CIRCUIT ANALYSIS WORKSHEET (EX-1A)
Component ID AOV-8879-B Component Type AOV Component Description Example 1 Normal Position Open Failed Electrical Position Closed Failed Air Position Closed Function State 8879B-O-C Initial Position Open Desired Position Closed BE Code 8879B_FTC High Consequence Component Yes No Power Supplies XCP 6109 (Subpanel 3) Breaker FU-SI70 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments SIW61X Y S/O-HS SIW62X N Not Required SIW71X Y S/O-HS SIW72X N Not Required SIW73X N Not Required SIW74X Y S/O-HS SIW79X Y S/O-HS
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies None Comments Ungrounded 125VDC control circuit Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 125V D.C. Subpanel 3 MICRO SWITCH - CMC - 91O - AEA I, PTCC
( ) SS-SI70 2 POSITION MAINTAINED POS 1 H SUBPANEL 3 6A FU-SI70 1 2 5 6 1 2 5 6 H XCP6109 3
3 4 7 8 3 4 7 8 P- CLOSE OPEN TBA-56 XPN7125 G G N SS-SI70 MCB XCP6107 33ao 33bc 33bc 33ao A B A B G H G H 3 13 W
2 C 4 SPARE SPARE SPARE SPARE 3 SS-SI70 OPEN R SS-SI70 G SS-SI70 W SS-SI70 4 XCP6107 XCP6107 XCP6107 XCP6107 12 I I4 F D F Q P R SS-SI70 SS-SI70 33ac E 33bo F E F R- G- W-1 2 7 8 SPARE SPARE SPARE SPARE TBA-53 TBA-55 TBA-57 TBA-58 XPN7125 XPN7125 R R R 1 1 2 E SS-SI70 E SIW61X TBA-53 TBA-55 TBA-57 5 6 SPARE SIW62X O1 -
SIW71X NOTES:
O2 - O3 -
ELECTRICAL PENETRATION SIW72X D 1. R1=1950 - 20 WATTS, R2=1600 - 20 WATTS. D RESISTORS TO BE MOUNTED ON BLANK TERMINALS.
SIW73X 2. FOR SS-SI70 PLUG IN MODULE CONNECTION VALVE TERMINATION BOX DIAGRAM SEE DWB. IMS-28-14O-54 SIW74X C C 3. FOR LIMIT SWITCH DEVELOPMENT SEE 33ac 33bo 20 VALVE VALVE VALVE DWG. 8-208-002, SHEET 01.
ENERGIZE SIW79X VALVE D 8879B D
8879B TO OPEN 8879B C C O4 -
SEPARATION GROUP X REF. W 271C622 SHEET 387 TBA-54 XPN7125 B (IMS-41-012-387-1) B 4
FU-SI70 6A XCP6109 2
Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
SUBPANEL 3
( ) NEG AOV-8879B OPEN Elec: CLOSED Air: CLOSED OPEN - CLOSED 125V D.C. Subpanel 3 A Elementary Diagram SIZE FSCM NO DWG NO REV A
B E-1A-1 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 1 OF 2 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 LEGEND:
A - CIRCUIT NO.
RB-412 SIW79X H 1-4-12 B - NO. COND. & WIRE SIZE H 125VDC C - VOLTS RB-441 EK-B1J 1-SI70 (XRP33A-ES) D - B/M ITEM 1.0G 2- E - CONDUIT SIZE MC-CONT 3- ELEC PEN 4- (STRL PEN 725A) F - NATURE OF CIRCUIT G - WIRE MARKS G RB-412 T T G SIW71X 2-1-14 125VDC (XVT8879B-SI) EK-J2A ( ) RB-441 0.75G (XRP33A-ES) 1-SI70 TERM. BOX MC-CONT ELEC PEN SOL. VALVE FOR 4-SI70 SI 27 (STRL PEN 725)
XVT8879B F F T T T
SIW74X 1-4-12 1-SI70 125VDC 2-SIW62X EK-B1J E 1-2-12 3- E
- 4-125VDC MC-CONT RB-412 T SIW72X 2-1-14 CB-436 125VDC SIW61X (XVT8879B-SI) EK-J2A (XPN7125-MC) 1-7-12 0.75G (XCP6109) 3-SI70 125VDC MC-CONT D OPEN LIMIT SW FOR 4-SI70 Subpanel 3 MCB TERM PNL D XVT8879B P-SI70 1-SI70 4-SI70 P-T T R-G-
W-SP (2)
C C (XCP6107)
RB-412 SIW73X 2-1-14 MCB 125VDC EK-J2A B (XVT8879B-SI) 0.75G B MC-CONT 2-SI70 CLOSE LIMIT SW FOR 4-SI70 XVT8879B T T Normal Position Failed Position Functional State [ INITIAL - FINAL ]
Title OPEN Elec: CLOSED Air: CLOSED OPEN - CLOSED AOV-8879B A Block Diagram SIZE FSCM NO DWG NO REV A
B E-1A-2 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 2 OF 2 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-1B)
Component ID AOV-8879-B Component Type AOV Component Description Example 1B Normal Position Open Failed Electrical Position Closed Failed Air Position Closed Function State 8879B-O-O Initial Position Open Desired Position Open BE Code 8879B_FTRO High Consequence Component Yes No Power Supplies XCP 6109 (Subpanel 3) Breaker FU-SI70 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments FTRO requires Inter-Cable hot short SIW61X Y LOP-BF with (-) conductor SIW62X Y LOP-BF FTRO SIW71X Y LOP-BF FTRO SIW72X Y LOP-BF FTRO Requires Inter-cable hot SIW73X Y LOP-BF FTRO short with (+) conductor SIW74X Y LOP-BF FTRO SIW79X Y LOP-BF FTRO
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies None Comments Ungrounded 125VDC control circuit Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 125V D.C. Subpanel 3 MICRO SWITCH - CMC - 91O - AEA I, PTCC
( ) SS-SI70 2 POSITION MAINTAINED POS 1 H SUBPANEL 3 6A FU-SI70 1 2 5 6 1 2 5 6 H XCP6109 3
3 4 7 8 3 4 7 8 P- CLOSE OPEN TBA-56 XPN7125 G G N SS-SI70 MCB XCP6107 33ao 33bc 33bc 33ao A B A B G H G H 3 13 W
2 C 4 SPARE SPARE SPARE SPARE 3 SS-SI70 OPEN R SS-SI70 G SS-SI70 W SS-SI70 4 XCP6107 XCP6107 XCP6107 XCP6107 12 I I4 F D F Q P R SS-SI70 SS-SI70 33ac E 33bo F E F R- G- W-1 2 7 8 SPARE SPARE SPARE SPARE XPN7125 TBA-53 TBA-55 TBA-57 TBA-58 XPN7125 R R R 1 1 2 E SS-SI70 E SIW61X TBA-53 TBA-55 TBA-57 5 6 SPARE SIW62X O1 -
SIW71X NOTES:
O2 - O3 -
ELECTRICAL PENETRATION SIW72X D 1. R1=1950 - 20 WATTS, R2=1600 - 20 WATTS. D RESISTORS TO BE MOUNTED ON BLANK TERMINALS.
SIW73X 2. FOR SS-SI70 PLUG IN MODULE CONNECTION VALVE TERMINATION BOX DIAGRAM SEE DWB. IMS-28-14O-54 SIW74X C C 3. FOR LIMIT SWITCH DEVELOPMENT SEE 33ac 33bo 20 VALVE VALVE VALVE DWG. 8-208-002, SHEET 01.
ENERGIZE SIW79X VALVE D 8879B D
8879B TO OPEN 8879B C C O4 -
SEPARATION GROUP X REF. W 271C622 SHEET 387 TBA-54 XPN7125 B (IMS-41-012-387-1) B 4
FU-SI70 6A XCP6109 2
Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
SUBPANEL 3
( ) NEG AOV-8879B OPEN Elec: CLOSED Air: CLOSED OPEN - OPEN 125V D.C. Subpanel 3 A Elementary Diagram SIZE FSCM NO DWG NO REV A
B E-1B-1 0 DRAWN TAYLOR, GABRIEL ISSUED SCALE 1:1 SHEET 1 OF 2 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 LEGEND:
A - CIRCUIT NO.
RB-412 SIW79X H 1-4-12 B - NO. COND. & WIRE SIZE H 125VDC C - VOLTS RB-441 EK-B1J 1-SI70 (XRP33A-ES) D - B/M ITEM 1.0G 2- E - CONDUIT SIZE MC-CONT 3- ELEC PEN 4- (STRL PEN 725A) F - NATURE OF CIRCUIT G - WIRE MARKS G RB-412 T T G SIW71X 2-1-14 125VDC (XVT8879B-SI) EK-J2A ( ) RB-441 0.75G (XRP33A-ES) 1-SI70 TERM. BOX MC-CONT ELEC PEN SOL. VALVE FOR 4-SI70 SI 27 (STRL PEN 725)
XVT8879B F F T T T
SIW74X 1-4-12 1-SI70 125VDC 2-SIW62X EK-B1J E 1-2-12 3- E
- 4-125VDC MC-CONT RB-412 T SIW72X 2-1-14 CB-436 125VDC SIW61X (XVT8879B-SI) EK-J2A (XPN7125-MC) 1-7-12 0.75G (XCP6109) 3-SI70 125VDC MC-CONT D OPEN LIMIT SW FOR 4-SI70 Subpanel 3 MCB TERM PNL D XVT8879B P-SI70 1-SI70 4-SI70 P-T T R-G-
W-SP (2)
C C (XCP6107)
RB-412 SIW73X 2-1-14 MCB 125VDC EK-J2A B (XVT8879B-SI) 0.75G B MC-CONT 2-SI70 CLOSE LIMIT SW FOR 4-SI70 XVT8879B T T Normal Position Failed Position Functional State [ INITIAL - FINAL ]
Title OPEN Elec: CLOSED Air: CLOSED OPEN - OPEN AOV-8879B A Block Diagram SIZE FSCM NO DWG NO REV A
B E-1B-2 0 DRAWN TAYLOR, GABRIEL ISSUED SCALE 1:1 SHEET 2 OF 2 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-2A)
Component ID MOV-8112-A Component Type MOV Component Description RCP Seal Water Return Isolation Normal Position Closed Failed Electrical Position As-Is Failed Air Position N/A Function State 8112A-C-O Initial Position Closed Desired Position Open BE Code RC-8112_FTO High Consequence Component Yes No Power Supplies MCC-1B Breaker 11BD Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 1VAFU-T4A Y N LOC-BF, S/C-HS 1VAFU-T4B Y N LOC-BF, S/C-HS 1VAFU-T4C Y N LOC-BF 1VAFU-T4D Y N LOC-BF 1VAFU-T4F Y N LOC-BF, S/C-HS 1VAFU-T4P Y N LOP 3-Phase power cable 1VAFU-T4Q Y N LOP 3-Phase power cable 1VAFU-T4Z Y N LOC-BF, S/C-HS
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies CIAS-Phase A, K607: Spurious CIAS-Phase A will cause spurious closure of MOV-8112-A. No direct On-Scheme hot short required to produce spurious close signal.
Comments Hot shorts on Cables A, B, F, and Z bypass limit and torque switches, which could cause permanent valve damage.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
CIRCUIT ANALYSIS WORKSHEET (EX-2B)
Component ID MOV-8112-A Component Type MOV Component Description RCP Seal Water Return Isolation Normal Position Closed Failed Electrical Position As-Is Failed Air Position N/A Function State 8112A-C-C Initial Position Closed Desired Position Closed BE Code RC-8112_FTRC High Consequence Component Yes No Power Supplies MCC-1B Breaker 11BD Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 1VAFU-T4A N N NR 1VAFU-T4B Y N S/O-HS Conductor 01 1VAFU-T4C N N NR 1VAFU-T4D N N NR 1VAFU-T4F N N NR 1VAFU-T4P N N NR 3-Phase power cable 1VAFU-T4Q N N NR 3-Phase power cable 1VAFU-T4Z Y N S/O-HS Conductor 01
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies No dependencies - valve already closed and no interlocks in OPEN circuit Comments Hot shorts on Cables B and Z bypass limit and torque switches, which could cause permanent valve damage.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
CIRCUIT ANALYSIS WORKSHEET (EX-2C)
Component ID MOV-8112-A Component Type MOV Component Description RCP Seal Water Return Isolation Normal Position Closed Failed Electrical Position As-Is Failed Air Position N/A Function State 8112A-O-C Initial Position Open Desired Position Closed BE Code RC-8112_FTC High Consequence Component Yes No Power Supplies MCC-1B Breaker 11BD Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 1VAFU-T4A Y N LOC-BF 1VAFU-T4B Y N LOC-BF, S/O-HS 1VAFU-T4C Y N LOC-BF 1VAFU-T4D Y N LOC-BF 1VAFU-T4F Y N LOC-BF 1VAFU-T4P Y N LOP 3-Phase power cable 1VAFU-T4Q Y N LOP 3-Phase power cable 1VAFU-T4Z Y N LOC-BF, S/O-HS
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies CIAS-Phase A, K607: CIAS-Phase A required operational for auto-function to close MOV-8112-A.
CIAS-Phase A, K813 Test: Spurious opening of CIAS-Phase A test contact K813 will prevent auto-function of CIAS-Phase A.
Comments Hot shorts on Cables A and Z bypass limit and torque switches, which could cause permanent valve damage.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
CIRCUIT ANALYSIS WORKSHEET (EX-3A)
Component ID MOV-8888 Component Type MOV Component Description Example 3A Normal Position Open Failed Electrical Position As-Is Failed Air Position N/A Function State 8888-O-O Initial Position Open Desired Position Open BE Code 8888_FTRO High Consequence Component Yes No Power Supplies MCC-1DA2Y Breaker 13DG Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments SIC241A N SIC242A N SIC243A Y S/C-HS Hot short on conductor 03 causes SIC244A Y S/C-HS MOV to close
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies Comments Grounded Circuit with individual control power transformer (CPT)
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 MCC XFMRP H 1 2 H COMPONENT RELATED NOTES MCC MCC MCC 01. TO ESF MONITOR LIGHTS, SEE B208066, SHT.MI09 480/120V 21 FU 1 GND 22 22 02. TO REDUNDANT LIGHT, SEE B208095, SHT. SI88
- 03. TO NORMAL INDICATING LIGHTS ON POWER LOCKOUT, MCC XFMRS MCC SEE B208095, SHT. SI30 MCC MCC Term. Panel MCC 04. SET 90% (+5% / 0%) OPEN
- 05. SET AT 1 49 33AO SSSI27 420 42C 28 29 15 06 TBD44 TBD51 03 23 G G MCC MCC 1 1A XPN7108 7 8 XPN7108 MCC MCC XVG888A XCP6107 MCC MCC GENERAL DRAWING NOTES 33TC SSSI27 42C A. REFERENCE WESTINGHOUSE DWG 27IC622 SHT. 398, (IMS41012398)
TBD43 05 24 B. DEVICES INDICATED IN MCC ARE LOCATED IN 53 55 1 2 XPN7108 MCC XVG8888A XCP6107 MCC XMC1DA27 UNIT#13DG; POWER SUPPLIED VIA UNIT 13AC C. FOR LIMIT SWITCH DEVELOPMENT, SEE B208002, SHT. 01 F 33B90 33BO SSSI27 42C 420 F 11 TBD48 TBD49 12 25 LAST WIRE MARK NUBMER 22 T1 T2 T3 5 5A 4 4A XPN7108 3 4 XPN7108 MCC XVG8888A XVG8888A XCP6107 MCC NOTE 04 33TO MOV-8888 SSSI27 420 TBD47 10 26 43 45 5 6 XPN7108 MCC SIC 241A XVG8888A XCP6107 MCC E NOTE 05 SIC 242A E
TBD52 RESISTOR TBD52 TBD50 SIC 243A M XPN7108 XPN7108 W W XPN7108 XPN7108 XCP6107 XCP6107 SIC 244A MOV8888 Term. Panel Term. Panel MCB D D 42C 42C 42O 42O 211 212 213 214 230 231 232 233 SSSI27 1 2 5 6 1 2 5 6 1 2 5 6 SPARE SPARE SPARE SPARE 3 4 7 8 3 4 7 8 3 4 7 8 33AO 33BO 33B90 33B90 33B90 33A0 33A0 C CLOSE OPEN C
2 2A 3 3A 6 6A 7 7A 8 8A 9 9A 10 10A SPARE TO SI30 SPARE SPARE SPARE SPARE SPARE MICROSWITCH CMC #910PGD533, PTCC NOTE 03 SPRING RETURN OPEN AND CLOSE TO NORMAL 33BO 33BO 33BC 33BC 33AC 33AC MTR HTR 75W 11 11A 12 12A 13 13A 14 14A 15 15A 16 16A CHANNEL A SPARE MON LT SPARE TO SI30 SPARE SPARE B
SPARE NOTE 01 NOTE 03 NUCLEAR SAFETY RELATED B 33AO 33AO 33AC 33AC 33BC 33BC 33BC 33BC SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
CHANNEL B CONTACTS MOV-8888 Solution OPEN Elec: AS-IS Air: N/A OPEN - OPEN STEM MOUNTED LIMIT SWITCH Elementary Diagram A SIZE FSCM NO DWG NO REV A DRAWN HOMER B E3A1 0 ISSUED SCALE SHEET 1 OF 2 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 NUCLEAR 1 VIA PBSIG, PBSI5 & PGSI4, PBSI48 H
SAFETY 2 VIA PBSI10, PBSI9 & PBSI8, PBSI49, XX3485A, 3486A, 3487A, 3488A & 3489A H
RELATED 3 TYPING NOTE 2 (SS200105) #8 G 095N4 G AB412 AB412 BLANK CIRCUITS : SIC244 THRU SIC250 SIC241A 1 3 134 NEXT CIRCUIT : SIC251 (XMC1DA27ES) 480V T1 SI27 (XVG8888ASI)
EKA3F T2 ENGINEERED 2.0G T3 LOW HEAD TO COLD SAFETY APPWR LEG CROSS TIE F FEATURES F VALVE 8888A MCC 1DA27 UNIT 13DG 066 SH. W44 6 SI27 095 SH. C27 SIC 241A 11 SIC 242A E E SIC242A 1712 2
4 SP SIC 243A 120V EKBIL SIC 244A 1.25G 15 ACCONT D D 3 SI27 3 SI27 5 5 2 SP 2 SP 6 6 CB448 10 CB486 SIC243A 10 11 C 11012 12 C 11 SIC244A LEGEND:
120V 12 (XPN7108MC) 11012 22 A - CIRCUIT NO.
EKBIM 22 MCB TERM PNL 120V 15 (XCP6107) B - NO. COND. & WIRE SIZE 15 ACCONT MCB C - VOLTS D - B/M ITEM E - CONDUIT SIZE B B F - NATURE OF CIRCUIT G - WIRE MARKS Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
OPEN Elec: AS-IS Air: N/A OPEN - OPEN A
CHANNEL A MOV-8888 Solution Block Diagram SIZE FSCM NO DWG NO REV A DRAWN HOMER B E3A2 0 ISSUED SCALE SHEET 2 OF 2 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-3B)
Component ID MOV-8888 Component Type MOV Component Description Example 3B Normal Position Open Failed Electrical Position As-Is Failed Air Position N/A Function State 8888-O-C Initial Position Open Desired Position Closed BE Code 8888_FTC High Consequence Component Yes No Power Supplies MCC-1DA2Y Breaker 13DG Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments SIC241A Y LOP Breaker trip FTC SIC242A Y LOP-BF FTC SIC243A Y LOP-BF FTC SIC244A Y LOP-BF FTC
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies Comments Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 MCC XFMRP H 1 2 H COMPONENT RELATED NOTES MCC MCC MCC 01. TO ESF MONITOR LIGHTS, SEE B208066, SHT.MI09 480/120V 21 FU 1 GND 22 22 02. TO REDUNDANT LIGHT, SEE B208095, SHT. SI88
- 03. TO NORMAL INDICATING LIGHTS ON POWER LOCKOUT, MCC XFMRS MCC SEE B208095, SHT. SI30 MCC MCC Term. Panel MCC 04. SET 90% (+5% / 0%) OPEN
- 05. SET AT 1 49 33AO SSSI27 420 42C 28 29 15 06 TBD44 TBD51 03 23 G G MCC MCC 1 1A XPN7108 7 8 XPN7108 MCC MCC XVG888A XCP6107 MCC MCC GENERAL DRAWING NOTES 33TC SSSI27 42C A. REFERENCE WESTINGHOUSE DWG 27IC622 SHT. 398, (IMS41012398)
TBD43 05 24 B. DEVICES INDICATED IN MCC ARE LOCATED IN 53 55 1 2 XPN7108 MCC XVG8888A XCP6107 MCC XMC1DA27 UNIT#13DG; POWER SUPPLIED VIA UNIT 13AC C. FOR LIMIT SWITCH DEVELOPMENT, SEE B208002, SHT. 01 F 33B90 33BO SSSI27 42C 420 F 11 TBD48 TBD49 12 25 LAST WIRE MARK NUBMER 22 T1 T2 T3 5 5A 4 4A XPN7108 3 4 XPN7108 MCC XVG8888A XVG8888A XCP6107 MCC NOTE 04 33TO MOV-8888 SSSI27 420 TBD47 10 26 43 45 5 6 XPN7108 MCC SIC 241A XVG8888A XCP6107 MCC E NOTE 05 SIC 242A E
TBD52 RESISTOR TBD52 TBD50 SIC 243A M XPN7108 XPN7108 W W XPN7108 XPN7108 XCP6107 XCP6107 SIC 244A MOV8888 Term. Panel Term. Panel MCB D D 42C 42C 42O 42O 211 212 213 214 230 231 232 233 SSSI27 1 2 5 6 1 2 5 6 1 2 5 6 SPARE SPARE SPARE SPARE 3 4 7 8 3 4 7 8 3 4 7 8 33AO 33BO 33B90 33B90 33B90 33A0 33A0 C CLOSE OPEN C
2 2A 3 3A 6 6A 7 7A 8 8A 9 9A 10 10A SPARE TO SI30 SPARE SPARE SPARE SPARE SPARE MICROSWITCH CMC #910PGD533, PTCC NOTE 03 SPRING RETURN OPEN AND CLOSE TO NORMAL 33BO 33BO 33BC 33BC 33AC 33AC MTR HTR 75W 11 11A 12 12A 13 13A 14 14A 15 15A 16 16A CHANNEL A SPARE MON LT SPARE TO SI30 SPARE SPARE B
SPARE NOTE 01 NOTE 03 NUCLEAR SAFETY RELATED B 33AO 33AO 33AC 33AC 33BC 33BC 33BC 33BC SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
CHANNEL B CONTACTS MOV-8888 OPEN Elec: AS-IS Air: N/A OPEN - CLOSED STEM MOUNTED LIMIT SWITCH Elementary Diagram A SIZE FSCM NO DWG NO REV A DRAWN HOMER B E3B1 0 ISSUED SCALE SHEET 1 OF 2 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 NUCLEAR 1 VIA PBSIG, PBSI5 & PGSI4, PBSI48 H
SAFETY 2 VIA PBSI10, PBSI9 & PBSI8, PBSI49, XX3485A, 3486A, 3487A, 3488A & 3489A H
RELATED 3 TYPING NOTE 2 (SS200105) #8 G 095N4 G AB412 AB412 BLANK CIRCUITS : SIC244 THRU SIC250 SIC241A 1 3 134 NEXT CIRCUIT : SIC251 (XMC1DA27ES) 480V T1 SI27 (XVG8888ASI)
EKA3F T2 ENGINEERED 2.0G T3 LOW HEAD TO COLD SAFETY APPWR LEG CROSS TIE F FEATURES F VALVE 8888A MCC 1DA27 UNIT 13DG 066 SH. W44 6 SI27 095 SH. C27 SIC 241A 11 SIC 242A E E SIC242A 1712 2
4 SP SIC 243A 120V EKBIL SIC 244A 1.25G 15 ACCONT D 3 SI27 D 5
3 SI27 2 SP 5
2 SP 6 10 6 CB448 11 CB486 C
SIC243A 10 12 C 11012 11 SIC244A 22 LEGEND:
120V 12 (XPN7108MC) 11012 15 A - CIRCUIT NO.
EKBIM 22 MCB TERM PNL 120V (XCP6107) B - NO. COND. & WIRE SIZE 15 ACCONT MCB C - VOLTS D - B/M ITEM E - CONDUIT SIZE B B F - NATURE OF CIRCUIT G - WIRE MARKS Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
OPEN Elec: AS-IS Air: N/A OPEN - CLOSED A
CHANNEL A MOV-8888 Block Diagram SIZE FSCM NO DWG NO REV A DRAWN HOMER B E3B1 0 ISSUED SCALE SHEET 2 OF 2 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-4A)
Component ID AOV-2869-A Component Type AOV Component Description Example 4A Normal Position Closed Failed Electrical Position Closed Failed Air Position Closed Function State 2869A-C-C Initial Position Closed Desired Position Closed BE Code 2869A_FTRC High Consequence Component Yes No Power Supplies Subpanel 11 Breaker FU-MS40 Reqd Subpanel 12 Breaker FU-MS43 Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments MSW201A - - NR MSW202A Y Y S/O-HS MSW203A Y Y S/O-HS MSW204A Y Y S/O-HS MSW205A - - NR MSW277A - - NR MSW278A Y Y S/O-HS MSW231B Y Y S/O-HS MSW232B Y Y S/O-HS MSW233B Y Y S/O-HS MSW234B Y Y S/O-HS MSW235B Y Y S/O-HS MSW236B Y Y S/O-HS
Cable ID Reqd? MHS? Fault Consequence Comments MSW237B Y Y S/O-HS MSW238B - - NR MSW266B Y Y S/O-HS MSW267B - - NR Equipment Dependencies K623 opens on MS Line A bypass isolation - no impact on desired position Comments This valve requires two independent hot shorts to produce a spurious operation. Coincident hot shorts must occur on 20A and 20B solenoid circuit to permit air to the AOV.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 125V D.C. TBA-24 OXPN7135
( ) 1A 1C 1D MS40X POS XCP6114 MICRO SWITCH - CMC - 91O - PGD 3, PTCC H NOTE 6 1 A C D H FU-MS40 SS-MS40 3 POS. SPRING RETURN TO CTR.
6A TBA-25 OXPN7135 XCP6114 SPARE SPARE COMPUTER 1 2 5 6 1 2 5 6 1 2 5 6 3 Y1954D P- 3 4 7 8 3 4 7 8 3 4 7 8 SEPARATION GROUP X 1 CLOSE AUTO OPEN TBA-13 XPN7115 MS40X MCB G 2 XCP6114 G b SS-MS40 XCP6114 3 13 W 33ao 33bc 33bc 2 C 4 3 SS-MS40 5 OPEN AUTO SS-MS40 R SS-MS40 G SS-MS40 W SS-MS40 4 XCP6114 6 XCP6114 XCP6114 XCP6114 XCP6114 SPARE SPARE SPARE 12 I I4 F T F 5 N C P TBA-17 XPN7115 SS-MS40 SS-MS40 33ac 33bo TBA-15 XPN7115 XPN7115 O2 - TBA-12 TBA-14 TBA-16 1 2 7 8 SPARE SPARE ESF SPARE O1 - MONITOR LT.
TB626-3 XPN7010 R R R 1 1 2 XCP6104 E 9 K623 SHT. MI41 E XPN7010 TBA-12 TBA-14 TBA-16 10 NOTE 2 TB626-4 XPN7010 TBA-11 XPN7115 O3 -
TBA-18 XPN7115 O4 - O5 - O6 - MSW201A D NOTES: D 33ao MSW202A 33ac 33bo 1. R1=1950, R2=1600 RESISTORS TO BE MOUNTED ON VALVE VALVE VALVE BLANK TERMINALS.
XVT-2869A XVT-2869A MSW203A XVT-2869A 2. K623 CONTACT OPENS ON MAIN STEAM LINE A BYPASS ISOLATION.
MSW204A 3. FOR SS-MS40 PLUG IN MODULE CONNECTION DIAGRAM SEE DWG. IMS-28-140-61 MSW205A 4. FOR LIMIT SWITCH DEVELOPMENT SEE C C DWG. 8-208-002, SHEET 01.
20-A ENERGIZE MSW277A 5. TO OPEN MAIN STEAM LINE BYPASS ISOLATION VALVE TO OPEN SOV-20A VALVES BOTH SOLENOIDS 20-A AND 20-B MUST BE XVT-2869A NOTE 5 MSW278A ENERGIZED, SEE B-817-002.
- 6. FOR APPENDIX R POWER DISCONNECT SWITCHES DS-17 IN XPN7106 AND DS-3 ON XCP6113 SUBPANEL 19A, REFER TO ONE LINE DIAG. E-206-080 TBA-19 XPN7115 B B 4 20-B 20-A SEPARATION GROUP A FU-MS40 6A NUCLEAR XCP6114 FC 2 SAFETY RELATED Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
( ) NEG 2869A AOV-2869A CLOSED Elec: CLOSED Air: CLOSED CLOSED- CLOSED A NOTE 6 Elementary Diagram SIZE FSCM NO DWG NO REV A
Subpanel 11 B E-4A-1 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 1 OF 4 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 125V D.C. W SELECTOR SW. - UNIT CAT. # OT1V9C - CAM #9 H ( ) SS-MS43 3 POS. SPRING RETURN TO CTR, STANDARD HANDLE. H POS NOTE 5 6A FU-MS43 1 2 5 6 1 2 5 6 1 2 5 6 XCP6114 MSW231B MSW236B P- MSW232B MSW237B 3 4 7 8 3 4 7 8 3 4 7 8 TBA-45 XPN7119 MSW233B MSW238B CLOSE AUTO OPEN G MSW234B MSW266B G N Q 7 SS-MS43 AUTO 1 SS-MS43 MSW235B MSW267B OPEN SS-MS43 SS-MS43 33bcH 8 XCP6114 OPEN 2 XCP6114 G S P 5 6 3 4 SPARE SPARE SPARE TBA-46 XPN7119 TBA-47 XPN7119 (TYPICAL F O3 -
EACH VALVE) F O1 - 33ac 33bc C D A B TB626-3 XPN7020 TB626-5 XPN7020 TB626-7 SPARE SPARE XPN7020 9 K623 11 K623 13 K623 TYPICAL EACH VALVE XPN7020 XPN7020 XPN7020 E 10 NOTE 3 12 NOTE 3 14 33ac 33bo 33ao E NOTE 3 E F A B E F TB626-4 XPN7020 TB626-6 XPN7020 TB626-8 XPN7020 O4 - O5 - O6 - SPARE SPARE SPARE TBA-50 XPN7119 TBA-48 XPN7119 TBA-49 XPN7119 TYPICAL EACH VALVE G C G C G C 33bo 33ao 33bo 33ao 33bo 33ao XVT-2869A XVT-2869A XVT-2869B XVT-2869B XVT-2869C XVT-2869C NOTES:
D H D H H D D D O7 - O8 - O9 -
- 1. FOR SS-MS43 PLUG IN MODULE CONNECTION DIAGRAM SEE DWG. IMS-28-140-121 (LOWER).
20-B 20-B 20-B 2. FOR LIMIT SWITCH DEVELOPMENT SEE ENERGIZE TO OPEN VALVE ENERGIZE TO OPEN ENERGIZE TO OPEN DWG. 8-208-002, SHEET 01.
VALVE VALVE XVT-2869A XVT-2869B XVT-2869C 3. K623 CONTACTS OPEN ON MAIN STEAM BYPASS ISOLATION.
C NOTE 4 NOTE 4 NOTE 4 4. TO OPEN MAIN STEAM LINE BYPASS ISOLATION C O2 - VALVES BOTH SOLENOIDS 20-A AND 20-B MUST BE ENERGIZED, SEE B-817-002.
- 6. FOR APPENDIX R POWER DISCONNECT SWITCHES TBA-51 XPN7119 DS-17 IN XPN7106 AND DS-3 ON XCP6113 SUBPANEL 19A, REFER TO ONE LINE DIAG. E-206-080 4
FU-MS43 6A B XCP6114 B 2
20 20 SEPARATION GROUP B NUCLEAR FC SAFETY RELATED
( ) NEG NOTE 5 Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
2869A,B,C CLOSED Elec: CLOSED Air: CLOSED CLOSED - CLOSED AOV-2869A A Elementary Diagram SIZE FSCM NO DWG NO REV A
B E-4A-2 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 2 OF 4 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 NUCLEAR H
SAFETY H RELATED G MSW277A G 1-4-12 (XCP 6114) 125VDC (XCP 6114)
CHANNEL A MCB MSW278A Subpanel 11 1-9-12 IB-436 125VDC F F CB-436 MSW201A CB-436 MSW202A 1-2-12 1-5-12 2 1-MS40 125VDC 125VDC 3-(XPN7010-SG) EK-B1K SOLID STATE EK-B1G (XPN7115-MC) 4-
- 1-MS40 1.0G PROT. SYS. CAB. 3-MS40 MCB TERM PNL AC-XVM2869A 5-E AC-XVM2869A IB-436 E TRAIN A 6- MSW204A 4-1-14 1-MS40 (OUTPUT SECT.) T T T 125VDC (XVT2869A-MS)
(-) 5K-J2A 3-HERMETIC CONN.
SPLICE BOX 0.75G 5-AT OPEN LIM. SW.
AC-XVM2869A 6-MS 21 FOR XVT2869A D T T -TRAIN A D IB-436 MSW203A 1-4-14 125VDC 1-MS40 MSW205A IB-436 (XVT2869A-MS) VFC-135 HERMETIC 6-MS40 2-1-14 1 0.75G 125VDC (XVT2869A-MS)
CONNECTOR AT AC-XVM2869A 2 SP EK-J2A HERMETIC CONN.
C SOL. VALVE 20A. 0.75G 4-MS40 AT CLOSE LIM. SW. C T T AC-XVM2869A 6-MS40 FOR XVT2869A
- TRAIN A T T 066-W17 066-W17 B LEGEND: B A - CIRCUIT NO.
B - NO. COND. & WIRE SIZE C - VOLTS 1 VIA XX-3518A D - B/M ITEM E - CONDUIT SIZE Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
CLOSED Elec: CLOSED Air: CLOSED CLOSED - CLOSED F - NATURE OF CIRCUIT AOV-2869A A VIA XX-3567A Block Diagram SIZE FSCM NO DWG NO REV A
2 G - WIRE MARKS B E-4A-3 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 3 OF 4 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 CHANNEL B NUCLEAR H
IB-436 IB-436 SAFETY H (XVT2869A-MS)
MSW231B 1-4-14 MSW235B 4-1-14 8-MS43 IB-436 RELATED 125VDC 125VDC (XVT2869B-MS)
HERMETIC EK-J2A 8-MS43 VFC-135 2 SP HERMETIC CONN.
CONNECTOR AT 0.75G 0.75G 1-MS43 7-MS43 AT OPEN LIM. SW.
SOL. VALVE 20B BC-XVM2869A AC-XVM2869B 5-MS43 G 2-MS43 FOR XVT2869B G T T T T -TRAIN B IB-436 MSW232B 5 MSW236B 1 2 3 4 IB-436 (XVT2869B-MS) 2-1-14 & 1-4-14 4-1-12 9-MS43 125VDC 125VDC (XVT2869C-MS)
HERMETIC EK-J2A & VFC-135 EK-J2A 9-MS43 CONNECTOR AT HERMETIC CONN.
F 0.75G 8-MS43 0.75G 1-MS43 F SOL. VALVE 20B AT OPEN LIM. SW.
BC-XVM2869B 2-MS43 AC-XVM2869C 6-MS43 FOR XVT2869C T T T T -TRAIN B IB-436 (-)
MSW233B 1 2 3 6 SPLICE BOX (XVT2869C-MS) 1-2-12 & 1-4-14 MS 24 125VDC 1-MS43 E HERMETIC MSW237B 1 CB-436 MSW238B CB-436 E EK-B1G & VFC-135 1-7-12 2-MS43 1-4-12 CONNECTOR AT 0.75G 125VDC 2SP 125VDC 3-MS43 (XPN7020-SG) 9-MS43 SOL. VALVE 20B BC-XVM2869C EK-BIL 4- EK-BIL 4- SOLID STATE 2-MS43 (XPN7119-MC) 1.25G 5- - 5- PROT. SYS. CAB.
T T BC-XVM2869A,B&C MCB TERM. PNL BC-XVM2869A,B&C 6- 6- - TRAIN B IB-436 MSW234B (OUTPUT SECT.)
4-1-14 T T T T D 125VDC 1-MS43 D (XVT2869A-MS)
EK-J2A 4-MS43 HERMETIC 0.75G 7-MS43 2SP CONNECTOR AT BC-XVM2869A MSW266B 7-MS43 P-MS43 OPEN LIM. SW. 1-9-12 T T (XCP6114) 125VDC 2-MS43 (XCP6114)
MCB Subpanel 12 C MSW267B C P-MS43 1-4-12 1-MS43 125VDC 3-MS43 LEGEND:
1 VIA XX-2139B 6SP A - CIRCUIT NO.
B - NO. COND. & WIRE SIZE 2 VIA XX-2451B C - VOLTS B D - B/M ITEM B 3 VIA XX-3570B E - CONDUIT SIZE F - NATURE OF CIRCUIT 4 SPLICE 4-1-14 WIRES, (EKJ9A), TO 1-4-12 WIRE IN SB-MS49 G - WIRE MARKS 5 VIA SB-MS131, CABLE FROM SB-MS131 TO Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
CLOSED Elec: CLOSED Air: CLOSED CLOSED - CLOSED SOLENOID IS 1-4-14 (VFC-135) AOV-2869A A Block Diagram SIZE FSCM NO DWG NO REV A
6 VIA SB-MS127. CABLE FROM SB-MS127 TO B E-4A-4 0 DRAWN HOMER SOLENOID IS 1-4-14 (VFC-135)
ISSUED SCALE 1:1 SHEET 4 OF 4 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-4B)
Component ID AOV-2869-A Component Type AOV Component Description Example 4B Normal Position Closed Failed Electrical Position Closed Failed Air Position Closed Function State 2869A-C-O Initial Position Closed Desired Position Open BE Code 2869A_FTO High Consequence Component Yes No Power Supplies Subpanel 11 Breaker FU-MS40 Reqd Subpanel 12 Breaker FU-MS43 Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments MSW201A Y N LOC-FTO MSW202A Y N LOC-FTO MSW203A Y N LOC-FTO MSW204A Y N LOC-FTO MSW205A Y N LOC-FTO MSW277A Y N LOC-FTO MSW278A Y N LOC-FTO MSW231B Y N LOC-FTO MSW232B Y N LOC-FTO MSW233B Y N LOC-FTO MSW234B Y N LOC-FTO MSW235B Y N LOC-FTO MSW236B Y N LOC-FTO
Cable ID Reqd? MHS? Fault Consequence Comments MSW237B Y N LOC-FTO MSW238B Y N LOC-FTO MSW266B Y N LOC-FTO MSW267B Y N LOC-FTO Equipment Dependencies K623 opens on MS Line A bypass isolation - spurious opening of contact could impact desired position.
Comments Both A & B train SOVs must remain functional to satisfy desired position.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 125V D.C. TBA-24 OXPN7135
( ) 1A 1C 1D MS40X POS XCP6114 MICRO SWITCH - CMC - 91O - PGD 3, PTCC H NOTE 6 1 A C D H FU-MS40 SS-MS40 3 POS. SPRING RETURN TO CTR.
6A TBA-25 OXPN7135 XCP6114 SPARE SPARE COMPUTER 1 2 5 6 1 2 5 6 1 2 5 6 3 Y1954D P- 3 4 7 8 3 4 7 8 3 4 7 8 SEPARATION GROUP X 1 CLOSE AUTO OPEN TBA-13 XPN7115 MS40X MCB G 2 XCP6114 G b SS-MS40 XCP6114 3 13 W 33ao 33bc 33bc 2 C 4 3 SS-MS40 5 OPEN AUTO SS-MS40 R SS-MS40 G SS-MS40 W SS-MS40 4 XCP6114 6 XCP6114 XCP6114 XCP6114 XCP6114 SPARE SPARE SPARE 12 I I4 F T F 5 N C P TBA-17 XPN7115 SS-MS40 SS-MS40 33ac 33bo TBA-15 XPN7115 XPN7115 O2 - TBA-12 TBA-14 TBA-16 1 2 7 8 SPARE SPARE ESF SPARE O1 - MONITOR LT.
TB626-3 XPN7010 R R R 1 1 2 XCP6104 E 9 K623 SHT. MI41 E XPN7010 TBA-12 TBA-14 TBA-16 10 NOTE 2 TB626-4 XPN7010 TBA-11 XPN7115 O3 -
TBA-18 XPN7115 O4 - O5 - O6 - MSW201A D NOTES: D 33ao MSW202A 33ac 33bo 1. R1=1950, R2=1600 RESISTORS TO BE MOUNTED ON VALVE VALVE VALVE BLANK TERMINALS.
XVT-2869A XVT-2869A MSW203A XVT-2869A 2. K623 CONTACT OPENS ON MAIN STEAM LINE A BYPASS ISOLATION.
MSW204A 3. FOR SS-MS40 PLUG IN MODULE CONNECTION DIAGRAM SEE DWG. IMS-28-140-61 MSW205A 4. FOR LIMIT SWITCH DEVELOPMENT SEE C C DWG. 8-208-002, SHEET 01.
20-A ENERGIZE MSW277A 5. TO OPEN MAIN STEAM LINE BYPASS ISOLATION VALVE TO OPEN SOV-20A VALVES BOTH SOLENOIDS 20-A AND 20-B MUST BE XVT-2869A NOTE 5 MSW278A ENERGIZED, SEE B-817-002.
- 6. FOR APPENDIX R POWER DISCONNECT SWITCHES DS-17 IN XPN7106 AND DS-3 ON XCP6113 SUBPANEL 19A, REFER TO ONE LINE DIAG. E-206-080 TBA-19 XPN7115 B B 4 20-B 20-A SEPARATION GROUP A FU-MS40 6A NUCLEAR XCP6114 FC 2 SAFETY RELATED Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
( ) NEG 2869A AOV-2869A CLOSED Elec: CLOSED Air: CLOSED CLOSED- OPEN A NOTE 6 Elementary Diagram SIZE FSCM NO DWG NO REV A
Subpanel 11 B E-4B-1 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 1 OF 4 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 125V D.C. W SELECTOR SW. - UNIT CAT. # OT1V9C - CAM #9 H ( ) SS-MS43 3 POS. SPRING RETURN TO CTR, STANDARD HANDLE. H POS NOTE 5 6A FU-MS43 1 2 5 6 1 2 5 6 1 2 5 6 XCP6114 MSW231B MSW236B P- MSW232B MSW237B 3 4 7 8 3 4 7 8 3 4 7 8 TBA-45 XPN7119 MSW233B MSW238B CLOSE AUTO OPEN G MSW234B MSW266B G N Q 7 SS-MS43 AUTO 1 SS-MS43 MSW235B MSW267B OPEN SS-MS43 SS-MS43 33bcH 8 XCP6114 OPEN 2 XCP6114 G S P 5 6 3 4 SPARE SPARE SPARE TBA-46 XPN7119 TBA-47 XPN7119 (TYPICAL F O3 -
EACH VALVE) F O1 - 33ac 33bc C D A B TB626-3 XPN7020 TB626-5 XPN7020 TB626-7 SPARE SPARE XPN7020 9 K623 11 K623 13 K623 TYPICAL EACH VALVE XPN7020 XPN7020 XPN7020 E 10 NOTE 3 12 NOTE 3 14 33ac 33bo 33ao E NOTE 3 E F A B E F TB626-4 XPN7020 TB626-6 XPN7020 TB626-8 XPN7020 O4 - O5 - O6 - SPARE SPARE SPARE TBA-50 XPN7119 TBA-48 XPN7119 TBA-49 XPN7119 TYPICAL EACH VALVE G C G C G C 33bo 33ao 33bo 33ao 33bo 33ao XVT-2869A XVT-2869A XVT-2869B XVT-2869B XVT-2869C XVT-2869C NOTES:
D H D H H D D D O7 - O8 - O9 -
- 1. FOR SS-MS43 PLUG IN MODULE CONNECTION DIAGRAM SEE DWG. IMS-28-140-121 (LOWER).
20-B 20-B 20-B 2. FOR LIMIT SWITCH DEVELOPMENT SEE ENERGIZE TO OPEN VALVE ENERGIZE TO OPEN ENERGIZE TO OPEN DWG. 8-208-002, SHEET 01.
VALVE VALVE XVT-2869A XVT-2869B XVT-2869C 3. K623 CONTACTS OPEN ON MAIN STEAM BYPASS ISOLATION.
C NOTE 4 NOTE 4 NOTE 4 4. TO OPEN MAIN STEAM LINE BYPASS ISOLATION C O2 - VALVES BOTH SOLENOIDS 20-A AND 20-B MUST BE ENERGIZED, SEE B-817-002.
- 6. FOR APPENDIX R POWER DISCONNECT SWITCHES TBA-51 XPN7119 DS-17 IN XPN7106 AND DS-3 ON XCP6113 SUBPANEL 19A, REFER TO ONE LINE DIAG. E-206-080 4
FU-MS43 6A B XCP6114 B 2
20 20 SEPARATION GROUP B NUCLEAR FC SAFETY RELATED
( ) NEG NOTE 5 Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
2869A,B,C CLOSED Elec: CLOSED Air: CLOSED CLOSED - OPEN AOV-2869A A Elementary Diagram SIZE FSCM NO DWG NO REV A
B E-4B-2 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 2 OF 4 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 NUCLEAR H
SAFETY H RELATED G MSW277A G 1-4-12 (XCP 6114) 125VDC (XCP 6114)
CHANNEL A MCB MSW278A Subpanel 11 1-9-12 IB-436 125VDC F F CB-436 MSW201A CB-436 MSW202A 1-2-12 1-5-12 2 1-MS40 125VDC 125VDC 3-(XPN7010-SG) EK-B1K SOLID STATE EK-B1G (XPN7115-MC) 4-
- 1-MS40 1.0G PROT. SYS. CAB. 3-MS40 MCB TERM PNL AC-XVM2869A 5-E AC-XVM2869A IB-436 E TRAIN A 6- MSW204A 4-1-14 1-MS40 (OUTPUT SECT.) T T T 125VDC (XVT2869A-MS)
(-) 5K-J2A 3-HERMETIC CONN.
SPLICE BOX 0.75G 5-AT OPEN LIM. SW.
AC-XVM2869A 6-MS 21 FOR XVT2869A D T T -TRAIN A D IB-436 MSW203A 1-4-14 125VDC 1-MS40 MSW205A IB-436 (XVT2869A-MS) VFC-135 HERMETIC 6-MS40 2-1-14 1 0.75G 125VDC (XVT2869A-MS)
CONNECTOR AT AC-XVM2869A 2 SP EK-J2A HERMETIC CONN.
C SOL. VALVE 20A. 0.75G 4-MS40 AT CLOSE LIM. SW. C T T AC-XVM2869A 6-MS40 FOR XVT2869A
- TRAIN A T T 066-W17 066-W17 B LEGEND: B A - CIRCUIT NO.
B - NO. COND. & WIRE SIZE C - VOLTS 1 VIA XX-3518A D - B/M ITEM E - CONDUIT SIZE Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
CLOSED Elec: CLOSED Air: CLOSED CLOSED - OPEN F - NATURE OF CIRCUIT AOV-2869A A VIA XX-3567A Block Diagram SIZE FSCM NO DWG NO REV A
2 G - WIRE MARKS B E-4B-3 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 3 OF 4 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1 CHANNEL B NUCLEAR H
IB-436 IB-436 SAFETY H (XVT2869A-MS)
MSW231B 1-4-14 MSW235B 4-1-14 8-MS43 IB-436 RELATED 125VDC 125VDC (XVT2869B-MS)
HERMETIC EK-J2A 8-MS43 VFC-135 2 SP HERMETIC CONN.
CONNECTOR AT 0.75G 0.75G 1-MS43 7-MS43 AT OPEN LIM. SW.
SOL. VALVE 20B BC-XVM2869A AC-XVM2869B 5-MS43 G 2-MS43 FOR XVT2869B G T T T T -TRAIN B IB-436 MSW232B 5 MSW236B 1 2 3 4 IB-436 (XVT2869B-MS) 2-1-14 & 1-4-14 4-1-12 9-MS43 125VDC 125VDC (XVT2869C-MS)
HERMETIC EK-J2A & VFC-135 EK-J2A 9-MS43 CONNECTOR AT HERMETIC CONN.
F 0.75G 8-MS43 0.75G 1-MS43 F SOL. VALVE 20B AT OPEN LIM. SW.
BC-XVM2869B 2-MS43 AC-XVM2869C 6-MS43 FOR XVT2869C T T T T -TRAIN B IB-436 (-)
MSW233B 1 2 3 6 SPLICE BOX (XVT2869C-MS) 1-2-12 & 1-4-14 MS 24 125VDC 1-MS43 E HERMETIC MSW237B 1 CB-436 MSW238B CB-436 E EK-B1G & VFC-135 1-7-12 2-MS43 1-4-12 CONNECTOR AT 0.75G 125VDC 2SP 125VDC 3-MS43 (XPN7020-SG) 9-MS43 SOL. VALVE 20B BC-XVM2869C EK-BIL 4- EK-BIL 4- SOLID STATE 2-MS43 (XPN7119-MC) 1.25G 5- - 5- PROT. SYS. CAB.
T T BC-XVM2869A,B&C MCB TERM. PNL BC-XVM2869A,B&C 6- 6- - TRAIN B IB-436 MSW234B (OUTPUT SECT.)
4-1-14 T T T T D 125VDC 1-MS43 D (XVT2869A-MS)
EK-J2A 4-MS43 HERMETIC 0.75G 7-MS43 2SP CONNECTOR AT BC-XVM2869A MSW266B 7-MS43 P-MS43 OPEN LIM. SW. 1-9-12 T T (XCP6114) 125VDC 2-MS43 (XCP6114)
MCB Subpanel 12 C MSW267B C P-MS43 1-4-12 1-MS43 125VDC 3-MS43 LEGEND:
1 VIA XX-2139B 6SP A - CIRCUIT NO.
B - NO. COND. & WIRE SIZE 2 VIA XX-2451B C - VOLTS B D - B/M ITEM B 3 VIA XX-3570B E - CONDUIT SIZE F - NATURE OF CIRCUIT 4 SPLICE 4-1-14 WIRES, (EKJ9A), TO 1-4-12 WIRE IN SB-MS49 G - WIRE MARKS 5 VIA SB-MS131, CABLE FROM SB-MS131 TO Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
CLOSED Elec: CLOSED Air: CLOSED CLOSED - OPEN SOLENOID IS 1-4-14 (VFC-135) AOV-2869A A Block Diagram SIZE FSCM NO DWG NO REV A
6 VIA SB-MS127. CABLE FROM SB-MS127 TO B E-4A-4 0 DRAWN HOMER SOLENOID IS 1-4-14 (VFC-135)
ISSUED SCALE 1:1 SHEET 4 OF 4 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-5)
Component ID MOV-11 Component Type MOV Component Description Example 5 Normal Position Closed Failed Electrical Position As-Is Failed Air Position N/A Function State 11-C-O Initial Position Closed Desired Position Open BE Code 11-FTO High Consequence Component Yes No Power Supplies DC Bus 1B Breaker LB02 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments DB2A Y LOP-BF, SC-HS, EI-HS DB2B Y LOP-BF DB2C Y LOP-BF, EI-HS DB2P Y LOP-BF
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies None Comments
- 1) Ungrounded DC control circuit
- 2) Cable DB2P could initiate a spurious close with a combination of four (4) proper polarity hot shorts.
However, the LOP and LOC failure modes dominate.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 H P1 H 33BO 33AO G G G1 R1 123 123 72C 72O 72C 72O HSC HSO CB-3 G R YC1 YO1 F F DC BUS-1B BREAKER LB02 A1 A2 ARM F1 72O 72C 125VDC E 72O 72C E SHUNT FIELD S1 WINDING C O SERIES D FIELD D WINDING YC2 YO2 33BO MOV-11 C CB-3 CTS 33AO 33BO OTS C A N1 P1, N1, YC1, YO1, B G1, R1, MOV-11, SCHEME DB2 B SP B
N1, YC2, YO2 DC BUS-1B C MOV-11 Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
P1, G1, R1 CLOSED Elec: AS-IS Air: N/A CLOSED - OPEN MOV-11 A P Elementary Diagram SI ZE FSCM NO DWG NO REV A
B E-5-1 0 N1, F1, S1, A1, A2 DRAWN HOMER ISSUED SCALE 1:1 SHEET 2 OF 1 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-6A)
Component ID MOV-15 Component Type MOV Component Description Example 6A Normal Position Closed Failed Electrical Position As-Is Failed Air Position N/A Function State 15-C-T Initial Position Closed Desired Position Throttled BE Code 15-FTO High Consequence Component Yes No Power Supplies DC BUS-1B Breaker 72-LB04 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments DB4A Y LOP LOC-HS, SO-HS, DB4B Y SC-HS Spurious Operation requires proper LOP-BF, LOC-HS, polarity hot shorts DB4C Y SO-HS, SC-HS
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies None.
Comments Ungrounded 125VDC Power Supply Ungrounded 48VDC control power Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 H H REMOTE 43 LOCAL G DC BUS-1B RAISE RAISE G (REM) (LOC)
P01 MCB REMOTE 43 LOCAL F F F01 F03 M01 MOV-15 DC BUS-1B 48 VDC LOWER LOWER E
BREAKER 4 POWER (REM) M (LOC) E 125 VDC SUPPLY F02 F04 M02 D D REMOTE 43 LOCAL N01 MCB RAISE RAISE (REM) (LOC)
C C F01, C REMOTE 43 LOCAL F02, F03, F04, SP MOV-15, SCHEME DB4 B A LOCAL B B DC BUS-1B P01, N01 CONTROL MOV-15 M01, M02 PANEL Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
MOV-15 CLOSED Elec: AS-IS Air: N/A CLOSED - THROTTLED(rem)
A Elementary Diagram SI ZE FSCM NO DWG NO REV A
B E-6A-1 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 2 OF 2 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-6B)
Component ID MOV-15 Component Type MOV Component Description Example 6B Normal Position Closed Failed Electrical Position As-Is Failed Air Position N/A Function State 15-C-T (L)
Initial Position Closed Desired Position Throttled - Local Control BE Code 15-FTO High Consequence Component Yes No Power Supplies DC BUS-1B Breaker 72-LB04 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments DB4A Y LOP LOC-HS, SO-HS, Spurious Operation requires proper DB4B Y SC-HS polarity hot shorts DB4C N Isolated in Local
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies None.
Comments Ungrounded 125VDC Power Supply Ungrounded 48VDC control power Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
8 7 6 5 4 3 2 1 H H REMOTE 43 LOCAL G DC BUS-1B RAISE RAISE G (REM) (LOC)
P01 MCB REMOTE 43 LOCAL F F F01 F03 M01 NOTE: For operation at MOV-15 Local Control Panel, Remote contacts are DC BUS-1B OPEN and Local 48 VDC LOWER LOWER contacts are CLOSED.
E BREAKER 4 POWER (REM) M (LOC) (Device 43).
E 125 VDC SUPPLY F02 F04 M02 D D REMOTE 43 LOCAL N01 MCB RAISE RAISE (REM) (LOC)
C C F01, C REMOTE 43 LOCAL F02, F03, F04, SP MOV-15, SCHEME DB4 B A LOCAL B B DC BUS-1B P01, N01 CONTROL MOV-15 M01, M02 PANEL Title Normal Position Failed Position Functional State [ INITIAL - FINAL ]
MOV-15 CLOSED Elec: AS-IS Air: N/A CLOSED - THROTTLED(local)
A Elementary Diagram SI ZE FSCM NO DWG NO REV A
B E-6B-1 0 DRAWN HOMER ISSUED SCALE 1:1 SHEET 2 OF 2 8 7 6 5 4 3 2 1
CIRCUIT ANALYSIS WORKSHEET (EX-7A)
Component ID CCW-1B Component Type Pump Component Description Component Cooling Water Pump 1B Normal Position Standby Failed Electrical Position Off Failed Air Position N/A Function State CCWB-STB-ON Initial Position Standby Desired Position On BE Code CCW-B_FTR High Consequence Component Yes No Power Supplies Bus 1F Breaker DF04 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 2VADF04A Y N LOC-BF, S/O-HS 2VADF04B Y N LOC-BF, S/O-HS 2VADF04E Y N LOC-BF, S/O-HS 2VADF04F Y N LOC-BF 2VADF04G Y N LOC-BF 2VADF04P Y N LOP 3-phase power cable 2VADF04Z Y N LOC-BF, S/O-HS 2VADFO5Z Y N LOC-BF
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies
- 3. DF05 52-MOC: Required to support auto-start of pump upon loss of redundant CCW pump.
- 4. DF05 2 and 86: Required for auto-start upon fault to redundant CCW pump. Has 1 sec time delay,
- 5. Load Shed (94F1): Required to support load shed of Bus 1F on undervoltage.
Comments
- 1. 125 VDC Control Power is included in Bus 1F analysis.
- 2. Circuit breaker fails As-Is on loss of 125 VDC control power. Thus, a loss of control power after The breaker is closed will not stop the pump, but it will be operating with no fault protection.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
Drawing D207185 Cable for bus differential relay is included with Bus 1F C3 CCW PUMP 1B C2,T4, 2-SP A1,C2,R1 L2,P2,T4,T5, C3,SP 2-SP P1,C2,T1 T4,2-SP AM SW A1,C1,L1 T6,P1,L2,T1 C2,T4, 2-SP A1,C2,R1 L2,P2,T4,T5, C3,SP 1,2,3: LOP 1,2,3 2-SP A1: LOC (?)
C1: C1 P1,C2,T1 L1: LOC A1,C1,L1 T4,2-SP T6: LOC T6,P1,L2,T1 P1: LOC L2: LOC 1,2,3 T1: LOC, S/O-HS C2: LOC T4: LOC Example No. Title Drawing No.
R1: LOC, S/O-HS CCW-B 7A Elementary Diagram D207183 P2: LOC T5: LOC STANDBY /
BlockElec:Diagram Normal Position Failed Position OFF Function State STANDBY - ON C3: LOC ON Air: N/A
1 Differential Scheme 1 1
included with Bus 1F Analysis 1 B
1 1 B 1
1 1
1
Spurious Load-Shed Signal will cause pump to trip B
LOSP Load Sequencer signal to CCW Pump B
CIRCUIT ANALYSIS WORKSHEET (EX-7B)
Component ID CCW-1B Component Type Pump Component Description Component Cooling Water Pump 1B Normal Position Standby Failed Electrical Position Off Failed Air Position N/A Function State CCWB-STB-OFF Initial Position Standby Desired Position Off BE Code CCW-B_FTRSP High Consequence Component Yes No Power Supplies Bus 1F Breaker DF04 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 2VADF04A Y N S/C-HS 2VADF04B Y N S/C-HS 2VADF04E Y N S/C-HS 2VADF04F Y N S/C-HS 2VADF04G Y Y S/C-HS Dependent on state of DF05 52-MOC 2VADF04P N N NR 3-phase power cable 2VADF04Z N N NR 2VADFO5Z N N NR
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies
- 3. DF05 52-MOC: Spurious trip of redundant CCW pump will auto-start CCW-B.
- 4. DF05 2 and 86: Spurious overcurrent fault signal from DF05 will auto-start CCW-B.
- 5. Load Shed (94F1): Load shed interlock Not Required. Break is open and desired open.
Comments
- 1. 125 VDC Control Power is included in Bus 1F analysis.
- 2. Circuit breaker fails As-Is on loss of 125 VDC control power. Thus, 125 VDC is only required if It is desirable to maintain overcurrent protection for 3-phase power cable and pump motor.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
Drawing D207185 able for bus differential relay is included with Bus 1F C3 CCW PUMP 1B C2,T4, 2-SP A1,C2,R1 L2,P2,T4,T5, C3,SP 2-SP P1,C2,T1 T4,2-SP AM SW A1,C1,L1 T6,P1,L2,T1 C2,T4, 2-SP A1,C2,R1 1,2,3: NR 1,2,3 L2,P2,T4,T5, C3,SP 2-SP A1: NR C1: S/C-HS P1,C2,T1 L1: NR A1,C1,L1 T4,2-SP T6: NR T6,P1,L2,T1 P1: NR L2: NR 1,2,3 T1: NR C2: S/C-HS T4: NR Example No. Title Drawing No.
R1: NR 7A CCW-B Elementary Diagram D207183 P2: NR T5: NR BlockElec:Diagram Normal Position Failed Position Function State C3: S/C-HS STANDBY /
ON Air:
OFF N/A STANDBY - ON
1 Differential Scheme 1 1
included with Bus 1F Analysis 1 B
1 1 B 1
1 1
1
Spurious Load-Shed Signal will cause pump to trip B
LOSP Load Sequencer signal to CCW Pump B
CIRCUIT ANALYSIS WORKSHEET (EX-8)
Component ID MCC-1B Component Type 480 V MCC Component Description Class 1E Motor Control Center No. 1B Normal Position Energized Failed Electrical Position Deenergized Failed Air Position N/A Function State MCC1B-E-E Initial Position Energized Desired Position Energized BE Code EDS-MCC1B_FTRE High Consequence Component Yes No Power Supplies LC-B Breaker ED10 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 1VAED10A Y N S/O-HS, LOFP-BF 1VAED10B Y N S/O-HS, LOFP-BF 1VAED10P Y N LOP 3-phase power cable 1VAED10Z Y N S/O-HS, LOFP-BF
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies None Comments
- 1. 125 VDC breaker control power is incorporated into the analysis for LC B.
- 2. No load shed scheme for MCC-1B supply breaker (ED10).
- 3. Breaker ED10 will fail As-Is on loss of 125 VDC control power.
- 4. Breaker ED10 will lose overcurrent protection for pump and power cable if 125 VDC control power is lost due to a fault causing the control circuit fuse(s) to blow.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
1B 1B 1B 1B 1B 1B B
480 No Load Shed Scheme for MCC ED-02 ED-12 ED-09 B (NORM) 480V Bus 1B B (EMERG) 480V Bus 1B ED03 ED04 ED05 ED06 ED15 ED14 ED13 ED11 ED10 ED08 480 MCC 1B Supply Breaker to MCC-1B Example No. Title Drawing No.
LC-B EX-8 14 E-14-1 E-08-1 One-Line Diagram Normal Position Failed Position Function State ENERIZED Elec: DEENERGIZED ENERGIZED Air: N/A
Title:
C:\Data\DOCUME~1\dmcl\00003745\demccoy1\80787657\D177007.cal
480V Must look at Detail "A" 480V 1,2,3: LOP P1: LOC, LOFP P2: LOC, LOFP C2: LOC, LOFP T2: LOC, LOFP, S/O-HS L2: LOC, LOFP A2: LOC, LOFP R2: LOC, LOFP C1: LOC, LOFP T1: LOC, LOFP, S/O-HS L1: LOC, LOFP A1: LOC, LOFP R1: LOC, LOFP AEE10 EE10 480V AED10 ED10 Example No. Title Drawing No.
MCC-1B SUPPLY BREAKER 14 ELEMENTARY DIAGRM E-14-2 No "Q" Cable Example No. Title Drawing No.
Be sure to use correct Normal Position EX-8 Failed MCC-1B Position SUPPLY BREAKER E-08-2 Function State 14 ELEMENTARY DIAGRM E-14-2 row in Adapter Table ENERIZED Normal Position Elec:FailedDEENERGIZED Position ENERGIZED Function State Air: N/A ENERIZED Elec: DEENERGIZED ENERGIZED Air: N/A
CIRCUIT ANALYSIS WORKSHEET (EX-9)
Component ID LC-1D Component Type 480 V Load Center Component Description Class 1E Load Center 1D Normal Position Energized (Norm)
Failed Electrical Position Deenergized Failed Air Position N/A Function State LC1D-E-E Initial Position Energized Desired Position Energized BE Code EDS-LC1D_FTRE High Consequence Component Yes No Power Supplies SST-1D Breaker N/A Reqd PNL-B-1D Breaker 6 Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 1VAED02A Y N LOC-BF, S/O-HS Breaker ED02 Control 1VAED02B Y N LOC-BF, S/O-HS Breaker ED02 Control 1VAED02Z Y N LOC-BF, S/O-HS Breaker ED02 Control 1VAED08A Y N S/C-HS Breaker ED08 Control (Close) 1VAED08B Y N S/C-HS Breaker ED08 Control (Close) 1VAED08C N N NR Breaker ED08 Control (Trip) 1VAED08D Y N S/C-HS Breaker ED08 Control (Close) 1VAED08P N N NR Isolated by ED08 1VAED08Q N N NR Isolated by ED08 1VAED08Z Y N S/C-HS Breaker ED08 Control 1VAED08Y N N NR Used for Breaker EA09 1VAED01A Y N LOP-UV Bus undervoltage trip 1VAED01B Y N LOP-UV Bus undervoltage trip
Cable ID Reqd? MHS? Fault Consequence Comments 1VAEA01Y Y N LOP-UV Bus undervoltage trip 1VADF14Y Y N LOP-UV Bus undervoltage trip 1VADF03C Y N LOP-OC Transformer differential trip Equipment Dependencies
- 1. SST-1D transformer differential trip and undervoltage trip are included in this analysis.
- 2. Load Shed (94F3): Breaker ED08 is open so load shed signal is not of concern.
- 3. LOSP and ESFAS Sequencer (R-16, R6F, XF): Spurious sequencer signals can result in spurious close of alternate supply breaker ED08, thus dependencies are required.
Comments
- 1. 125 VDC control power is not needed to maintain breakers in desired position. However, it is required for Breaker ED02 to maintain over current protection.
- 2. Mechanical interlock prevents spurious close of Breaker ED12, so no cables included.
- 3. Breaker ED08 is analyzed for spurious close to preclude paralleling 3-phase power out of phase.
- 4. Bus bar connection between SST-1D and main bus is local to switchgear.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
Date: 3/2/2007 Time : 12:49:53 PM Differential trip circuit must be considered Must ensure breakers remain open to prevent 480 spurious paralleling out 480 V Select LC of phase transformer as boundary 480V Local bus bar Indication Only Undervoltage trip circuit must be considered
Title:
C:\Data\DOCUME~1\dmcl\00003745\demccoy1\80787657\D177010.cal
Date: 3/2/2007 Time : 01:13:56 PM Must consider differential
Title:
C:\Data\DOCUME~1\dmcl\00003745\demccoy1\80787657\D177074.cal
Date: 3/2/2007 Time : 01:10:50 PM
Title:
C:\Data\DOCUME~1\dmcl\00003745\demccoy1\80787657\D177064.cal
Date: 3/2/2007 Time : 01:12:56 PM No analysis is needed because mechanical interlock prevents spurious closure
Title:
C:\Data\DOCUME~1\dmcl\00003745\demccoy1\80787657\D177072.cal
Date: 4/27/2007 Time : 06:59:47 PM Mechanical Interlock (Kirk-Key)
Title:
C:\Data\DOCUME~1\dmcl\00003745\48907e97.hst\807df76e\B177125.cal
Date: 3/2/2007 Time : 01:21:35 PM
Title:
C:\Data\DOCUME~1\dmcl\00003745\demccoy1\80787657\D177087.cal
Date: 3/2/2007 Time : 02:03:16 PM 480V
Title:
C:\Data\DOCUME~1\dmcl\00003745\demccoy1\80787657\D177171.cal
CIRCUIT ANALYSIS WORKSHEET (EX-10)
Component ID ANN-1 Component Type Annunciator Component Description High Bearing Temp AFW Pump A Normal Position Available Failed Electrical Position Unavailable Failed Air Position N/A Function State ANN1-A-NS Initial Position Available Desired Position Non-spurious BE Code ALA-ANN1-SP_IND High Consequence Component Yes No Power Supplies Vital-A Breaker 4 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments K16A Y N S/A-HS K16N Y N S/A-HS
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies None Comments 3X-5/AFW-A is a local temperature switch (mechanical). The switch itself has no additional circuits.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
33: NR 34: S/I-HS
CIRCUIT ANALYSIS WORKSHEET (EX-11)
Component ID FCV-605A Component Type Throttling AOV Component Description RHR Flow Control Valve Normal Position Closed Failed Electrical Position Closed Failed Air Position Closed Function State FCV605A-C-MOD Initial Position Closed Desired Position Modulate BE Code RHR-605A_FTM High Consequence Component Yes No Power Supplies APN5902 Breaker 13 Reqd APN1FA Breaker 12 Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments RHR6XD Y N LCS, ECS RCU453X N N ISOL Isolation at Loop Power Supply MIR55XD Y N LCS, ECS MIR9X N N ISOL Isolation at NCI Computer Input MIR156X N N ISOL Isolation at NAI DC Controller RHN9X N N ISOL Isolation at NAI DC Controller M/A Station could introduce MIR71XD Y N LCS, ECS spurious signal RHR5XD Y N LCS, ECS FI605A Y N LCS, ECS
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies
- 1. Instrument Air is required for operability.
Comments Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
Flow Transmitter FT605A produces 4-20 mA signal Credited Isolation Point I/P Converter for FCV-605A 3-15 psi control air signal Example No. Title Drawing No.
FCV-605A 11 Instrument Loop Diagram E-11-1 Normal Position Failed Position Function State CLOSED Elec: CLOSED CLOSED - MODULATE Air: CLOSED
CIRCUIT ANALYSIS WORKSHEET (EX-12)
Component ID TTR2 Component Type Indicator Component Description RHR Flow Indication Recorder Normal Position Available Failed Electrical Position Unavailable Failed Air Position N/A Function State TTR2-AV-AV Initial Position Available Desired Position Available BE Code RHR-TTR2_FTRA High Consequence Component Yes No Power Supplies APN5902 Breaker 13 Reqd APN1FA Breaker 12 Reqd APN5906 Breaker 17 Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments RHR6XD Y N LIS, EI RCU453X Y N LIS, EI MIR55XD N N ISOL Isolation at Loop Power Supply MIR9X N N ISOL Isolation at Loop Power Supply MIR156X N N ISOL Isolation at Loop Power Supply RHN9X N N ISOL Isolation at Loop Power Supply MIR71XD N N ISOL Isolation at Loop Power Supply RHR5XD N N ISOL Isolation at Loop Power Supply LIR1330 Y N LIS, EI
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies Comments Recorder requires separate power from APN5906, Bkr 17 to function.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
Flow Transmitter FT605A produces a 4-20mA signal Temperature Recorder TTR2 has 3 inputs - we are only analyzing signal from TTR2 has a separate FT605A power supply that must be included to assure functionality Credited Isolation Point Example Example No.
No. Title Title Drawing Drawing No.
No.
TTR2 FCV-605A FCV-605A 12 17 Instrument E-12-1 E-17-1 Instrument Loop Loop Diagram Diagram Normal Normal Position Position Failed Failed Position Position Function Function State State AVAILABLE CLOSED CLOSED Elec:
Elec: UNAVAIL CLOSED CLOSED AVAIL CLOSED CLOSED - AVAIL
-- MODULATE MODULATE Air:
Air: N/A CLOSED CLOSED
CIRCUIT ANALYSIS WORKSHEET (EX-13)
Component ID COMP-1B Component Type Air Compressor Component Description Air Compressor 1B Normal Position Cycle Failed Electrical Position Off Failed Air Position N/A Function State COMP1B-CY-CY Initial Position Cycle Desired Position Cycle BE Code IA-COMP1B_FTR High Consequence Component Yes No Power Supplies LC-1 Breaker EQ-17 Reqd Breaker Reqd Cable Analysis Cable ID Reqd? MHS? Fault Consequence Comments 1UYEQ17J Y N S/O-HS, LOCP Breaker control circuit 1UYEQ17P Y N LOP 3-phase power 1UYEQ17A Y N LOC-BF Cooling water 1UYEQ17B Y N LOC-BF 1UYEQ17E Y N LOC-BF 1UYEQ17H Y N LOC High water temperature 1UYEQ17I Y N LOC-BF Sequence controller 1UYEQ17M Y N LOC-BF 1UYEQ17N N N NR Annunciation 1UYEQ17T N N NR Annunciation
Cable ID Reqd? MHS? Fault Consequence Comments Equipment Dependencies Comments 125 VDC control power for Breaker EQ-17 is included with analysis for LC-1.
Cable Analysis Failure Mode(s)
Grounded?
Single Aggregate or Power Double Circuit (AC or Insulation Intra Inter GFEHS Cable ID Break Type DC) / Shield 7150 Table P(x)
ate: 5/8/2007 Time : 04:01:43 PM 480 V Bus LC-1
Title:
C:\Program Files\Cygna\PDMS\temp\0900374580105762_D172746.cal
480 480