Requests Addl Info Re GL 92-08, Thermo-Lag 330-1 Fire Barriers at North Anna & Surry Power Stations,Units 1 & 2
ML18153A478
Person / Time
Site: Surry, North Anna  
Issue date: 07/02/1996
From: Imbro E
NRC (Affiliation Not Assigned)
To: Ohanlon J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
References
GL-92-08, GL-92-8, TAC-M85576, TAC-M85577, TAC-M85611, TAC-M85612, NUDOCS 9607080084
Download: ML18153A478 (3)


Text

UNITED STATES e

e NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555--0001 July 2, 1996 Mr. J. P. O'Hanlon Senior Vice President - Nuclear Virginia Electric and Power Company 5000 Dominion Blvd.

Glen Allen, Virginia 23060

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION REGARDING GENERIC LETTER 92-08, "THERMO-LAG 330-1 FIRE BARRIERS" - NORTH ANNA AND SURRY POWER STATIONS, UNITS 1 AND 2 (TAC NOS. M85576, M85577, M85611 AND M85612)

Dear Mr. O'Hanlon:

You were required, pursuant to Section 182a of the Atomic Energy Act of 1954, as amended, and 10 CFR 50.54(f), to submit written reports, under oath or affirmation, that contained the information specified in the request for additional information (RAI) regarding Generic Letter 92-08, "Thermo-Lag 330-1 Fire Barriers." Question l.d. of the December 1994 RAI requested that licensees submit a supplemental report after test and analyses of Thermo-Lag materials have been performed.

The NRC staff has reviewed your responses of March 28, 1995, to the RAI of December 1994 and determined that they are incomplete in regard to the consistency of Thermo-Lag materials. Since you did not provide a complete response, you are still required pursuant to Section 182a of the Atomic Energy Act of 1954, as amended, and 10 CFR 50.54(f), to submit in writing, under oath or affirmation, a plant-specific response to Question l.d. of the December 1994 RAI stating that the Thermo-Lag materials used at your site to meet NRC requirements or licensing commitments are representative of the population of samples that were tested by the Nuclear Energy Institute.

You need not submit the results of your chemical tests or a detailed evaluation of those results.

However, you should retain these test results for future NRC audit or inspection.

We request that you provide your response within 30 days from receipt of this letter.

The information collection contained in this request is covered by the Office of Management and Budget clearance number 3150-0011, which expires July 31, 1997.

The public reporting burden for this collection of information is covered by the original estimate and previous increases, which totaled 540 person-hours for each addressee's response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the collection of information.

Senq (1,Q c**,. 1

.. *o *u 8

Mr. J. P. O'Hanlon comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing this burden, to the U.S.

Nuclear Regulatory Commission, Washington, DC 20555-0001, and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202 (3150-0011),

Office.of Management and Budget, Washington, DC 20503.

If you have any questions about this matter, please contact Bart C. Buckley at (301) 415-1452 or Gordon E. Edison at (301) 415-1448.

Docket Nos. 50-338, 50-339 and 50-280, 50-281 cc:

See next page DISTRIBUTION:

\\Doclcat--:fi+e~-'\\

PUBLIC PDII-1 RF S. Varga J. Zwolinski S. West FILENAME - G:\\NOANNA\\RPTl OFFICE LA:PDII-1 PM:PDII-1 Sincerely, (Original Signed By D. Trimble For)

Eugene V. lmbro, Director Project Directorate 11-1 Division of Reactor Projects - 1/11 Office of Nuclear Reactor Regulation E. lmbro A. Pal B. Buckley R. Jenkins E. Dunnington OGC M. Gamberoni ACRS P. Gi 11 A. Belisle, RII D. Oudinot

~

e

'~.....,.,.

Virginia Electric & Power Company cc:

William C. Porter, Jr.

County Administrator, Louisa County P.O. Box 160 Louisa, Virginia 23093 Michael W. Maupin, Esq.

Hunton and Williams Riverfront Plaza, East Tower 951 E. Byrd Street Richmond, Virginia 23219 Dr. W. T. Lough Virginia State Corporation Commission Division of Energy Regulation P.O. Box 1197 Richmond, Virginia 23209 Old Dominion Electric Cooperative 4201 Dominion Boulevard Glen Allen, Virginia 23060 M. L. Bowling, Manager Nuclear Licensing and Operations Support Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, Virginia 23060 Office of the Attorney General Commonwealth of Virginia 900 East Main Street Richmond, Virginia 23219 Senior Resident Inspector North Anna Power Station U.S. Nuclear Regulatory Commission 1024 Haley Drive Mineral, Virginia 23117 Senior Resident Inspector Surry Power St~tion U.S. Nuclear Regulatory Commission 5850 Hog Island Road Surry, Virginia 23883 e

Robert B. Strobe, M.D., M.P.H.

State Health Commissiorier

.Qffice of the Commissioner Virginia Department of Health P.O. Box 2448 Richmond, Virginia 23218 Regional Administrator, Region II U.S. Nuclear Regulatory Commission 101 Marietta Street, N.W. Suite 2900 Atlanta, Georgia 30323 W. R. Matthews, Manager North Anna Power Station P.O. Box 402 Mineral, Virginia 23117 J. P. O'Hanlon Senior Vice President - Nuclear Virginia Electric and Power Co.

Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, Virginia 23060 Mr. David Christian, Manager Surry Power Station Virginia Electric and Power Company 5570 Hog Island Road Surry, Virginia 23883 Chairman Board of Supervisors of Surry County Surry County Courthouse Surry, Virginia 23683 Mr. Al Belisle U.S. Nuclear Regulatory Commission 101 Marietta Street, N.W. Suite 2900 Atlanta, Georgia 30323-0199 I.