Region III Fire Protection Utilities Group Meeting Atif Shaikh Dariusz Szwarc June 12, 2018 ADAMS Accession Number: ML18176A340
Topics
- Fire protection staff
- PFSSD training
- Inspections
- Findings
- Inspection procedure changes 2
Fire Protection Staff
- EB3 inspectors
- Alan Dahbur, Jasmine Gilliam, Jessie Hafeez, George Hausman, John Robbins, Atif Shaikh, Dariusz Szwarc
- DRP inspectors
- DRS inspectors 3
Post Fire Safe Shutdown Training
- IMC 1245, Appendix C-7
- Completed
- NRC inspectors
- NUREG Handbook 4
2017 and 2018 Inspections
- Monticello 2017007
- Fermi 2017012
- LaSalle 2017010
- Duane Arnold 2018010
- Palisades 2018011 & 2018415 (reports not issued)
- Braidwood 2018013 (report not issued) 5
Upcoming Inspections
- 2018
- Perry
- 2019
- Byron
- Davis-Besse
- Prairie Island (NFPA 805)
- Point Beach (NFPA 805)
- Quad Cities 6
Recent Findings and Violations
- Inadequate Alternative Compensatory Measure
- Inadequate Appendix R Fire Barrier
- Fire Door Degraded Barrier
- Inadequate Pre-Fire Plans
- Inadequate AOP for SSD 7
Inadequate Alternate Compensatory Measure
- Monticello 2017007
- Non-conforming fire barrier
- Identified during 2014 inspection
- Replenishment of diesel fuel
- Requirement for continuous fire watch 8
Inadequate Appendix R Fire Barrier
- Monticello 2017004
- LER 2016002-02 Closeout
- Fire causes CR evacuation
- Path to remote shutdown panel passes through fire
- Green NCV 9
Fire Door Degraded Barrier
- LaSalle 2017010
- Fire door not engaged and pinned
- Door lower pin missing and broken
- Missed daily surveillance identification
- Green NCV 10
Inadequate Pre-fire Plans
- Duane Arnold 2018010
- 2 Examples of deficient PFPs
- PFPs lacking fire hazard information
- Battery room and switchgear room
- Green NCV 11
Inadequate AOP for SSD
- Duane Arnold 2018010
- Operator action to isolate RWCU due to fire
- Operator action removed from AOP
- Action required to meet NSCA
- Green NCV 12
- Clinton 2017008
- MSOs are a requirement
- Licensee dispositioned identified MSOs
- Analysis not limited to four components
- SSD path components 13
Potential IP Changes
- Triennial versus quadrennial
- Self-assessments
- Reduction in resources
- FP as a program inspection
- 2018 decision 14
Summary
- Fire protection staff
- PFSSD training
- Inspections
- Findings
- Inspection procedure changes 15