ML18227B280

From kanterella
Jump to navigation Jump to search
Submit Proposed Facility Operating Licenses with ECCS Reanalysis
ML18227B280
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 01/27/1978
From: Robert E. Uhrig
Florida Power & Light Co
To: Stello V
Office of Nuclear Reactor Regulation
References
L-78-32
Download: ML18227B280 (8)


Text

REGULATORY INFORMATION DISTRIBUTION SYSTEM'RID~

DISTRIBUTION FOR INCOMING MATERIAL 25i REC: STELLO V ORG: UHRIG R E DOCDATE: 0 l/27/78 NRC FL PWR 5 LIGHT DATE RCVD: 02/0 l/78 DOCTYPE: LETTER NOTARIZED: YES COPIES RECEIVED

SUBJECT:

LTR 3 ENCL 40 LICENSE NO DPR-3l 5 4l APPL FOR AMEND: TECH SPECS PROPOSED CHANGE CONCERNING APPENDIX A> REVISIOIV TO THE ECCS ANALYSIS PERTAINING TO THE THERMAL AND HYDRAULIC SAFETY LIMIT CURVES FOR 3-LOOP OPERATION... NOTORIZED Ol/27/78.

PLANT NAME: TURKEY 'POINT UNIT 3 REVIEWER INITIAL: X JM TURKEY POINT UNIT 4 DISTR IBUTER INITIAL:

++++++<4++4~++4++4. DISTRIBUTIOIV OF THIS MATERIAL IS AS FOLLOWS 4++4+<+<<4++<<<<<<

GENERAL DISTRIBUTION FOR AFTER ISSUAlVCE OF OPERATING LICENSE.

(DISTRIBUTION CODE A00l)

FOR ACTION: BRANCH CHIEF EAR++W/7 ENCL INTERNAL: REG FILE++W/EN L NRC PDR++W/ENCL OELD+4~LTR ONLY HANAUER++W/ENCL CHECK++W/ENCL EI SENHUT++W/EIVCL SMAO~+W/ENCL BAER4>W/ENCL BUTLER+~W/ENCL GRIMES~~W/ENCL J. COLLINS<4 W/ENCL J. MCGOUGH++W/ENCL EXTERNAL: LPDR~S MIAMIi FL++W/ENCL T I C++W/ENCL NSIC++W/ENCL ACRS CAT B>>W/lb ENCL DISTRIBUTION: LTR 40 ENCL 39 CONTROL NBR: 780320024 I

S ZE: 2P+ i P+37P THF END ,I

~

~ <

p

. O. BOX 013100, 'MIAMI, FL 33101 FLORIDA POWER & LIGHT COMPANY January 27, l978 L-'78-32 Director of Nuclear Reactor Regulation Attention: Nr. Victor Stello, Director Division of Operating Reactors ~fg lf~

U. S. Nuclear Regulatory Commission l

CB 'g Igpa~

Nashington, D.C. 20555

Dear Nr. Stello:

~ASS g~11 Re: Turkey Point Units 3 and 4 Docket .Nos. 50-250 and 50-251 Ltd Proposed Amendment to Facility 0 erati;n Licenses DPR-31 and DPR-41 Xn accordance with 10 CFR 50;30, Florida Power s Light; Company submits herewith three (3) signed'riginals ance forty (40) copies of a request to amend Appendix A of Facility Gperating Licenses DPR-31 a'nd DPR-41.

t An ECCS reanalysis has',be'en performed .assuming greater, than 15% steam generator tube plugging and its anticipated effect on RCS flow. The reanalysis has shown that 'a 'technical,Speci-f'ication amendment is necessary to support operat on 'under these conditions. The proposed amendment is desc='bed below and shown on the accompanying Technical Specification pages bearing the date of this letter in the lower right hand corner.

Figure 2.,1-1 A note is added to the reactor core thermal and hydraulic safetv limit curves for 3-loop operation to indicate that the curves are applicable when steam generator tube plugging is less than or equal to 15%.

Additional reactor core, thermal and hydraulic safety limit curves for 3-loop operation have been developed to incor-porate a reactor coolant system flow rate of'88 thermal design flow. These curves will be applicable when steam generator tube plugging is greater than 15% but less than or equal .to 19%.

Pa e 2.3-2 Page 2,.3-2 for Unit 3 and page 2.3-2a for Unit. 4 are com-bined into one page applicable to both units., A, note is

),.il~

3(i(0 PEOPLE... SERVING PEOPLE

0 I t

iver. Victor rector Proposed Amen'ment

-Pa e Two added to lower the factor Kl for 3-loop operation from 1.095 to 1.08 when steam generator tube plugging is greater than 15% but less than or equal to 19%.

Pa e 2.3-3 Page 2.3-3 for Unit 3 and page 2.3-'3a for Unit 4 are com-bined into one page applicable to both units. A note is added to lower the factor 1.11 in the Overpower hT equation to 1.10 when steam generator tube plugging is greater than 15% but less than or equal to 19%.

Page 3.1-7 for Unit 3 and page 3.1-7a for Unit 4 are com-bined into one page applicable to both units. A note is added to lower the "reactor coolant flow" DNB parameter from 268,500 gpm to 263,130 gpm when steam generator tube plugging is greater than 15% but less than or equal to 19%.

Page 3.2-3 The hot channel factors of Specification 3. 2.6 are revised to provide separate specifications for steam generator tube plugging less than or equal to 15 percent and for tube plugging greater than 15 percent but less than or equal to 19 percent.

The proposed amendment has been reviewed by the Turkey Point Plant Nuclear Safety Committee and the Florida Power & Light Company Nuclear Review Board. They have concluded that it does not affect the health and safety of the public.. A safety evalua-tion is attached.

Very truly yours, Robert E. Uhrig Vice President REU/HAS/lah Attachment cc: Nr. James P. O'Reilly, Region II Robert Lowenstein, Esquire

STATE OF FLORIDA )

) ss.

COUNTY OF DADE )

Robert E. Uhrig, being first, duly sworn, deposes and says=

That he is a Vice President, of Florida Power & Light Companyr the Licensee herein; That he has executed the foregoing document,; that the state-ments made in this said document are true and correct to the best of his knowledge, information, and belief, and that he is authorized to execute the document on behalf of- said Licensee.

Robert E. Uhrig Subscribed and sworn to before me this aaV o9 19~)

NOTARY PUBLIC, in and for the County of Dade, State of Florida My commission expires:

0 H'

t,"~ '.

~ y~

(5 ~

I f