LER-2019-002, High Pressure Coolant Injection System Inoperable Due to a Lack of Hydraulic Oil Pressure by the Auxiliary Oil Pump
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(v), Loss of Safety Function
3662019002R00 - NRC Website

text

~ Southern Nuclear MAY 1 6 2019 Docket Nos.: 50-366 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Thomas A. Vehec Hatch Nuclear Plant Vice President-Plant Hatch 11028 Hatch Parkway North Baxley, GA 31513 912 5375859 tel 912 366 2077 fax Nl-19-0576 Edwin I. Hatch Nuclear Plant Unit 2 Licensee Event Report 2019-002-00 High Pressure Coolant Injection System Inoperable Due to a Lack of Hydraulic Oil Pressure by the Auxiliary Oil Pump Ladies and Gentlemen:

In accordance with the requirements of 10 CFR 50.73(a)(2)(v)(D) Southern Nuclear Operating Company hereby submits the enclosed licensee Event Report.

This letter contains no NRC commitments. If you have any questions, please contact the Hatch licensing Manager, Jimmy Collins at 912.537.2342.

~

T.A. Vehec Vice President - Hatch TAV/UAP/SCM Enclosure: LEA 2019-002-00 cc:

Regional Administrator, Region II NRR Project Manager - Hatch Senior Resident Inspector-Hatch RTYPE: CHA02.004

Edwin I. Hatch Nuclear Plant Unit 2 Licensee Event Report 2019-002*00 High Pressure Coolant Injection System Inoperable Due to a Lack of Hydraulic Oil Pressure by the Auxiliary Oil Pump

NRCFORM366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 31150-0104 EXPIRES: 0313112020 (04-2018)

Es-.d-I"' I1!SpCift;O ID ~

llllllhs,.._,. cdll<llon rw<J&t 80,._.

    • .,.v*...... ~

LICENSEE EVENT REPORT (LER)

RlpCII!ed lesonl letlned ** in=rpcnled no tw ~

poxes 11111 led ted lo ltlllaty S11111 Cllllll1>erts 1111rilll buden el-1 lo IN......,_, s.r.c.t Brn11

!¥~

(See F'age 2 for required number or dlg'tsleharaclers lor each blOCk)

(T l F43~ U S.lkii*R"""'cry Calm:o.on. ~DC lO!SGUOI or by......

I!

lo ln!-R~

gow lrd ID IIIII De:~ Ollcor Olce ollnbmlhrl lrd

\\,;

)

(See NUREG-1022. R 3 for instrucbon and guidance for completing this ronn R~

Allon IIEOB 10202 (31504104) OGice d ~

11111 lludgd.

Wclql111. DC lll50lll 1 -

IGed 1D -*

., -.n C<11e<1on docs R11 llt1il Uwww.lll:k.gQv/readiDg anld~~II!H;!IQnstnureg:i£li!Dff!sd0221Qll dqUt o......-tr wold OM!....,. runllor lie NIC _, 1111 CZIIUt ~._ n1 a pelliOiio RllfttJ'I"d 1D I!Spandlo. ~~~--

3, Page Edwin I. Hatch Nudear Plant Unit 2 05000 366 1

OF 2

4. Tllla High Pressure Coolant Injection System Inoperable Due to a lack of Hydraulic OR Pressure by the Auxibary Oil Pump
6. Evant Date s. LER Number
7. Report Date
8. Other Facilities Involved Monlll

~

Ye:ar Yoar I s.q.. ntlal I llov Month D3V Yo :at lf'~llllylbmo Oocllotttu-.

NUIIIIIIr No.

06000 002 OS 16 2019 l'aolllt'ftt.llmo Docket Humber 03 19 2019 2019 w

w 00 06000

9. Operating Modo
11. lhls Report is Submitted Pursuant to tho Requirements of 10 CFR §: (Check all thllr apply) 0 20:!201(b) 0 20 2:!03(a)(3)(i) 0 50 73(a)(:!)(*i)(A) 0 5073(a)(2){viii)(A) 2 0 20 :!:!01(d)

O 20 2:!03(a)l3)(1i) 0 SO 73(a)(:!)(ii)(B) 0 SO 73(a)(:!)(YIII)(B) 0 20 :!:!03(a)(1 1 0 :!0 :!:!03(8)(4) 0 50.73(a)(:!)(lii) 0 50.73(e)(::!)(ix)(A) 0 20 ::!203(a)(:!}(l) 0 50 36(ci(1)(1)(A) 0 SO 73(a)(:!)(iv)(A) 0 5073(a)(::!)(*l

10. Power Level 0 20 :!:!OJ(a)(:!)(li) 0 50315(c)(1)(fi)(A) 0 50.73(a)(:!)(v)(A) 0 73.71(8}(4) 0 20 2:!03(a)(:!)(ih) 0 50 36(c)l:!l 0 50 73(B)(:!)(v)(B) 0 73.71(a)(S) 0 :!0 :!203(B)(:!)(iv) 0 50 46(a)(31(ii) 0 50 73(a)(:!l(v)(C) 0 7377(al(1) 001 0 20 :!:!03(a)(:!Kvl 0 50 73(a)I:!J(i)(A) 0 50 73(a)(:!)(v)(O) 0 73 77(a)(:!l(*l 0 20 :!:'03(8 )(:!)(vi) 0 50 73(a)(:!)(i)(B) 0 50.73(a)(:!)(vii) 0 73 77(e)(:!)(ii)

I~

] 0 50 73(a)(:!)(i)(C) 0 Other (Specify In Abstract below or 1n NRC Fonn 366A)

12. Licensee Contact for this LER Licensee Contact Telephone Numbor (Include Area Code)

Edwin I. Hatch I Jimmy Collins-Ucensing Manager 912-537-2342

13. Complete One Una for each Component Failure Described In this Report

~""

llyslllll I Component I lobnulocturer Reporbblo to ICES

~I Cwse I 8y&lllll I COmponent

~xtur11 I Reportable to ICI!S D

BJ MCC GOBO y

14. Supplemental Report Expected MDnlll

!loy Yt:ar 0 Yes (II yes complele 15. & peeled SubmisSion Dale)

IL]No

16. Expected Submission Date Abstract (Limit to 1400 spaces, I.e
  • approximately 14 single-spaced typewnUen tines)

At 0140 EST on March 19,2019, while Unit 2 was at approximately 1 percent power in Mode 2, Operations dedared the High Pressure Coolant Injection (HPCI) inoperable following a failed Operability test. During the test, the HPCI auxiliary oil pump failed to start when the control switch was taken to start. Due to the lack of hydraulic oil pressure provided by the auxiliary oil pump, the HPCI main stop valve did not open followed by the illumination of the HPCI turbine trip annunciator, thus, preventing HPCI from starting and making it inoperable. An investigation was performed and found the secondary connection stabs on the Motor Control Center Pan Assembly feeding the auxiliary oil pump were not making adequate contact. The stab tension was adjusted and the oil pump was started followed by successful completion of the HPCI pump operability test. Because HPCI does not have a redundant system, the pump failure to start on demand represents a safety system functional failure as defined in NEI 99-02 and is reportable per 50.72(b)(3)(v)(D).

NRC FORU 3615 (04-:!018) U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3160.(1104 EXPIRES: 03/3112020 (04*:!01&),............

!¥'

\\.

~

LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET (See NUREG-1 022. R 3 for instruction and guidance for completing this form http ttwww OOOS.Q!!ftS!_adJrg:,ll:IM!oc-col1ect *onslnuregststa!f!§!.1!17~

EWnaled bllrd!n per rMpOn$810 ~Y wlh lhis mandalory cdleclion reque:t 80 llow'c. R~ed les::ora lelm!d aro lnctrp(f11ed inlo 1he lic:ercing proc= and lad back lo indu~rt Ser.d cornmant; regardng burden esti~la 1o lhe lnlcnnalon SeMees Branch (T-2 F43), U. S. ~'<<~dear RegLiatay Cornnmion, Wa$1inglon, DC 20555-0001, or by e-mai Ia lnfotdlects ~

gov. and 1o IIHt Dd. 0&<<, OC!ict d lnlamamn and RegLiatcry Maire, NE08-10202, (11~104), Olfrct d Management and Budge!, Wr..hinglon, DC 20501

~ a means u;ed ID l~e an lnlormalion cdloclon dolls nol d$Jlay a C~!fenly ~id OMB con*d nunter, IIHI tflC may nol conWct or spwor, and a per;oo rs nol raqlired lo mpond lo. Ute lnkrrnalon cdleciort

3. LER NUMBBt Edwin I. Hatch Nuclear Plant Unit 2 05000-1 366 NARRAnVE

EVENT DESCRIPTION

At 0140 EST on March 19,2019, while Unit 2 was in MODE 2 (with Reactor Steam Dome Pressure> 150 PSIG) and at approximately 1 percent power, following a refueling outage, Operations declared the High Pressure Coolant Injection (HPCI) [EllS BJ] inoperable following a failed Operability test. During the test, the HPCI auxiliary oil pump failed to start when the control switch was taken to start. Due to the lack of hydraulic o~ pressure provided by the auxiliary oil pump, the HPCI main stop valve did not open followed by the iUumination of the HPCI turbine trip annunciator. The Unit entered into a required action statement (RAS) for technical specification 3.5.1 Condition C, for the auxiliary oil pump failure to start that resulted in HPCI being declared inoperable.

EVENT CAUSE ANALYSIS

The subsequent investigation and analysis determined that the secondary connection stabs, on the Motor Control Center (MCC) [EllS MCC] Pan Assembly feeding the auxiliary oil pump, were not making adequate contact in the MCC causing the auxiliary oil pump not to start. The inspection procedure failed to include the inspections of the stabs and contacts.

REPORT ABILITY AND SAFETY ASSESSMENT:

HPCI does not have a redundant system, therefore, this condition was reportable per 50.73(a)(2)(v)(D). A pump failure to start on demand represents a safety system functional failure as defined in NEI 99-02. The safety significance of this event is minimal due the a short duration of less than 14 hours1.62037e-4 days <br />0.00389 hours <br />2.314815e-5 weeks <br />5.327e-6 months <br /> that HPCI was declared inoperable and the concurrent availability of the Reactor Core Isolation Cooling [EllS BN] system. This MCC Pan Assembly only feeds the HPCI auxiliary oil pump.

CORRECTIVE ACTIONS

The stab tension was adjusted and the auxiliary oil pump started followed by the successful completion of the HPCI pump operability. The RAS was exited on March 19,2019 at 1522 EST.

Corrective action v.;u be taken to update the General Electric Low Voltage MCC Inspection procedure to include the visual inspection of the MCC subcomponents, such as the secondary connection stab tension Work orders have been generated to inspect the MCC pan assembly connection stabs on both units by end of 2020 as part of the extent of condition.

PREVIOUS SIMILAR EVENTS

None NRC FOR Ill 3&8A (04-:!0t&)

of 2