Text

.

L

'df UNITED STATES

[ '*g - f( }

NUCLEAR REGULATORY COMMISSION

)/

e wasmNcros. o. c. :osss

.%g%2fl y

r JUl' 2 0 mg MEMORANDUM FOR:

D. Ziemann, Chief, Operating Reactors Branch #2, Division of Operating Reactors FROM:

G. Lainas, Chief, Plant Systems Branch, Division of Operating Reactors

SUBJECT:

OYSTER CREEK, REQUEST FOR ADDITIONAL INFOPFATION FOR DEGRADED GRID VOLTAGE (TAC 10038)

Plant Name: Oyster Creek Docket No.-

50-219 Responsible Branch: ORB #2 Project Manager:

S. Nowicki Reviewing Branch:

Plant Systems Branch Status:

Awaiting Information In response to technical assistance request TAC 10038, the Plant Systems Branch has reviewed the licensee's submittal of April 18, 1977 and found that additional information is required in order to complete our review.

The attached request for additional infonnation should be foraarded to the licensee as soon as possible with a request for response within 45 days.

G. Lainas, Chief Plant Systems Branch Division of Operating Reactors

Contact:

S. Rhow, X28077 C. Cleveland, EG&G

Enclosure:

As stated f

r,,

I L.

l L_

790005004y

ORC J Ol'

-2_

cc w/ enclosure:

D. Eisenhut B. Grimes R. Vollmer W. Russell S. Nowicki G. Lainas D. Tondi M. Chiramal P. Shemanski S. Rhow C. Cleveland, EG&G

~

() 4' '

_m L

REQUEST FOR ADDITIONAL INFORMATION OYSTER CREEK DEGRADED GRID VOLTAGE (TAC 10038)

Basrc. e, var review of your submittal dated April 28, 1977 we have concluded that t'a use of the existing undervoltage relaying to protect against a suste:ned degraded grid condition is not acceptable. Hence, we require that you provide your proposed design modification and changes in the Technical Specification based on the guidance contained in the staff positions submitted to you by our letter dated June 3,1977.

I A

4, \\ ' h.a ^' '

a.-

-