ML18346A205

From kanterella
Jump to navigation Jump to search
Steam Generator Flushing Report No. 6, Covering Period of 04/28/1975 Through 05/31/1975
ML18346A205
Person / Time
Site: Palisades 
Issue date: 06/27/1975
From: Sewell R
Consumers Power Co
To:
Office of Nuclear Reactor Regulation
References
Download: ML18346A205 (2)


Text

..,.**I

~:-;._.~*~,: * ~.:: J

-- "I consumers Power company June 27, 1975 lJREGULATORY DOCKET FILE COP"fil_

Division of Reactor Licensing US Nuclear Regulatory Commission Washington, DC 20555 Gentlemen:

Re:

Docket 50-255 License DPR-20 Palisades Plant Flushing Report Attached is Stearn Generator Flushing Report No 6 for the Palisades Plant.

This report covers the period from April 28, 1975 to May 31, 1975*

RBS/de CC:

JGKeppler, USNRC Yours very truly,

~~

Ralph B. Sewell Nuclear Licensing Administrator

PALISADES PLANT Steam Generator Flushing Report No 6 This report covers the period from April 28, 1975 to May 31, 1975.

In compliance with Appendix C to the Provisional Operating License DPR-20, as revised March 28, 1975, graphs are attached showing steam generator:

1.

Phosphate.and Sulphate Concentration

2.

Conductivity (µmho/cm)

3.

pH

4.

Weight of Phosphate and Sulphate Removed These graphs detailing steam generator chemistry for this period show the stability achieved with AVT.

Steam Generator P04 has remained 0.2-0.4 ppm.

Steam Generator S04 has remained less than detectible (<1.0 ppm).

Blowdown from the steam generators has been nearly continuous at 5000 lb/h per steam generator.

The a.mount of phosphate removed from the steam generators increased during this period by a little over one pound per generator.

Steam.generator pH control during this period has alternated between ammonia and morpholine; however, the relationships between the concentrations of these volatiles and expected pH has not held, with pH being lower than expected.

The reason for this condition is currently under study.

Suspended solids in the blowdown have averaged about 0.5 ppm from both steam generators during this period.