads to assure proper distribution of spray.

If the design does indeed consider these two factors, then we find it acceptable.

You should complete these modifications in accordance with the schedule contained in Table 3.1 of the Safety Evaluation Supporting Amendment No. 56 to DPR-46.

Sincerely,

.h y. b-D l

Thomas'A. Ippolito, Chief Operating Reactors Branch =3 Division of Operating Reactors uc:

See next page 7 909 I 00G(/

S.30.34

Mr. J. M. P11 ant Nebraska Public Pcwer District 2-August 10, 1979 cc:

Mr. G. D. Watson, General Counsel Nebraska Public Power District P. O. Box 499 Columbus, Nebraska 68601 Mr. Arthur C. Gehr, Attorney Snell & Wilmer 3100 Valley Center Phoenix, Arizona 85073 Cooper Nuclear Station ATTN: Mr. L. Lessor Station Superintendent P. O. Box 98 Brownville, Nebraska 68321 Auburn Public ' Library 118 - 15th Street Auburn, Nebraska 68305 9