ML18227B280
| ML18227B280 | |
| Person / Time | |
|---|---|
| Site: | Turkey Point |
| Issue date: | 01/27/1978 |
| From: | Robert E. Uhrig Florida Power & Light Co |
| To: | Stello V Office of Nuclear Reactor Regulation |
| References | |
| L-78-32 | |
| Download: ML18227B280 (8) | |
Text
REGULATORY INFORMATION DISTRIBUTION SYSTEM'RID~
DISTRIBUTION FOR INCOMING MATERIAL 25i REC:
STELLO V NRC ORG:
UHRIG R E FL PWR 5 LIGHT DOCDATE:
0 l/27/78 DATE RCVD: 02/0 l/78 DOCTYPE:
LETTER NOTARIZED:
YES
SUBJECT:
LICENSE NO DPR-3l 5 4l APPL FOR AMEND:
CONCERNING APPENDIX A>
REVISIOIV TO THE THE THERMAL AND HYDRAULIC SAFETY LIMIT OPERATION... NOTORIZED Ol/27/78.
COPIES RECEIVED LTR 3 ENCL 40 TECH SPECS PROPOSED CHANGE ECCS ANALYSIS PERTAINING TO CURVES FOR 3-LOOP PLANT NAME: TURKEY 'POINT UNIT 3 TURKEY POINT UNIT 4 REVIEWER INITIAL:
XJM DISTR IBUTER INITIAL:
++++++<4++4~++4++4. DISTRIBUTIOIV OF THIS MATERIAL IS AS FOLLOWS 4++4+<+<<4++<<<<<<
GENERAL DISTRIBUTION FOR AFTER ISSUAlVCE OF OPERATING LICENSE.
(DISTRIBUTION CODE A00l)
FOR ACTION:
INTERNAL:
BRANCH CHIEF EAR++W/7 ENCL REG FILE++W/EN L HANAUER++W/ENCL EISENHUT++W/EIVCL BAER4>W/ENCL GRIMES~~W/ENCL J.
MCGOUGH++W/ENCL NRC PDR++W/ENCL OELD+4~LTR ONLY CHECK++W/ENCL SMAO~+W/ENCL BUTLER+~W/ENCL J.
COLLINS<4W/ENCL EXTERNAL:
LPDR~S MIAMIi FL++W/ENCL TIC++W/ENCL NSIC++W/ENCL ACRS CAT B>>W/lb ENCL DISTRIBUTION:
LTR 40 ENCL 39 SIZE:
2P+ iP+37P CONTROL NBR:
780320024 THF END
,I
~<
~
p
. O. BOX 013100, 'MIAMI, FL 33101 FLORIDAPOWER & LIGHT COMPANY January 27, l978 L-'78-32 Director of Nuclear Reactor Regulation Attention:
Nr. Victor Stello, Director Division of Operating Reactors U. S. Nuclear Regulatory Commission Nashington, D.C.
20555
Dear Nr. Stello:
Re:
Turkey Point Units 3 and 4
Docket.Nos.
50-250 and 50-251 Proposed Amendment to Facility 0 erati;n Licenses DPR-31 and DPR-41
~fg lf~
CB'g Igpa~
~ASS g~11 ltdL Xn accordance with 10 CFR 50;30, Florida Power s Light; Company submits herewith three (3) signed'riginals ance forty (40) copies of a request to amend Appendix A of Facility Gperating Licenses DPR-31 a'nd DPR-41.
t An ECCS reanalysis has',be'en performed.assuming greater, than 15% steam generator tube plugging and its anticipated effect on RCS flow.
The reanalysis has shown that 'a 'technical,Speci-f'ication amendment is necessary to support operat on 'under these conditions.
The proposed amendment is desc='bed below and shown on the accompanying Technical Specification pages bearing the date of this letter in the lower right hand corner.
Figure 2.,1-1 A note is added to the reactor core thermal and hydraulic safetv limit curves for 3-loop operation to indicate that the curves are applicable when steam generator tube plugging is less than or equal to 15%.
Additional reactor core, thermal and hydraulic safety limit curves for 3-loop operation have been developed to incor-porate a reactor coolant system flow rate of'88 thermal design flow.
These curves will be applicable when steam generator tube plugging is greater than 15% but less than or equal
.to 19%.
Pa e 2.3-2 Page 2,.3-2 for Unit 3 and page 2.3-2a for Unit.
4 are com-bined into one page applicable to both units.,
A, note is
),.il~
3(i(0 PEOPLE... SERVING PEOPLE
0 I
t
iver. Victor Proposed Amen'ment
-Pa e Two rector added to lower the factor Kl for 3-loop operation from 1.095 to 1.08 when steam generator tube plugging is greater than 15% but less than or equal to 19%.
Pa e 2.3-3 Page 2.3-3 for Unit 3 and page 2.3-'3a for Unit 4 are com-bined into one page applicable to both units.
A note is added to lower the factor 1.11 in the Overpower hT equation to 1.10 when steam generator tube plugging is greater than 15% but less than or equal to 19%.
Page 3.1-7 for Unit 3 and page 3.1-7a for Unit 4 are com-bined into one page applicable to both units.
A note is added to lower the "reactor coolant flow" DNB parameter from 268,500 gpm to 263,130 gpm when steam generator tube plugging is greater than 15% but less than or equal to 19%.
Page 3.2-3 The hot channel factors of Specification 3. 2.6 are revised to provide separate specifications for steam generator tube plugging less than or equal to 15 percent and for tube plugging greater than 15 percent but less than or equal to 19 percent.
The proposed amendment has been reviewed by the Turkey Point Plant Nuclear Safety Committee and the Florida Power
& Light Company Nuclear Review Board.
They have concluded that it does not affect the health and safety of the public..
A safety evalua-tion is attached.
Very truly yours, Robert E. Uhrig Vice President REU/HAS/lah Attachment cc:
Nr.
James P. O'Reilly, Region II Robert Lowenstein, Esquire
STATE OF FLORIDA
)
)
COUNTY OF DADE
)
ss.
Robert E. Uhrig, being first, duly sworn, deposes and says=
That he is a Vice President, of Florida Power
& Light Companyr the Licensee herein; That he has executed the foregoing document,; that the state-ments made in this said document are true and correct to the best of his knowledge, information, and belief, and that he is authorized to execute the document on behalf of-said Licensee.
Robert E. Uhrig Subscribed and sworn to before me this aaV o9 19~)
NOTARY PUBLIC, in and for the County of Dade, State of Florida My commission expires:
0
~ y ~
I H'
t,"~ '.
(5 ~
f