ATTACHMENT 1 REVISED PROPOSED TECHNICAL SPECIFICATION CHANGE SURRY POWER STATION UNITS 1 AND 2 REACTOR TRIP BYPASS BREAKER TESTING 9001090194 891228 PDR ADOCK 05000280 P

PDC

TABLE 4.1-1 (Continued)

MINIMUM FREQUENCIES FOR CHECK. CALIBRATIONS. AND TEST OF INSTRUMENT CHANNELS Channel Description Check Calibrate Test Remarks

33.

Loss of Power

a.

4.16 KV Emergency Bus Under-N.A.

R M

voltage (Loss of Voltage)

b. 4.16 KV Emergency Bus Under-N.A.

R M

voltage (Degraded Voltage)

34.

Deleted

35.

Manual Reactor Trip N.A.

N.A.

R The test shall independently verify the operability of the undervoltage and shunt trip attachments for the manual reactor trip function. The test shall also verify the operability of the bypass breaker trip circuit.

36.

Reactor Trip Bypass Breaker N.A.

N.A.

M(1),

1)

Remote manual undervoltage trip prior R(2) to placing breaker in service.

2)

Automatic undervoltage trip.