SLRA Email Transmittal of Draft RAIs with Attachments - 7JUN2019
ML19176A281
Person / Time
Site: Surry  
Issue date: 06/07/2019
From: Sayoc E
NRC/NRR/DMLR/MRPB
To: Aitken P, Blocher E
Dominion Energy Co
Sayoc E
References
Download: ML19176A281 (2)


Text

From:

Sayoc, Emmanuel To:

Paul Aitken; "Eric A Blocher" Cc:

Wu, Angela

Subject:

Draft RAI 4.7.3-7 Surry SLR 4.7.3 LBB TLAA Date:

Friday, June 07, 2019 10:51:43 PM Attachments:

RAI 4.7.3-7 Surry SLR 4.7.3 LBB TLAA.docx Paul, Eric, draft RAI attached.

Clarification call soon.

Thanks Manny

RAI 4.7.3-7 Regulatory Basis In accordance with 10 CFR 54.21(c)(1), the applicant shall provide a list of time-limited aging analyses (TLAAs), as defined in 10 CFR 54.3. The applicant shall demonstrate that: (i) the analyses remain valid for the period of extended operation; (ii) the analyses have been projected to the end of the period of extended operation; or (iii) the effects of aging on the intended function(s) will be adequately managed for the period of extended operation.

=

Background===

SLRA Section 4.7.3 addresses a TLAA on leak-before break (LBB) for the reactor coolant system (RCS) primary loop. Dominion (applicant) indicated that the LBB analysis for 80 years of operation is documented in WCAP-15550, Revision 2. WCAP-15550, Revision 2 identifies three elbow locations (locations 3, 6 and 15) as critical locations in the LBB analysis.

Issue WCAP-15550, Revision 0 (August 2000) is the basis document for the 60-year LBB analysis of the Surry plant, as indicated in Section IV.1.B.vii.2 of the Surry power uprate application dated January 27, 2010. WCAP-15550, Revision 0 indicates that location 4 is one of the critical elbow locations for the 60-year LBB analysis. In contrast, WCAP-15550, Revision 2 indicates that location 3 is one of the critical elbow locations instead of location 4.

Request Provide the basis for the change to the critical elbow location from location 4 (WCAP-15550, Revision 0) to location 3 (WCAP-15550, Revision 2) to confirm that location 3 is the highest stressed elbow location for the hot leg.