Calvert Cliffs GSI-191 Program Use of Risk Metrics for Containment Sump Tech Spec Operability Determination June 21, 2018

Future Licensing Basis

  • After the Risk-Informed GSI-191 license amendment is approved, Calvert Cliffs licensing basis for operability of emergency recirculation sump will be risk-based.

- The risk of LOCA events that could threaten strainer performance is Very Low, which is consistent with RG 1.174 acceptance guidelines

  • Proposed Technical Specification for the Containment Sump Summary of Calvert Cliffs Risk-Informed Approach 1

Debris Acceptance Guidelines

  • The following is the proposed risk metric to be added to the UFSAR.

RISK INCREASE LIMITS DUE TO CONTAINMENT DEBRIS

- The CDF or LERF values due solely to the effects of debris on the emergency recirculation strainer may not exceed the following limits.

- Maximum CDF limit = 3.0E-07 - Maximum LERF limit = 3.0E-08

- Current preliminary results from GSI-191 risk analysis Summary of Calvert Cliffs Risk-Informed Approach 2

Questions/Concerns

  • Jointly Review Issues, Questions, and Concerns Summary of Calvert Cliffs Risk-Informed Approach 3