ML19031C375

From kanterella
Jump to navigation Jump to search
Letter Response to IE Bulletin No. 78-04
ML19031C375
Person / Time
Site: Salem  
(DPR-070, DPR-075)
Issue date: 03/23/1978
From: Martin T
Public Service Electric & Gas Co
To: Grier B
NRC/IE, NRC Region 1
References
IEB-78-004
Download: ML19031C375 (1)


Text

I I** *.

I I

Tho.mas J. Martin Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 201/430-8316 Vice President Engineering and Construction Mr. Boyce H. Grier, D~rector U. S. Nuclear Ragulatory Commission.

Office of Inspe~tion and Enforcement Region 1

. 631 Park Avenue King. of Prus&ia, Pennsylvania 1940&

Dear Mr. Grier:

NRC IE BULLETIN NO. 78-04 NO. 1 AND 2 UNITS SALEM NUCLEAR GENERATING STATION March 23, 1978 In resporise to your letter of February 21, 1978, transmitting NRC IE. Bulletin No. 78-04 which was rec~ived on February 24, 1978, we have investigated this matter with respect to applicability to Salem No. 1 and No. Z Units.

Tha following is: in response to the conc.erns addressed ili the subject bulletin~

The noted NAMCO D2400X. limit switches were found on a number of*

containment isola:tion. valves (inside containment) for both Units 1 and 2 at Salem..

The control cir.cuitry for these valves utilize the limit switches as a. seal~in f~ature similar to that described in the NRC Bull~tin and the referenced Westinghouse Technical Bulletin NSD-TB-77-13.

The seal-in cir.cuitry will be modified where*.

possible to eliminate the need for the limit switch contacts.

In cases. where th.is is not feasible, the NAMCO DZ400X limit switches.

will be replaced with suitably qualified limit switches.

This

  • modification/replacement program is expected to be completed for Unit 1 by the end of th.a first refueling outage and for Unit 2 prior to receipt of operating license.

In.addition to the NAMCO limit switche* a few isolation valves utilize* a. different type* limit switch. in a. similar seal-in applica-tion..

The qualificati.on data. for thes.e* switches. is now under review.

If not. suitable:P they* will also be modified. or replaced.

as appropr.ia*te*.

If you have any additional questions, we will be pleased to discuss them with. you.

CC~ Dr. Ernest Volgenau Bethesda, Ma.ryland 2.0014.

Very truly yours,