NRC FORM 195 12 76I KRC DISTRIBUTION FQR PART 50 DO U.S. NUCLEAR REGULATORY COMMISSION CKET MATERIAL FILE NUMBER MONTHLY RE Ne Ro CD FROM:

Florida Power

& Light Company Miami, Florida A.

D Schmidt DATE OF DOCUMENT.

5/5/77 DATE RECEIVED 5/l2/77 LETTER i%ORIGINAL OCOPV ONOTORIZED UNCLASSIFIED PROP INPUT FORM NUMBER OF COPIES RECEIVED

(

g 1 g rc/pA DESCRIPTION Iatter trans the following:

g(lIIII~gIIik IImm N.III~%

ENCLOSURE Monthly Report for APRIL, 1977 Plant

&, Component Operability

&, Availability.

+is Report to be used in preparing Gray Book by PlanS 8 Operations.

(l-P)

(B-P)

PLQPV NAME Turkey Point Units 3

& 4 RJL 2-CYS FOB CTI N FOR ACTION/INFORMATION INTERNALD IST RI BUTION C

D rane e

ss EXTERNAL Dl T IBUTION CGNTROL NUMBER 77134OOlg NRC FORM 196 <2 75)

P. O. BOX 013100, MIAMI, FL 33101 FLORIDA POWER & LIGHT COMPANY May 5, 1977 Office of Management Information and Program Controls U.

S. Nuclear Regulatory Commission Washington, D.

C.

20555 Qfe gea4~~W Gentlemen:

Attached are the April, 1977, Operating Status Reports for Turkey Point Unit Nos.

3 and 4 and St. Lucie Unit No. l.

Very truly yours, A. D. Schmidt Vice President Power Resources VTC/DDC cc:

Mr. Norman C. Moseley Robert Lowenstein, Esquire 77134OI)gP PEOPLE... SERVING PEOPLE

APPENDIX B AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50 - 250 Turkey Point UNIT Unit No.

3 DATE Bay 5, 1977 COMPLETED BY >. T. Chxlson TELEPHONE

{305) 552-3769 MONTH A ril 1977 DAY AVERAGE DAILY POWER LEVEL (NHe-Net)

DAY AVERAGE DAILY POWER LEVEL QÃe-Net) 10 12 13 677 673 673 669 672 673 623 567 683 680 678 683 682 17 18 20 21'2 23 24 25 27 28 29 671 666 667 665 656 341 603 308 676 671 30 666 16 668 NOTE:

Average daily power greater than 666 MWe due to cooler condenser cooling water.

APPRiDIX C OP~TDiC DATA RZPORT REPORT NONTH April 1977 DOCKET NO.

50 - 250 Turkey Point UNIT Unit No.

3 DATE Na 5.

1977 OPERATING STA,CS CO%'LTD BY V. T. Chilson TZLZPHONE (305) 552-3769 9~ ~

~OR '~C PERIOD: 0001977904901 GROSS HOURS ZN RZPORTZtG PERIOD:

THROUGH 240 7

CURRY-.

Y *L NOR m

?Ot cR ~VZL (MWt):

2200 M.DEPEND.

CAPACITY (NWe-Net):

666 DKSLGN ELECTRICAL RATLlG (NWe Net):

693 719.0e 3.

POtEER L~c, TO Vc5ZCH RvZSTRX~ (I: A:SY)

(NWe<<Net):

NONE 4.

RZASONS FOR RZSTRIC XGN (I A!V):

THIS NONTH YEAR.0 DAA=

CSJMJLATXVK 5

~

ÃRBERS 0.

EQ"RS MAC QR EAS C'4 2 CAC.....

594.2 29982I 6.

RECTOR RZSKRVE S~a

~

OWN HOURS 0

0-HOURS CBPcRATOR ON LLfE...................

579.6 2 246.5

~2 8.

UNIT RESKVS'K SETDOWN HOURS..

~.

~ ~ ~.

~ ~.

~.

~. ~8. 0 9.

GROSS ESERM~ B~c-GY G=KRATKD (NWH)....,

~

1 244 675 4 783 145 56 512 733 10.

CROSS K'"CTR M. DRGY G>cERATKD (NtEH)...

401 220 1 554 580 18 125 031 NET K ~GAL hWGY G~c ZD (WH). ~ ~ ~.

380 593 1 474 705 17 150 690 12.

RKAC.OR SERVICE FACTOR.

82.6 83.0 REAC OR AVAZLABILZY FAC:OR.....

~.....,...

82.6 83.0 78.8 79.0 14.

LN SEESVZCE FAC OR.

80.6 78.0 75.8

)5 UNZT AVAIEMILZ.. -.ACTOR~,

80.6

78. 0 76.1 264 IDGT CAPACI FACMR (Using,'K)C)
79. 5 76.9

~62

)7.

UNZ CAPAC.Y FAC"AOR (Using Design NWe)...

76.4 73.9 S

ZNiIT FORCE OLlACE RATE ~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

1.7 1.5 2.8 19.

25.

SHCTDOWNS S~~tA'LKD OVEt NEXT 6 NONTHS (TYPES DAT=S AV) DURATION OF EACH) c Steam Generator Inspection - JuLy 10 - Aug.

6, 1977

'IP SHUTDOWN AT BG) OF iQPORT P~vODS EST~TG) DAT OF STARTUP:

'2 2 MJITS XN TEST STAAJS (PR OR TO CON(ERCZAL OPTATION):

L'EiM. CRZTZCALZY ZNITZAL ELEC RIC

~A FORECAST COMKRCM. OPERATION NOTE:

Change to Daylight Saving Tine

I)

REASOH A:

Ki)UIPHENT FAILURE (EXPLAIN)

B:

HAIHI'. OR TEST I'.:

RFFIIEI.INC D:

RECUIATORY RESTRTCTION F.:

Ol'KkATOR TkhllilNC AND I.ICKNS8 EXAHINATI OH F:

ADHIHISTRATIVE C:

OPKRATIOtihl. FIIROR (KXPIAIH)

II:

OTIIER (KXI'ITIN)

APPENDIX D IINIT SIIUTDOWNS AND POMFR REIRICTIONS REPORT HONTII~A ril 1977 POCKET NO.

50 - 250 UNIT NAHE Turks Point Unit No.

3 DATE Hay 5, 1977 COHPI.ETED DY V. T. Cbllson TEI.KPHOIIE (305) 552-3769

.')

HETIIOD I:

IIANIIAI.

2:

HANIIAI. SCRAH 3:

AUTIRIATIC Si:RAII ll'<Iiiii (KXPIAIN)

NO.

l)ATE TYPF.

F:

FORCED S:

SCIIKDUI.KD DURATION (IIOIIRS)

RFASON(1)

HETI(OD OF SIIUTTING DOMN TIIE REACTOR OR REDIICIHC I'OMER(2)

CORRKCT1VE ACTIONS/COflHENTS 12 13 77-04-07 77-04-22 77-04-24 9.8 129.6 B

Load reduction to perform periodic test of turbine main steam stop, reheat stop, and reheat intercept valves.

(Non-nuclear system)

Unit No.

3 uas removed from service to repair stem packing leak on drain valve located inside contain-ment.

(Nuclear system) linlt No.

3 vss removed from service for maintenance.

(Nuclear and Non-nuclear system)

SIIHHARYt Unit No. 3 operated st approximately 100X R.P. except for load reduction on April 7, 1977, snd outages on April 22, and April 24 to 29, 1977.

APPEG)IX C OPERATIC DATA REPORT REPORT HONZH April 1977 OPERAT NG STATUS DOCKET NO.

50 - 251 Turkey Point T Unit No.

4 DATE May 5, 1977 CQ.JP~

BY V. T. Chilson TELEPHONE (305) 552-3769 2.

ABORTING,PHGOD:0001,77,04,01 CROSS HOURS & REPORTER PERIOD:

THROUGH 2400 77 04 CURRY<"'4I MTHORI~ ?OVER I~cL (66it):

2200 NAX.DEPEND. CAPAC TY (RJMe-Net):

666 DESIGN ELECTRZCAL RATZfG (NJe-Net):

693 719.0*

3.

POJU~

UMBEL TO J"EJZCH RESTRI~~

(IF ANY)

(Sie-Net):

4.

~AEONS FOR RESTRICT ON (IF ANY)-

NONE THIS NONTH YEAR TO DATE CRRJLATIVE S.

RL RIESS OS RGURS IIEACOR UAS,CREEICAL..... ~6.

~cE 24-11JLZ 6.

REACTOR 3

3 'IUE SRUEOOIIR ROUSE

~ ~ ~

~

~

~

~ ~

~

~ ~.

~ ~

~SCIL 7 ~

HOURS Gc>ERAAOR ON LINEA ~

~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

611.0 2 375.2 22 917.2 8.

UNI RESERVE SHUTDOWi HOURS.

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~. 9 GROSS SIKE AL IDGE G IERAEEO OUIRI

~1334 0

~4~4 61~

10 GROSS ELEC~CAL ~CY G~TED (NJZ>..

433 400 1 685 065 15 642 748 11.

NET HSCTRZCAL c~~{CY Cc~&TED (NJ'H).....

412 373 1 602 874 14 833 340 12.

REACTOR SERVICE FACTOR....

85 0 83.2

74. 6 13 ~

REACTOR AVAILABZLITi Y~ FA~R

~ ~ ~ ~ ~ ~ ~ ~ ~ ~, ~ ~ ~

83.2 14 ~

UNIT SERVICE FACTOR.

85.0 82.5 15.

UNIT AVAILABILITYFA~R,.......,...,.. ~.

85.0 82.5 16.

K{IT CAPACI Y FAC OR (Using

(.'GDC)... ~.

86.1

83. 6 75.0
70. 9 70.9 69.5 17.

UNIT CA?ACZTY FACTOR (Using Design MJie) ~ ~.

18.

UNIT FORCED OUTAGE RAT

~.4 ~ ~

~.....

~....

~

82.8 80.3 66.2 3-2 19 'HUTDOJJÃS SCHEDL'LED OVER NEE 6 NO~M (TYPE, DA AhD DURATION OF Refueling, maintenance9 and inspections -.ay 9 " July 9, 1977 20.

IF SHUTDOWN AT Cia) OP REPORT PHLIODR EST&DYED DATE OF STAR'LLP. Na39 EACH) 4 1977 21 ~

UNITS IN TEST STATUS (PRIOR TO CNMZCIAL OPERATION):

FORECAST ACHIEVED L!ITIALCRITICAL TY LJZTIAL ELECTRICITY CO.'QKRCIAL OPERAT ON NOTE:

  • Change to Daylight Saving Time

APPENDIX B AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50 - 251 Turkey Point UNIT Unit No.

4 DATE Ma 5,

1977 COMPLETED BY V. T. Chilson TELEPHONE (305) 552-3769 MONTH April 1977 DAY AVERAGE DAILY POWER LEVEL (Kle-Net )

DAY AVERAGE DAILY PO~ LEVEL (MWe-Net) 10 12 13 14 15 671 670 673 673 674 673 683 682 682 684 691 692 687 679 682 676 17 18 19 20 21'2 23 24 25 26 27 28 29 30 NOTE:

680 682 678 675 675 672 671 641 671 282 Average daily power greater than 666 MWe due to cooler condenser cooling water.

I)

REASI)N A:

EliUII'HENT FATI.URE (EXPIAIN)

B:

IIAINT. OR TEST C:

REFUEI.INC n:

REI:UIWTORY RESTRrCT1ON E:

Ol KkhTOR TRAININC AND I.ICENSE EXAHINATION F:

Ale!INISTRATIVE Ol'ERATIONAI~ ERROR (EXPIhIN)

II:

I)TillR (KXI'IAI N)

APPENDIX 0 UN1T SUUTIRIWNS AND POWER REDUCTIONS RPPIIIIY lll)HTII~Arll1977 DATE Ha 5

1977 COHI'I.ETED BY V. T. Chilson TEI.EI'IIONE (305) 552-3769 DOCKET NO.

50 - 251 UNIT NAHE Turke Point Unit No.

4

!)

HYTIIOD I:

HANUAI, 2:

HANUAI. SCRAH 3:

AUTOHATIC SCRAH 4:

03IIER (EXI'I.A1N)

NO.

DATE TYPE F:

FORCED S:

SC!!EDUCED DURATION

(!!OURS)

RCASON(1)

HETIIOD OF SIIUTTINC DOWN TIIE REACTOR OR REDUC)NC POWER(2)

CORRECT1VE ACTIONS/COHHENTS 77-04-26 108.0 Unit No.

4 was removed from service to repair steam generator No.

4C tube leak.

Corrective actions included plugging three leaking tubes.

Additional tubes vere plugged as a preventative measure.

(Nuclear system)

SUHHARY: Unit No.

4 operated at approximately 1002 R.P. except for outage of April 26 to Hay 4, 1977.

APPENDIX B AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. St. Lucie UNIT Unit No.

1 DATE Ma 5,

1977 COMPLETED BY V. T. Chilson TELEPHONE (305) 552-3769 MONTH A ril 1977 DAY AVERAGE DAILY POWER LEVEL (MWe-Net) 755 773 181 DAY AVERAGE DAILY PO~r.

LEVEL (MWe-Net) 17 18 19 20 21'2 23 24 10 12 14 188 786 794 776 509 25 26 27 28 29 30 150 242 NOTE:

Average daily power greater than 777 MNe due to cooler condenser cooling water.

APP DW C OPERATZNG DATA REPORT DOCKET NO.

50 - 335 UAAI St. Lucia Unit No.

1 REPORT HONTH Aotsl 1977 DATE Mav 5 1977 C0%'~

BY V. T. Chi1son OPERA~0 STA US TELEPHONE (305) 552-3769 2.

R~ORTING PERIOD: 0001.77 04 01 GROSS HOURS Ll ABORTING P~vOD:

THROUGH 2400 77 04 CUR~VY AUTHORIZE PO~

LEVR.

(NWt):

2560 NAX DEPDlD. CAPACITY (NWe-Net):

777 (Est.)

DESIGN -

eC RICAL RA ING (NWe-Net):

802 719.0+

3.

POWER LEI'EL.0 WHICH RESTRI~J (XF ANY)

(Mle-Net):

4 ~

MASONS FOR RESTRICTION (I: A'ST):

NONE THIS HOisTH YEAR TO DATE CUMlLATIVE S.

RIRRRRS OS COORS RSACSOR RAS CRL.RCAL.....

2OI.A

~2

~~ZLJi 6.

RZACTOR RZSERV SHU'JJOWN HOURS...........

~ 7 ~

HO?ARS GRKRA OR ON LLlEA 8.

l.'NIT RESERVE SH..DOlsN HOURS...............

181.8 2 217.4 2 481.4 9 ~

GROSS ANNAL HKRGY GENERATED (?lWH)......

407 185 4 706 482 5 054 085.

10.

GROSS ELEC RXCAL ~GY GElERA ZD (?URH)...

133 040 1 545 000 1 653 270 1

AAEJ G

~J. ICAL RiGLGY GENERATED (N?RH). ~. ~ ~

118 624 1 440 576 1 539 551 12.

~vC.OR SERVICE FAC OR.

28.8 80.3 82.0 13.

REACJJ)R AVAILABXL'XTYFACTOR...........

~. ~.

28. 8 80.3 14 UNIT SERVICE FAC OR

~ ~ ~

~ ~ ~

~ ~ ~

~ ~ ~ ~ ~

~'7.0

82. 0 79 '

15.

UNIT AVAI~ILXTYFACTOR... ~...

~ ~ ~........

25 ~ 3 77.0 16 ~

?D(IT CAPACI~J PACER (Ushzg

(?lDC)..........

21.2 64.4 79.0 63.0

'7 ~

UNX CAPACITY FACTOR (Using Design NWe)...

18 ~

UNXJ FORCED OUTAGE RATEA ~ ~ ~ ~

s ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~

20.6 74.7 62.4 21.1 61.1

19. 3 19A SHUTDOWilS SCLSZDULZO OVER NEX 6 NONTHS (TYPE, DATE, AND DURATION OF EACH):

29.

XF SHU,DOWN AT EG) OF REPORT

PERXOD, ESTDfATZD DATE OF STAR~i 21.

UNITS EN TZS.

STATUS (PRIOR TO COMKRC~ OPERATION):

XNI IAL CRITICALITY INITIALELZ~XCITY CO. KRCIAL OPERATION FORECAST ACHI VED NOTE:

Change to Daylight Saving Tine

(I)

REASON A:

El)UIPHFAIT FAIIAIRE (EXPLAIN)

B:

IIAINT. OR TEST C:

RFFUELIHC 0:

<<EOUIATORY RESTRICTION E:

OPL'RATOR TEAININO AND LICENSE EXAMINATION F:

AININIS'I'RATIVE 0:

OPE<<ATIOHAL ERROR (EXPIWIH)

II:

OTII FR (EXP ITIN)

APPENDIX D UNIT SIIUTDOWHS AND POWER REDUCTIONS DOCKET HO.

WHIT NAHE 50 - 335 St. Lucie Unit No. I DATE HQ 5

1977 TEI.EPNOHE (305) 552-3769 COHPLETED BY V. T. Chilson (2)

METHOD 1:

HANUAI.

2:

MANUAL SCRAH 3:

AUTOMATIC SCRAH 4:

OlllEil (EXPLAIN)

HO.

DATE TYPE PI FORCED S:

SCHEDULED DURATION (IIOURS)

REASON(1)

HETIIOD OF SIIUTTIHC DOWN TIIE REACTOR OR REDUCING POWER(2)

CORRECTIVE ACTIONS/COtDIFNTS 12 77-04-03 200.0 Unit was manually tripped uhcn a fire occurred In l.hc area of the general. or main lead box.

Corrective actions Included repairing hydrogen leak and modifying generator main lead box.

Outage uas extended to perform other maintenance uork.

(Non-nuclear system) 13 77-04-15 77-04-30 332.5 4.6 Unit uas manually tripped due to loss of containment instrument air vhich resulted In loss of component cooling uater to equipment located inside containment.

Corrective actions included replacing the instrument air compressor discharge check valves and providing sn automatic redundant instrument sir supply.

(Nuclear System) t Unit uas tripped during transient condition caused by malfunction of heater drain pump control system.

(Hon-nuclear system)

Unit operated at approximately 99X R.P. except for unit outsges on April 3 to ll, April 15 to 29, and April 30, 1977.