Attachment 3 to ULNRC-06510 Page 1 of 2 ATTACHMENT 3 Markup ofT$ Bases Page (for information only)

uacnment to ULNRC-0651 0 Page2 of 2 BASES ESFAS Instrumentation B 3.3.2 Su RVEI LLANCE REQUIREMENTS 3.3.2.13 (continued)

Frequency Control Program and prior to entering MODE 4 for Functions I.b, 3.a.(2), and 7.a whenever the unit has been in MODE 5 or 6 for

> 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, if not performed within the previous 92 days (Reference 12).

The Surveillance Frequency is based on operating experience, equipment reliability, and plant risk and is controlled under the Surveillance Frequency Control Program.

SR 3.3.2.14 SR 3.3.2.14 is the performance of a SLAVE RELAY TEST as described in R33..6 e ce ttha SR3.3.2.l4hasaNotes ecu in thatita lies I

to ci ye re a K 2 a d 7 0. 1 e el yc or tect d it a

Frequency cpeciflethn the Surveillance FreqienoyGontroI Program-and prior to entering MODE 3 for Functionc 5.a and 9.a whenever the unit has been in MODE 5 or 6 for > 24 houre, if not performed within the previouc 02 dayc. The SLAVE RELAY TEST of relay K620 doec not includethe oircuitry-accociated with the main feedw er ump tn c lenoidc since hat cir ui ry erve n

r q re c fe 1 n ti e

u e a c q e c s

based on operating experience, equipment reliability, and plant risk and is controlled under the Surveillance Frequency Control Program. Testing slave relay K750 at power would result in opening the PORVs and depressurizing the RCS. If the PORV block valves are closed, there is not enough pressure to open the PORVs.

REFERENCES I

FSAR, Chapter 6.

2.

FSAR,Chapterf.

3.

FSAR, Chapter 15.

4.

IEEE-279-197 1.

5.

10 CFR 50.49.

6.

Callaway Setpoint Methodology Report (NSSS), SNP (UE)-565 dated May I

, I 984, and Callaway Instrument Loop Uncertainty Estimates (BOP), J-U-GEN.

7.

Not used.

(continued)

Replace lined through text with the following:

only to slave relay K750.

The slave relay is tested with a Frequency specified in the Surveillance Frequency Control Program and prior to entering MODE 3 for Function 9.a whenever the unit has been in MODE 5 or 6 for

> 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, if not performed within the previous 92 days.

CALLAWAY PLANT B 3.3.2-69 Revision 14b