e e
VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 September 18, 1990 United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D. C. 20555 Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT 2 10 CFR 50 APPENDIX J EXEMPTION REQUEST ADDITIONAL INFORMATION Serial No.
90-570A NO/ETS Docket Nos.
50-281 License Nos. DPR-37 In our letter of September 14, 1990 (Serial No.90-570), a one-time exemption from 1 OCFRSO, Appendix J, Section 111.D.3, was requested for Surry Unit 2 to extend the Type C test interval until the upcoming refueling outage. In a subsequent telephone conversation between our staffs, additional information was requested to augment our submittal. The enclosed attachment provides the requested information.
If you have additional questions regarding this information, please contact us.
W. L Ste rt Senior Vice President - Nuclear Attachment cc:
U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, N. W.
Suite 2900 Atlanta, Georgia 30323 Mr. W. E. Holland NRG Senior Resident Inspector Surry Power Station
ATTACHMENT SURRY POWER STATION UNIT 2 CONTAINMENT ISOLATION VALVE TYPE C TEST EXEMPTION ADDITIONAL INFORMATION
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 007 2-Sl-0150 09/04/89 09/04/91 No Globe MOV-S l-2867C 09/04/89 09/04/91 No Split Wedge Gate MOV-Sl-2867D 09/04/89 09/04/91 No Split Wedge Gate System: Safety Injection 015 2-CH-0309 09/22/88 09/22/90 Yes-2 Check MOV-CH-2289A 09/03/89 09/03/91 No Split Wedge Gate System: Charging and Letdown 019 MOV-CH-2381 07/05/89 07/05/91 No Split Wedge Gate System: Charging and Letdown 020 2-Sl-0032 12/06/88 12/06/90 Yes-4 Globe System: Safety Injection 021 MOV-Sl-2842 07/22/89 07/22/91 No Split Wedge Gate System: Safety Injection page 1 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 023 MOV-Sl-28698 09/03/89 09/03/91 No Split Wedge Gate System: Safety Injection 024 MOV-RH-0200 09/26/88 09/26/90 Yes-3 Solid Wedge Gate System: Residual Heat Removal 028 HCV-CH-2200A 01/20/89 01/20/91 Yes-1 Globe 028 HCV-CH-22008 01/20/89 01/20/91 Yes-1 Globe 028 HCV-CH-2200C 01/20/89 01/20/91 Yes-1 Globe 028 TV-CH-2204 10/01 /89 10/01 /91 No Globe System: Charging and Letdown 032 TV-GW-0202 09/23/88 09/23/90 Yes-4 Globe 032 TV-GW-0203 09/23/88 09/23/90 Yes-4 Globe System: Gaseous Waste 033 TV-DG-0208A 10/25/88 10/25/90 Yes-3 Globe 033 TV-DG-02088 10/25/88 10/25/90 Yes-3 Globe System: Primary Drain page 2 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 038 TV-DA-0200A 11/10/88 11/10/90 Yes-1 Ball 038 TV-DA-0200B 09/09/89 09/09/91 No Ball System: Aerated Drain 042 2-SA-0081 10/19/88 10/19/90 Yes-4 Solid Wedge Gate 042 2-SA-0082 10/19/88 10/19/90 Yes-4 Solid Wedge Gate System: Service Air 043 2-RM-0003 09/23/88 09/23/90 Yes-2 Check 043 TV-RM-0200A 09/23/88 09/23/90 Yes-2 Globe System: Radiation Monitoring 044 TV-RM-0200B 09/23/88 09/23/90 Yes-4 Globe 044 TV-RM-0200C 07/06/89 07/06/91 No Globe System: Radiation Monitoring 045 2-RC-0160 09/26/88 09/26/90 Yes-2 Check 045 TV-RC-2519A 07/10/89 07/10/91 No Diaphragm System: Reactor Coolant (Primary Grade Water - Header to Containment) page 3 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 046 FCV-CH-2160 10/03/88 10/03/90 Yes-1 Globe System: Charging and Letdown 047 2-IA-0704 10/02/88 10/02/90 Yes-2 Solid Wedge Gate 047 2-IA-0864 10/02/88 10/02/90 Yes-2 Check 047 TV-IA-0200 10/02/88 10/02/90 Yes-2 Globe System: Instrument Air 048 TV-VG-0209A 03/31 /89 03/31/91 Yes-4 Globe 048 TV-VG-02098 04/04/89 04/04/91 Yes-4 Globe System: Vent & Drain 050 TV-Sl-0201 A 12/05/88 12/05/90 Yes-4 Globe 050 TV-Sl-0201 B 12/10/88 12/10/90 Yes-4 Globe System: Safety Injection 051 2-SW-0206 09/18/88 09/18/90 Yes-4 Solid Wedge Gate 051 2-SW-0208 09/18/88 09/18/90 Yes-4 Solid Wedge Gate System: Service Water page 4 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 053 2-Sl-0304 09/24/88 09/24/90 Yes-2 Check 053 TV-Sl-0200 10/29/88 10/29/90 Yes-2 Globe System: Safety Injection 054 2-VA-0001 09/26/88 09/26/90 Yes-4 Solid Wedge Gate 054 2-VA-0009 09/26/88 09/26/90 Yes-4 Solid Wedge Gate System: Vent & Drain 055D TV-LM-0200E 09/18/88 09/18/90 Yes-4 Globe 055D TV-LM-0200F 09/18/88 09/18/90 Yes-4 Globe System: Leakage Monitoring 056A TV-SS-0206A 09/30/88 09/30/90 Yes-4 Globe 056A TV-SS-02068 09/30/88 09/30/90 Yes-4 Globe System: Sample 0568 TV-SS-0202A 02/14/89 02/14/91 Yes-4 Globe 0568 TV-SS-02028 02/14/89 02/14/91 Yes-4 Globe System: Sample page 5 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 0560 TV-SS-0200A 09/20/88 09/20/90 Yes-4 Globe 0560 TV-SS-02008 04/05/90 04/05/92 No Globe System: Sample 057A TV-SS-0201 A 08/05/89 08/05/91 No Globe 057A TV-SS-0201 B 07/14/89 07/14/91 No Globe System: Sample 0578 TV-DA-0203A 09/26/88 09/26/90 Yes-4 Globe 0578 TV-DA-0203B 10/29/88 10/29/90 Yes-4 Globe System: Aerated Drain*
057C TV-LM-0200G 09/18/88 09/18/90 Yes-4 Globe 057C TV-LM-0200H 09/18/88 09/18/90 Yes-4 Globe System: Leakage Monitoring 0570 TV-SS-0204A 09/01/89 09/01 /91 No Globe 0570 TV-SS-0204B 09/19/88 09/19/90 Yes-4 Globe System: Sample page 6 of 13
--~------
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 058 1-IA-0704 11/10/88 11/10/90 Yes-4 Solid Wedge Gate 058 2-IA-0868 07/06/89 07/06/91 No Check System: Instrument Air 060 MOV-S l-2890A 09/04/89 09/04/91 No Split Wedge Gate System: Safety injection 061 MOV-Sl-2890C 09/06/89 09/06/91 No Split Wedge Gate System: Safety Injection 062 MOV-Sl-2890B 09/04/89 09/04/91 No Split Wedge Gate System: Safety Injection 063 2-CS-0024 07/12/89 07/12/91 No Check 063 MOV-CS-0201 C 07/20/89 07/20/91 No Butterfly 063 MOV-CS-0201 D 07/20/89 07/20/91 No Butterfly System: Containment Spray page 7 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY
.064 2-CS-0013 07/12/89 07/12/91 No Check 064 MOV-CS-0201 A 07/21 /89 07/21/91 No Butterfly 064 MOV-CS-0201 B 07/21 /89 07/21/91 No Butterfly System: Containment Spray 066 MOV-RS-0255A 07/14/89 07/14/91 No Plug System: Recirculation Spray 067 MOV-RS-02558 07/14/89 07/14/91 No Plug System: Recirculation Spray 068 MOV-S l-2860A 08/20/89 08/20/91 No Split Wedge Gate System: Safety Injection 069 MOV-Sl-2860B 08/20/89 08/20/91 No Split Wedge Gate System: Safety Injection 070 2-RS-0011 11/30/88 11/30/90 Yes-1 Check 070 MOV-RS-0256B 09/03/89 09/03/91 No Butterfly System: Recirculation Spray page 8 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 071 2-RS-0017 01 /18/89 01/18/91 Yes-1 Check 071 MOV-RS-0256A 07/24/89 07/24/91 No Butterfly System: Recirculation Spray 089 2-VP-0012 10/07/88 10/07/90 Yes-1 Check 089 TV-SV-0202A 10/31/88 10/31 /90 Yes-1 Plug System: Auxiliary Steam and Air Removal 090 MOV-VS-0200C 11/19/89 11/19/91 No Butterfly 090 MOV-VS-02000 11/19/89 11 /19/91 No Butterfly 090 MOV-VS-0201 11/19/89 11 /19/91 No Butterfly System: Air Cooling & Purge 091 MOV-VS-0200A 11/19/89 11/19/91 No Butterfly 091 MOV-VS-0200B 11/19/89 11/19/91 No Butterfly 091 MOV-VS-0202 11/19/89 11/19/91 No Butterfly System: Air Cooling & Purge page 9 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION VALVE PEN NO NO. & TYPE 092 TV-CV-0250C Globe 092 TV-CV-0250D Globe 092 TV-GW-0204 Plug 092 TV-GW-0205 Plug LAST TEST DATE 11/03/88 04/03/90 01/30/89 09/22/88 System: Containment Vacuum and Gaseous Waste 093 093 093 093 TV-CV-0250A Globe TV-CV-02508 Globe TV-GW-0200 Plug TV-GW-0201 Plug 11/03/88 10/26/88 09/18/88 09/18/88 System: Containment Vacuum and Gaseous Waste 094 094 2-CV-0002 Flexible Wedge Gate HCV-CV-0200 Globe System: Containment Vacuum 0978 TV-SS-0203A Globe 0978 TV-SS-02038 Globe System: Sample 09/23/88 09/23/88 09/28/88 09/28/88 page 1 O of 13 TEST EXPIRATION DATE 11/03/90 04/03/92 01/30/91 09/22/90 11/03/90 10/26/90 09/18/90 09/18/90
'09/23/90 09/23/90 09/28/90 09/28/90 EXEMPTION &
TEST PRIORITY Yes-4 No Yes-4 Yes-4 Yes-4 Yes-4 Yes-4 Yes-4 Yes-2 Yes-2 Yes-4 Yes-4
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST VALVE LAST EXPIRATION EXEMPTION &
PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 097C TV-LM-0200A 09/18/88 09/18/90 Yes-4 Globe 097C TV-LM-0200B 09/18/88 09/18/90 Yes-4 Globe System: Leakage Monitoring 100 TV-GW-0206 09/30/88 09/30/90 Yes-4 Globe 100 TV-GW-0207 09/30/88 09/30/90 Yes-4 Globe System: Gaseous Waste 101 2-FP-0151 09/29/88 09/29/90 Yes-3 Ball 101 2-FP-0152 09/29/88 09/29/90 Yes-3 Ball System: Fire Protection 103 2-RL-0003 01/20/89 01/20/91 Yes-3 Diaphragm 103 2-RL-0005 01/20/89 01/20/91 Yes-3 Diaphragm System: Reactor Cavity Purification 104 2-RL-0013 01/20/89 01/20/91 Yes-3 Diaphragm 104 2-RL-0015 01/20/89 01/20/91 Yes-3 Diaphragm System: Reactor Cavity Purification page 11 of 13
e e
SURRY UNIT 2 CONTAINMENT ISOLATION VALVE ADDITIONAL INFORMATION TEST
\\
VALVE LAST EXPIRATION EXEMPTION &
I PEN NO NO. & TYPE TEST DATE DATE TEST PRIORITY 1058 TV-LM-0200C 09/18/88 09/18/90 Yes-4 Globe 1058 TV-LM-0200D 09/18/88 09/18/90 Yes-4 Globe System: Leakage Monitoring 105C TV-GW-0211A 09/30/88 09/30/90 Yes-4 Globe 105C TV-GW-0211 8 09/30/88 09/30/90 Yes-4 Globe System: Gaseous Waste 106 2-Sl-0073 09/18/88 09/18/90 Yes-4 Globe System: Safety Injection 112 TV-IA-0201 A 09/30/88 09/30/90 Yes-3 Plug 112 TV-IA-02018 09/30/88 09/30/90 Yes-3 Plug System: Instrument Air 113 2-Sl-0174 07/27/89 07/27/91 No Globe 113 MOV-S l-2869A 07/27/89 07/27/91 No Split Wedge Gate System: Safety Injection page 12 of 13
J e
e VALVE TESTING PRIORITY In the event of an unplanned, extended outage prior to the Cycle 10 refueling outage, the valves included in the exemption request will be tested, with the following priorities: (1) first test the valves with the highest leakage history, (2) then test stop check valves, (3) and then larger sized valves, (4) and finally, test the smaller sized valves. In addition, the projected length of the forced outage will be considered when determining valve testing priorities.
page 13 of 13