NPDES Noncompliance Notification:On 841107,4 H Composite Sample for Total Suspended Solids Exceeded Permit Limit. Caused by Increased Hydraulic Load at Peak Flow Times.Daily Wasting of Clarifier Sludge Undertaken
ML18142A128
Person / Time
Site: Surry  
Issue date: 11/14/1984
From: Taylor J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: Ronaldo Jenkins
VIRGINIA, COMMONWEALTH OF
References
NUDOCS 8411280356
Download: ML18142A128 (1)


Text

..

l"'"" ___,

e Vepco VIRGINIA ELECTRIC AND POWER COMPANY, RICHMOND, VIRGINIA 23261 November 14, 1984 CERTIFIED MAIL

.RETURN RECEIPT REQl!ESTED Mr. Ray R. Jenkins, Jr.

Piedmont Regional Office State Water Control Board 2201 W. Broad Street Richmond, Virginia 23230 IE FILE COP'(

Surry Power Station - NPDES Permit Exception

Dear Mr. Jenkins:

This is to confirm the NPDES permit exception at our Surry Power Station that was reported to you on Novenber 9, 1984.

On Novenber 7, 1984, a four hour composite sarrple was collected for total suspended solids (TSS) at outfall 008, the sewage treatrrent plant.

Subsequent analysis on Novenber 8, 1984 revealed that the maximwn TSS measured was 51.3 rrg/1.

This exceeded our permit limit of 45 rrg/1.

The apparent cause of this exception was an increased hydraulic load at peak flow times.

'Ihis is due to extra personnel being on site during the current refueling outage.

In addition, the plant is still undergoing recovery following the addition of foretgn substances during October.

Corrective action had included daily wasting of clarifier sludge and additions of a synthetic seed to increase microorganism activity.

Should you have any further questions regarding this matter, please let us know.

~;;~-

John A. Taylor, Ph.D.f Manager Water Quality cc:

Mr. James P. O'Reilly - Docket No. 50-280/50-281 Regional Administrator, Region II, USNRC

~- Harold R. Denton - Docket No. 50-280/50-281 Director, Office of Nuclear Reactor Regulation, USNRC Mr. Donald J. Burke - Docket No. 50-280/50-281 NRC Resident Inspector, Surry Power Station