Responds to NRC Bulletin 89-002, Stress Corrosion Cracking of High-Hardness Type 410 Stainless Steel Internal Preloaded Bolting in Anchor Darling Model S350W Swing Check Valves or or Valves.... Util Replaced Studs in twenty-five Valves
ML18153C073
Person / Time
Site: Surry, North Anna, 05000000
Issue date: 01/15/1990
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
89-548, IEB-89-002, IEB-89-2, IEIN-88-085, IEIN-88-85, NUDOCS 9001240001
Download: ML18153C073 (4)


Text

I I

I

~,

  • United States Nuclear Regulatory Commission Serial No.89-548 Attention: Document Control Desk
  • NO/JZL:

Washington, D. C. 20555 Docket Nos. 50-280 50-281 50-338 50-339 License Nos. DPR-32 DPR-37 NPF-4 NPF-7 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNITS 1 AND 2 NORTH ANNA POWER STATION UNITS 1 AND 2 NRC BULLETIN NO. 89-02: STRESS CORROSION CRACKING OF HIGH-HARDNESS TYPE 410 STAINLESS STEEL INTERNAL PRELOADED BOLTING IN *ANCHOR DARLING MODEL S350W SWING CHECK VALVES OR VALVES OF SIMILAR DESIGN NRC Bulletin No. 89~02 advises recipients of the potential failure of Anchor Darling

  • susceptible to sec and/or if cracking has occurred.

'::-'00:l :I. 5

()::; t)l)(i~? :::: ,.)

FDC

I S350W swing check valves. The replacement studs were of a new material recommended by Anchor Darling, ASTM A564-630-1100, which is not Type 41 o stainless steel. Therefore, while Virginia*Electric and Power Company does use the Anchor Darling Model S350W swing check*valve, none of the valves are susceptible to the failure described in Bulletin 89-02. While no specific examination of the original retaining block studs was performed, no obvious defects or broken studs were noted.*

We also evaluated other check valves used at our nuclear power stations to determine if a similar concern might exist for other valves. We have determined that Velan check valves, Models B10-31148-13MS and B14-3114B-13MS, may use ASTM A193 Grade 86 material for fhe hanger' bracket bolts. The hanger bracket bolt in the Ve Ian valve is analogous to the retaining block stud in the Anchor Darling valve. Velan check valves are used at both North Anna and Surry Power Stations in the chemical and volume control system and the safety injection system. We identified 50 potentially applicable Velan check valves at North Anna Power Station and 47 applicable Velan check valves at Surry Power Station. Component drawings for the Surry Power Station show the hanger bracket bolt as ASTM A 193 Grade 86. Component drawings for the North Anna Power Station, which are a later revision, show the hanger bracket bolt as ASTM A 193 Grade 88. ASTM A 193 Grade 88 is not a Type 41 O stainless steel and is therefore not susceptible to the SCC failure discussed in Bulletin 89-02. Accordingly, we consider the Velan check valves at Surry Power Station to be within the scope of NRC Bulletin 89-02, while the Velan check valves at North Anna Power Station are not.

In accordance with NRC Bu*lletin 89-02, the safety-related Velan check valves at Surry Power Station which may contain Type 41 O hanger bracket bolts will be inspected at

- the next available refueling outage of each unit. The Type 410 hanger bracket bolts will be replaced with non-Type 41 O bolting. The results of our inspection will be provided to the NRC within 60 days of completion, as required by Bulletin 89-02. We also intend to inspect a portion of the Velan check valves installed at North Anna Power Station, to confirm that non-Type 410 hanger bracket bolts were used. No additional reporting requirements are expected for the North Anna Power Station. If it is later determined that the North Anna Velan check valves are within the scope of Bulletin 89-02, we will notify the NRC at that time.

Should you have any questions concerning this submittal, please contact us.

Very truly yours, r-,, ,[;J\

\xC~.-~

W. L. Stewart Senior Vice President - Nuclear

    • cc: U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, N. W.

Suite 2900 Atlanta, Georgia 30323 Mr. W. E. Holland NRC Senior Resident Inspector Surry Power Station Mr. J. L. Caldwell NRG Senior Resident Inspector North Anna Power Station

.} -*

)

COUNTY OF HENRICO )

The foregoing document was acknowledged before me, in and for the County and Commonwealth aforesaid, today by W. L. Stewart who is Senior Vice President - Nuclear, of Virginia Electric and Power Company. He is duly authorized to execute and file the foregoing document in behalf of that Company, and the statements in the document are true to the best of his knowledge and belief.