Richard M. Eckert Vici:: Prnsidr;nt Public Service Electric and Gas Company 80 Park Place Nowark. N.J. 071O1 201/622-7000 Engineering and Construction Mr. James P. O'Reilly, Director U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406
Dear Mr. O'Reilly:
NRC IE BULLETINS 76-02 AND 76-03 DOCKET NO. 50-272 AND 50-311 NO. 1 AND 2 UNITS SALEM NUCLEAR GENERATING STATION
<rr~' ~~
~L\\.;L\\Vtu
~
MAYl 319/G~
S NUClE>.R 11.mutA70!\\Y1 U, '
COMMISS!Oi-1 h\\<:tl Sectlo.!J Referring to NRC IE Bulletins 76-02 and 76-03 received March 22, 1976 we offer the following:
Bulletin 76-02, "Relay Coil Failures -
GE Ty-pe HFA, HGA, HKA and HMA Relays 11 All HFA relays in the 4 kv group and vital buses have been inspected and were found to hav2 Lexan coil spools.
There are HGA relays used in these buses and in the Diesel Generat~r control panels which have not been inspected because of recent testing schedules.
If any nylon ~oil spools are found, they will be replaced by the Energy LaboratoTy with coil spools made of Lexan.
Bulletin 76-03, "Relay Malfunctions -
GE Type STD Relays" We do not use type STD relays at Salem.
=~'. -*.* -*, *.
-;-. *: '.~.
-.. :* -~' ~. *;..; *...... ;_*:;. ::....-... ;...
200 Years or Energy Leadership!
-~-------*-*.. -- --*-.---*--*-* *********---
~-*-*-----~,~**---*- --
I
- .j I'
I I,,
Mr. James P. O'Reilly 5/11/76 If you require additional information our engineer~ will discuss it with you.
CC:
Director, l & E Washington, D.C.
Very truly yours,
_~...,,.~~---.._.._,_... ___ ~-------_***_-*-_--_-_* _____
_... _---_~-=-*------- -*--*--- -----
I r
I I
I I