QDR-5437-78-01 QUALIFICATION REVIEW PACKAGE CUTLER HAMMER 480V MOTOR CONTROL CENTERS SURRY UNIT 2

LffiNUS L__tj CORPORATION 81 D a._C)PPEFl FIOAD GA.ITHEFISBUFlG. MAFlYLAND 20878

, l 2~-BC:00 March 15, 1982 NOB.1-VOl-24 7 File 4.16 e

Mr. A. L. Parrish, III Manager, Multiple Power Projects Virginia Electric & Power Co.

P.O. Box 564 Richmond, VA 23204 Attention: J.E. Wroniewicz

Subject:

Surry Unit 2 Transmittal of Qualification Review Package

Dear Mr. Parrish:

Transmitted herewith is one (1) copy of the qualification docu-ment review package QDR-5437-78-0lfor cutler Hammer Motor C.ontrol Centers dated 3/12/82 for your review and acceptance.

The review of this package indicates that the equipment is lo-cated in mild environment hence we recommend to delete it from the master list of the harsh environment.

In this qualification package an analysis is performed for the radiation dose which reveals that the equipment is qualified to sustain the required radiation without any damage.

Upon your review and acceptance of this, a final signed-off copy of this complete package will be transmitted for your pe~manent files.

Enclo*sure cc:

N. K. Garg, NUS w/enc.

B. J. Reckman, NUS w/o enc.

J. L. Renehan, NUS w/o enc.

s. B. Gerges, NUS w/o enc.
c. J. Endlich, NUS w/enc.

Very truly yours, N,k*G~-

R. c. Wilson Project Manager 0 A Halliburton Company

e TABLE OF CONTENTS Section 1

2 3

4 Table 1

2 Qualification Document Review Checklist List of Reference Documents Qualification Report Review Summary Attachment #1 Correspondence DOR Guidelines Appendix C Conclusion Section, Reference Section and Response to 10 Day Letter TABLES (Section 1)

Special Environmental Requirements Special Requirements Worksheet QDR-5437-78-01 Page 1

5 8

10 2a 3a 4a 6

7 12 NUS CORPORATION

QDR-5437-78-01 QUALIFICATION REVIEW PACKAGE CUTLER HAMMER 480V MOTOR CONTROL CENTERS SURRY UNIT 2 SECTION #1 COMPLETE CHECKLIST,

FIGURES,

& WORKSHEETS NUS CORPORATION

e e

-~:;_..-**cat.a Porm Qt>Jt-3/01/80 Client IO:

Virainia t:ectric, ~:wer Co~~ar.y P:.ant:

s~rey Unit 2

Quali!icatio~ O.OC'.llte~t R~viev C~ecklist Sheet 1 QOI.-S437-78-01

~eviev for:

DOR Guidelines (xJ llC'llG-osaa D

1.

~&lie of t!\\e aeviever: --~C-*-'"'"...,Eol,lolY,d,1,1,llic!..Lb"------Da te:

3/9/82

2.

Equipment Covere~:

Cutler Hanuner 480V Motor Control Centers J.

Equipment Tag llo Ca).:

2 -Hl-2 (North & South), 2 -Jl-2.(East & West)

Does the report address all of the Class I£ equipment in this cate,gory li1ted in the master IE equipment

  • s.
  • 7.-

list?

II the report traeeab!e to the plant equipment?

Does the report specify an acceptance criteria for e,quipmeat perfo~e?

Was a base line test ~ce.to estab-lish the reference ba1i1?

Do tbe ux imwa and/or aec:ic!ent:

temperature and pressure usl'd in the test envelQpe tboae for the plant?

('l'U>l* 1)

I.

Are th*nul atlnt. par meters chosen anc! used ln the te*t*_*upportec! bf adequate loc~at*tion or re!aieftCeS?

5ote: Ag1D9 ttaes 1*** tban 100 *r*

DOt ac(;eptable.

  • 10. ta r~!ation *tf..nl a&c!resM47 (Tut or anatr*l*. If an1lJ9!1, 11 at!a,quat*

&>euMntat~on *rowi4.a?)

  • u. ~* the tallatlon fJoH,roflle, t.*.
  • lnte,grat..a lo** for ao~ op.rattan*

an4 K-Cic!*nt for the plant, fall with-ln the envel~ used ln 4ltl*lifie.ationa?

IIOTZ:

~ter!sk

  • l~dieatea ites.a appli~able t.o DOR 9l} 14el!z,e1.

YES NO NA Page llef.

X Item 1, Attachment I X

Item 1, Attachment 1 X

Item 1, Attachment 1

. X Item 1, Attachment 1 X

Item 1, Attachment 1 X

Item 1, Attachment 1 X

Item 2, Attachment 1 X

Item 2, Attachment 1

e e

Rev O Dated 3/12/82 S!':eet 2 Fora QOR-3/01/10 Client 1D:

Vir=~r.ia E:eetrie & Power CO~?a~y Plant:

Su:-ry Unit 2*

QOR. - S 4 3 7-78-01

  • 12a.

Does the total integrated dose inc1ude Beta radiation?

b. If not is there an analysis for this?
c. Is it required?
13.
14.
  • 16 *.
17.

1,.

20.
    • '12.

Was bwnidity aging consi~ered?

(Rot required for cables.)

Was vibration (ambient) aging eddressed?

Was ir,eehanical and/or electrical cycling addressed?

Do the DBE test parAmeters meet or ezee~ these given in the srec-lfieation? Make a copy ot the temperature envelope used in the test and superimpose it on the required en*iron.mental envelope.

Ass:.ire t~at deviations between the tvo are justified in the report.

t>oe* DI! temperature envelope used ln the test contain the double peak r.quired by IED-323-7.t?

Doe* the DB! qualification include

  • chemical *pray?

(Test or analysi1)

Doe* the -.,raf rate and auration used I.JI te1ta aHt or escHd those to be uec! for the plant? -

.r..:...

      • the 1pray testing aoae vbll* *"-
  • 1mder the e1trese* of preasure an4 tup.rature?

Are the aarltna ued 1n DBI teat :

gar... tera ef1ne47

Do tbe *rtl.u oontora to *tboM

't. ****

~~ired bf IZZZ-JZJ*lt7C an4 &nf app11ca~1* 4a~gbter 1ta.adar4 for thl*

e,qu i ;,ua t 1

  • Yes 5o to.

Pa;e Ref.

X Item 3, Attachment 1 X

Item 3, Attachment 1

" x. Item 3, Attachment 1 X

Item 1, Attachment 1 X

Item I, Attachment 1 X

Item 1, Attachment 1 X

Item I, A ttachmerit _ I X

Item I, Attachment I X

Item 1, Attachment 1 X

Item l, Attachment l

  • .. *r X

Item 1, Attachment l X

Item 1, Attachment 1

-~ ;

X Item I, Attachment I

Rev O Dated 3/12/82 Form Qoi-3;.*,1110 Client IO:

VirQ:nia t:ectric, ro-er Com?a..~y S?-,eet 3 QtR-S437-78-01 e

Pla.nt:

SilrryUnit 2

  • 23.

Did t.~e 1peei!ic1tion provi~e t.be re,quir~ op.rating tiJN for the equipment in the DI! or other 1p*eifi~~ harsh environment?

  • 24.

Does the test operating time under the harsh environment equal or exce*d that in the e,quipr.ient 1peei!ication? Assure that ade-(1\\Jate justification ii provided for c!eviation.

  • 25.

Does the specification call out the subme:;ence requirements if any?

  • 26.

Doest.he test pr09ram inelude submer-9ence tests? If not assume t.h1t the justification is provided.

I1 t~e aceuraey demonstrated duriDg testing e,qual to or better than that l?e"Cifi~?

  • 21.

A:e the l90unting and installation interfaces used in the te1t config-uration 1iailar to those used in tbe plant?

2t.

Wast.be test measuring equipment ('l'ME calibration ad~ressed in th* report?

30. Doe* 1t sp.cify that th* callbratloa of t.h* '?Ml 11 traceable to DS or other se-con4*rr 1tafk1arl*7 Jl. W'u tbe se1saic testiftt/anal.r*1* loae

. on ~~ comi<)n*nt oc equ1paent7

12. Old the _.!sale te1tl.nt/analr1L*

ad4reaa effe-cta of age?

  • :.:_--: ~JJ. Doe* the setnic ~**t itsporlff o4/ >

or criteria use-c! e.*elope the re-quire-d r**i"°r.se *p.ct.ra for th*

pl~t?

Tes I No X

j C

!O, Pai;e Ref.

Work Sheet #6-23 thru 6-26 X

Item I, Attachment 1 X

Item 1, Attachment I X

Item I, Attachment 1 X

Item I, Attachment I X

Item I, Attachment I X

Item I, Attachment I X

Item 1, *Attachment l X

Item 1, Attachment l X

Item 1, Attachment

  • X Item 1, Attachment l

e e

e Rev O Dated 3 / 12 / 8 2 For* QtlP-3/01/90 C! i ent Itl:

Vi :-cir:.:. a E: ectr ic, ?:,\\.le:- Cc::-,~any P:Ant:

S.;r:.-y Unit 2

  • 34.

Was t.~e 1a.me teat 1~eimen,u~ject to the entire test 1equence?

(In-eluding aging tests? -

MOR.?G OSB8)

  • JS.

Compare the ble>c:k dia;rmn for this report 191inst the *one you have pre-P*.r ed fr om your under stand in9 of vhat test and procedures are required as per l?£E-323-l974 and any applicable daughter standard for thi* e,quiyment.

Do you believe the report meets the inten~ of these standar~s?

  • 36.

Is the qualified life (OL) explicitly stated? Fill thi1 infor~ation in the aaster 1! equipment list.

  • 37.

t)O t~e aging tests/analysis results support the QL conclusion and is adeq~ate dcc~entation provid~ to support this concluaion?

  • Je.

lev!ev the test results on a relative comparison basis (i.e., performa.nce

  • paraJDeters of the base line tests vers~s those during the *arious tests)

Was ~ere any aajor di1c:epancy?

  • 39. lf.o, va1 it satiafactorily ezpl1ined in the report?
  • to. Are maintenance requk***nts w caa-ponent replaeeitent intervals specified
  • tl. !!ave you coapare4 M1ntenance ana re-fl*c~m*nt r.-quir~*nta to tho** ill th*
  • ta~dard ln1tr~ct1on/aa1ntenarice sa.nua!1 and 14entif1~ any speclal ite.* in !able 17 Yes 7

No Sheet,

QDR -S437 01 NA Fac;e Ref.

X Item I, Attachment 1 X

Item 1, Attachment 1 X

Item I, Attachment 1 X

Item 1, AttachmeQt 1 X

Item 1, Attachment 1 X

Item 1, Attachment 1 X

Item 1, Attachment 1 X

Item 1, Attachment 1

e e

For* QOJt-3/01/80 ei~ent I~: Vir;i~~a t:ectric, Pc~er Co~f&ny p ! ant:

S;.;r::-y Unit 2 Rev O Dated 3/12/82 s~.eet 5 QOR-5437-78-01 tilt all t~e re!erence de>c~:e~ts used for this :eview by their titles and identification no., with t~eir revision l*vel and date.

1)

DOR Guidelines: Bulletin 79-0lB, dated January 14, 1980.

2)

Environmental Zone Description Tables (Zone AB-13B dated August 24, 1981 for VEPCO Surry Power Stations 1 and 2.

3)

.5)

6)
7)

Ref. 129 J. F. Kircher and R. E. Bowan, "Effects of Radiation on Materials and Components, n Reinhold, 1 ~ 964.4.

Ref. 1.30 REIC report No. 21, "The Effect of Nuclear Radiation in Elastomeric and Plastic Components and Materials," Battelle Memorial Institute, 1964

  • Ref. 131

'I'. W. Parkinson and 0. Sipman, "The Use of Plastics and Elastomers in Nuclear Radiation, "Oak Ridge National Laboratory, published in Nuclear Engineering and Design, VoL 17, 1971

  • Ref. 132 EPRI.Research Project Report NP-1558, "A Review of Aging Theory and Technology," 1980.

'Ref. 133 Table C-1 *Thermal aJ}d Radiation Aging Degradation of Selected Materials," Appended to DOR Guidelines, Enclosure."- to IE Bulleting 79-0IB.

8)

Cutler Hammer letter, dated February 18, 197.7 to Stone & Webster Engineering Corporation *.

e PARAMETER Operating Time Temperature Pressure lative umidity Radiation Sli>mergence TAF<LE l J\\ev o

Dated 3/12/82 Sheet 6 QDR-5437-78-01 Surry lln it 2 Special Environn,ental Requ:iremerits MOTOR CONTROL CENTERS DOCUMENT REFERENCE SPE>CIFIED

, QUALIFIED SPECIFIED QUALIFIED COMMENTS

-- 120 days 120 days W. Ref. Letter Para. 4.3.3,..

No. NS-SS-4, IE Bulletin 79287 79-01 B dated 1-14-1980 l20°F 120°F Env. Zone As Above Description Table (AB-13B)

N.A.

N.A.

As Above N.A.

N.A.

As Above LOCA:

lxlOE.5 sand w Cale. Item 2 of 3.2xlOE4 12846.44-UR 40 Years:

(B)-043-0 this QDR l ~ 9fixl OF.4 Env. Zone N.A.

N.A.

_Description Tabre

~

AB-13B N.A~

= Not Applicable

Rev O Dated 3/12/82 ror~ Q~~-3/01/90 Client I:>: \\*;.rg::.ni! !:ect:-::.c, Pc.,,..e:- Corn?a.ny S!ieet 7 Q'DR -5437 01 Plant:

s~rry Unit 2 Table 2 Special Requirements

1. Mainter.anee Requirementa/Interval1 N.A.

N.A.

e

3. Stora;e Requireme~ts*

N.A.

.* ~--..

N.A.

-* *~-

.::. ;...,**_:.,._.** ~.:...*.*.*.,*.**

'i

~

~._.:. -~--

e e

~=- -*.*-

e Rev_o~ Dated 3/12/82 Fera QC~-3/01/90 S~,e,e,t 8 Clie~t IO:

Viroi~ia !:e,ctric, ?o~er Co~;ar.v

P:ant:

s~r=-i Unit 2

QO:R -S437 01 QO~~I7lC~T!ON RZ?ORT R.!'V~r,,i S~.>..RY

1.

lquipment Qualitieation laviewed:

Para 4.3.3, Encl 4 of IE Bulletin 7~-0IB, dated January 14, 1980 and Items 3 thru 7 on Sheet 5 2f this QPR, 2~

Stat~* of,Qualification Records:

X Records ident i tied f:Pvl=ltPu*t=i=a=M, obt1 ined ~l=l=/Tat~ i-a--l"),

--- and review (P,,,:l=l-,'Par-t-i:ai*' S..mlllU i zed on QDR-3/01-80 forms.

The following additional documents have ~een requested:

l.
3.
5.
2.

Fo!.lowin; areas/docwaents require. additional rev:ew:

l.
2.
3.

I

5.

Other comment* on *t*t~* of qualification records:

J.

Statua of Qualification x

Equipment ~aliflcation 11Ht1 the 911lc!a.nce of DOR guidelines.

For conunents ana-reconunendations see section 5.

! \\

__ Ja&!ltlonal _..1a1tlce *t1 attaei to j111tlfy quallflca-tlon *tatn. *eetalla of.Ultloaal "alllation n*~*

attaeb~.

Qualification testa con*lste~t wilb ~e re-ec.a::::~nd,1tion1


of ~-0588 for Cate-9ory 1.qui,ment 1hould be per-fonaed on the e,quipaent.

~=~~'T'ON

Porm QOR-3/01/80 Client IO:

Virqinia Electric, Power Company Plant:

Surry Unit 2 Rev 0 Dated 3/12/82 Sheet 9 QCR-5437~78-0l

!quipment *hould ~ reloc::at~d to an area where it will not~ exposed to a harsh environment.

Other recommendations:

S.

Additional Comments/Recom.'1\\e.ndations

1)

After reviewing the environmental conditions of the auxiliary building cable vault for LOCA, MSLB and/or HELB conditions it is concluded that the area is con-sid~red as MILD and no specific qualification evalua-tion is required for the subject MCCs.

For analysis see attachment #1, Question 10.

2)

For additional comments see Attachment #1.

Environmental qualification docWflent1 for the ~i7"11ent identi-fi&d herein have been reviewed and determined to be adequate and audit~ble.

Prepared bf*

c. J. Endlich ~

Date:

3/9/82

.Certified by:

N. K. Garg

J:1?¥-f Date:

3/]2/82 Date:

Date:

1)

Rev O Dated 3/12/82 Sheet 10 QDR-5437-78-01 Surry Unit 2 ATTACHMENT #1 TO QDR-5437-78-01 ADDITIONAL INFORMATION/CLASSIFICATIONS/JUSTIFICATIONS Questions 4 thru 9, 13 thru 22, and 24 thru 41 Since the subject equipment is located in an area (auxiliary building zone AB-13B) where temperature, pressure and humidity do not change during a LOCA, MSLB and/or HELB, and.chemical spray is not a required condition, NUS considers this environ-ment as mild.

During a LOCA the radiation dose increases to 3.lxlOE4, which is considered below the threshold value for concern (for discussion see questions 10 & 12).

There-fore, per paragraph 4.3.3 of Enclosure 4 to IE Bulletin 79-0lB dated January 14, 1980, no specific consideration need be given to the environmental qualification.evaluation of these Motor Control Centers.

2)

Questions 10 and 11

1)

The subject Cutler Hammer MCCs consist mainly of the following components, mounted inside a steel enclosure.

(Ref. correspondence from Cutler Hammer).

1.

Contractors - size 4

2.

Starter sizes 1 thru 4 (also reversing starters sizes 1 thru 3)

3.

power jack terminals

4.

circuit breakers, type "FA" to "FB", conversion kit

5.

control circuit fuses

6.

relays (Type M -

lOA, 600V & Type AA-lSA, 600V)

7.

control transformers

8.

unit mounted indicating lights

9.

selector switches & agastat timer

2)

These MCCs are located in the Auxiliary Building cable vault (zone no. AB-13B) where the total radiation dose (40 yrs= l.96x10E4 and LOCA = 3.lxl0E4) is 5.06xlOE4 rads.

For evaluation to NRC IE Bulletin 79-0lB a radiation "threshold" of 10E4 rads for integrated circuits, transistors, and,silicon control rectifiers and lOES rads for all other materials is used.

All equipment exposed to radiation doses less than the threshold is evaluated generically through a material evalua-tion rather than an individual *specific qualification evaluation.

This threshold value is based on an en-gineering review of material susceptibility to radia-tion damage as presented in existing literature (Ref.

129 through 133).

NUS CORPORATION

e ATTACHMENT #l(CONTINUED)

==

Conclusion:==

Rev O Dated 3/12/82 Sheet 11 QDR-5437-78-01 Surry Unit 2 The MCCs use plastics and elastomers in the form of gaskets, o-rings, seals, electrical insulation, supports and potting com-pounds.

The references show that such materials all have a minimum radiation damage threshold of lOES rads and in most cases the radiation dose 5.06xlOE4 to which the MCCs might be subjected is well below these values.

It is therefore concluded that Motor Control Centers located in the auxiliary building (cable vault) where radiation dose is less than lOES rads do not require specific qualification evaluations.

References:

129 J. F. Kircher and R. E. Bowan, "Effects of Radiation on Materials and Components," Reinhold, 11964.4.

130 REIC Report No. 21, "The Effect of Nuclear Radiation in Elastomeric and Plastic Components and Materials," Battelle Memorial Institute, 1964.

131 W.W. Parkinson and o. Sipman, "The Use of Plastics and Elastomers in Nuclear Radiation," Oak Ridge National Laboratory, published in Nuclear Engineering and Design, Vol. 17, 1971.

132 EPRI Research Project Report NP-1558, "A Review of Aging Theory and Technology," 1980.

133 Table C-1 "Thermal and Radiation Aging Degradation of Selected Materials," Appended to DOR Guidelines, Enclosure 4 to IE Bulletin 79-0lB. *

3)

Question 12 Beta radiation effects are considered negligible for this equipment, since it is located outside containment.

NUS CORPORATION

r**. *

(~:-..-*

Feoility: VEPCO, SURRY SYSTEH COMPONENT EVALUATION WORKSHEET - 90 DAT REVIEW Untt:

2 Dooket:

50-281 SYSTEM:

COMHON ELECTRICAL EQUIPHENT

!QUIPMElfT DESCRIPTION PLANT ID NO.

2-H1-2 South COf1PONEKT:

qeov Hotor Control Centere HAlfUF'ACTURER:

Cutler -

H11111111er MODEL NUMBER:

Unitrol FUNCTION:

Supply Power to Safety, Syste111s

  • ACCURACY:

Spec:

Demo: NII LOCATION: AB-13B Auxlliarv Building Cable Vault SERVICE:

NR FLOOD LEVEL ELEV:

KR ABOVE FLOOD LEVEL: Tes No Units

OPER, TIHE Environment SpecHic11tton 120 days Quellfioatlon Note 1 TEHP NR NR F

PRESS.

NR pale NR

REL, HUH. s CHEH.

SPRAY RAD,.

AGING

SUB, NR NR LOCA
  • 3,1 x 10Eq Note 1 QO Tr s 1.96 x 10Eq HR NR Documentation Reference out-standing Items

NS-SS-79287 CV\\V* 'co tJ~

-fffl--,

r>esc~if'n o N T1}(?.Li; - M-1!,e.

NR HR S&W Calo.

128Q6,5Q-RP-035-0 Qualif.

Method

.Mo~ba'iot@ T' lflYtrl I '-1,

.ll-l Lt C.

HR

~j5 /JOIA-f None None None None J

Note 1

~

None a

2 n

NR None Nft

  • Not required.

All n11111bere written in Documentation Reference Quelifloetlon oolumn are identified in Section 8, NOTES: 1)

Manufacturer he11 been glven information neoe1111ary to obtain qu11Ilflc11tlon data. Heterial composition of the HCCs should be available by February 15, 1981.

DELETED - See conclusion section.

2-H1-2 South Deleted Rev,q 6-23

-~... '

  • C/) :0 C/) t1 s::

t1 ::,-' p, Ii !:O Cl) rt Ii I Cl)

Cl)

~ tn rt P.,

~

C: Wf-' W

i

-.J N......_

I-'*

I I-'

rt -..j l'v CD N

I CD 0

l'v I-'

f'aclllty: VEPCO, SURRY Unit:

2 Docket:

50-281 SYSTEM:

COMHON ELECTRICAL EQUIPMEMT EQUI""ENT DESCRIPTION PLAIIT ID NO.

2-H1-2 Horth COMPONENT:

qeov "otor Control Center "AIIUF ACTUREII:

Cutler-H11111111er MODEL IM4BER:

Unltrol FUNCTION:

Supply Power to Safety Systt!III ACCURACY:

Spec:

Demo: N.R LOCATION: AB-138 Auxiliary Bulldlng Cable Vault SERVICE:

NR FLOOD LEVEL ELEV:

NR ABOVE FLOOD LEVEL: Yes No

.~,.

SYSTEM COMPONENT EVALUATION WORKSHEET - 9~Y REVIEW Environ111ent Documentation Reference out-

~

OPER.

TIME TEMP F

Spectrlc11t1on 120 days HR PRESS.

IIR pala REL.

NR HUH. I

CHEM, NR SPRAT Qu111lrto11Uon Note 1 NII HR RAD.

LOCA ~ 3,1 x 10E-Note qo Yr* 1.96 x 10EQ

~ y-.,s.

AGING

~

re 1:1 d'

l!I t n.o SUB.

HR NR

~eclflcatlon West.inf house Ref. L r, No.

NS-88-79287 I =°""". 21' "'-"-

-- J)~RIPTI Cl\\/

TAl?.lE All-13'1

-lllL_

S&W Clllc, 128116.511-RP-035-0 V_t-PCo Sflec_

-wit" shndlns Quallf.

Method Items ffot11 I* ~i

>iwt.-- tJhv..

114.(..

1'tf" HII None 14 C.

inr NR None 14 (.

NR None NR None

-"', IJJ N9ff-t ffo1:tr"'

Hoh 1 L'-( t.

Ri to* None R t S fn;j.2

( g ng NR NR Hone NR s Not required.

All nU111bers written in Documentation Reference Qualification column are ldentiflt!d in Section 8.

NOTES: 1)

M8n11fllet.11nv 111111 ~HR 11Svea lafgs:*a~ka 11oaes11e,iy ~ obt.altt-q11aUFleat.~n data.

Mal.eFhl ae111pe'1t1oa of the...MC.Q D£LETEO~~n~i~!~~~l:e:r1:~~~u11ry 15, 1981.

M(c j_,;

loc_ev~~ '-""'

'11L1)

ENU-kJv ~-S Se.e

~'DG? - S-4'3.;- 78-o/ ( f<_a.J /46/

2-H1-2 North I

\\....

Faolllty: VEPCO, SURRY Unit:

2 Docket:

50-281 SYSTEM:

COHHON ELECTRICAL EQUIPMENT EQUIPMENT DESCRIPTION PLAlfT ID NO, 2-J1-2 West CIJ1PON!NT:

Q80V Motor Control Centers NANUFACTURER:

Cutler-H11lllffler MODEL NUMBER:

Unitrol FUIICTION:

Supply Power to Safety Systffl ACCURACY:

Spec:

~mo: NR LOCATION: AB-13B Auxiliary Building Cable Vault SERVICE:

MR FLOOD LEVEL ELEV:

NR ABOVE FLOOD LEVEL: Yes No

  • e SYSTDtCONPONENT EVALUATION WORKSHEET - 90 DAY REVIEW Enviromaent Units OPER.

TIHE TEMP F

Speolfloatton 120 days NR PIIESS.

HR psh IIEL.

NR HUH. I CHEM.

1111 SPRAY Quallfloatton

  • Note 1 NR NR RAD.

LOCA

  • 3.1 x 10EII Note 110 Tr* 1.96 x 10EII AGING SUB.

~ 'J-.S lfncllinure II (Ju1, 1

II

~t

.o NR NR Do011111entetlon Reference

~peolfio11tlon Westinghouse Ref. Ltr. No.

NS-SS-79287 e.v.V. 2t>N6

-H-DB"cRIP no fY TAl!.L A~-15~

S&W Calo.

128Q6,511-RP-035-0 VEPlA?

Sft:c.

141:,

-ffR-14 (,

1"t I Lt(., I

~

133 I l/ <o NR Out-11t11ndln1 Net.hod Items

~jS"

!vO"hL '

'tiott-+-'.' -Note t None None None None

~,

Note 1 NI.._

None NR None NR a Not required.

All n1111ber11 written ln Documentation Reference Qualiftcatlon column ere ldentlfied ln Section 8.

NOTES: 1) fflln11rae,11J:er bu IIHA given ln~P*aUon neoeultt"y t.o e1btaln q*1111U!is:.allon data.

Mat..Phl u,mpe11il:lo11 or the Mef!!I she11lcl tM a111ll111lle b{ FellP11aJ:f 15r498-l,.

M c. c..

  • , 5 Loe "'-rr:::- D t N
  • MIL "h c;v1,.;.
Per,

/1_-- /-~ J.

DELETED - See conclusion sec ion.

__,.

  • c

.JI rrrt~*'

Sa.c 62D~- ~43?-7g-oJ (f<L1-14'.)

2-Jl-2 West Deleted Rev.Q 6-25 e

cn:o rn ~

~ t1 ::J' (D li~(D~

Ii I (DI

'-<: ~ rt- 0 C:::: Wf-'

l:l --.J""' t1 i-,. I p,

rt --.J rt-OJ (D

l\\.l I

0.

0,_,

w f-'

l\\.l 00 l\\.l

-~

/'.. *,, -

Faollity: VEPCO, SURRY SYSTEM COMPONENT EYAl,UATION WORKSHEET - 90 DAY REVIEW

.Unit:

2 Docket:

50-281 SYSTEM:

Envlron11ent Do0U11ent11t1on Reference out-COMMON ELECTRICAL standing

/**

EQUIPMENT

~

S2eo1r1oat1on Quall float.ion

~ea i floatlon

Quallf, Method It.ems I Y'{,

~~iJ~

EQUIPMENT DESCRIPTION

OPER, 120 daya Note 1 Weatinfhouse

~

TIME Ref. L r. No.

PLANT ID NO, NS-SS-79287 2-J1-2 East

/ E: l'\\V. 'Z..On e.

TEMP NA NR C

,!,!".c;rf*** -

NA None COMPONENT:

F I<-/ I:,

1180V Hot.or Control 1A.1,1~ AfJ-1.3(5 Centers I:

MANUFACTURER:

I 4{,

Cutler-Hammer

PRESS, NR NR

--tfft, JMt NR None I

psia I:

MODEL NUHBER:

Unitrol I '-f ~

REL, NR JIit NR None HUH,
  • FUNCTION:

Supply Power to Safety I 'I I, Syst.@111

CHEM, NR

-ifft-JIit NR None SPRAY

~

ACCURACY:

Spec:

14~ Iii Demo: NR

RAD, LOCA
  • 3, 1 JI 10EII Note 1 S&W Calo, tllmr"T" ~, -lh,w-t j\\)o-k I 40 Yr e 1,96 JI 10E4 12846.54-RP-LOC~TION: AB-138 035-0 Auxiliary Building Cable Vault

~y~

~Nt SERVICE:

AGING E~II ft> '/-.1 v 5: pco > /Jc..

}ll<.. 'fib None NR G i s

R p~

s tl

.o S

.2

(

i g)

FLOOD LEVEL ELEV:

NR SUB.

NR NR NR NR NR None ABOVE fLOOD LEVEL: Yes No NR

  • Not required.

All numbers written in Do0ument11tion Reference Qualification column are identified ln Section 8.

NOTES: 1) Ha11uhot11rec bu ba*R gl tell 111r0t meblon neo.*111aFy ~9 et.bttl1t-~ttflontlo11 dat11.

Heter lnl co111pm1lblon of bhe MGC:. ~-

.sho**l d he svellabl* b,: Eehr1111ry l~t-93-l,-

MCC

/S loco..~ L-v\\

MILD ~\\.I'J)'t) ~{.. ~

.1.

DELETED - See conclu~ion sect.ton.

S°tUZ.. (12 1)~ -

5'"437-7<;:

0 I ( N. II.{'/

2-Jl-2 EMt Deleted Rev,4 6-26 en o en !:d

~ o::rro Ii ::u (D <:

Ii I (DI

~ ~rt 0 C: WI-'

i -..Jt.n 0 1--'*

I PJ rt -..J rt CX)

(D l'v I

0.,

0 I-'

w I-'

Iv CX)

Iv

.... ~-~.*~. -...:..,.

~ ~--. *-*

SECTION #2 SPECIFICATIONS, PURCHASE ORDERS, VENDOR PROPOSAL NUS COFIPORATION

Page 2a CORRESPONDENCE

(

(

_2-NUS a--~TON

~

4 ~ESEA~,.., 1=1..ACE

.e i:c:x:xviL... E. MAC::VL..ANO 20850 x:r. S4S - ?Oio Mr. John Cooke Eaton Corp. (Cutler-Hammer)

P.O. Box 310 Glen Burnie, MD 21061

Dear Mr.. Cooke :

May 8, 1981 5437-4.7~

Please refer to our telephone conversation on May 7, 1981 re-garding the Motor Control Centers Cutler-Hammer supplied to VEPCO for Surry Power Stations, Unit 1 and 2 in 1969 or 1970.

This confirms that you are willing and able to furnish us with the following information which we need for the evaluation of those MCC's:

1. Material compositions of the following components used in the MCC's -
1) Circuit Breakers
2) Starters with Contactors and Control Transformers
3) Terminal Blocks
4) Wires and Connectors
5) Relays and Meters, and
6) Switches
2.

Type numbers, model numbers and catalog numbers of the above components *

.,fi,,.*.

  • 3.. Names of manufacturers of the above various components included in the follqwing MCCs.

e*

The designations of the MCC's are:

Unit 11:

Uni{~t2:

l-B1-2 South 1-B1 -2 North l-J1-2 West 1-J1~2-: East 2-81 -~ * ~~ih~* _.,._,

2-111-2 North-:.-.~*-,*

2-Ji-2 West 2-J1-2 East Please provide the approximate time and your quotation for the above services.

cc: "'f' J.a8-W§,

N. Garg Very t~ly yours,

'~-;;, t *:.., C.

/ 1:.c.---.

A. It. Ballav

APR !l 1981 TELECON ~TE No. ____ _

Data: ~/ It 18 I II,9-,-t.

Fill: __

S'fa.__:...:;;:3_7L..:.:-_4_. 7=------

H.r.

f.3

  • V~r of: _--'-~....i:.&..I :;;c:_,tfk,~L......Z~=--'-~~=-=~~c:_Y_

Aftd: ___

11~*--"-K.._*_~'--._..::._-=.,:~---'NUC)

DISCUSSION:

i

...i ACTION ITEMS:

. _z.

I

-~j

"'* I L ',\\' ~ U K

E C: *

.~ I ( -ONSIN 5 3 2 0 I FOR:

ATTENTION:

JOB NA~.~E:

PURCHASER:

CONTRACTOR:

Cl'TLER !-!..:i.>:'.*'.!::P.

, l\\C.

5 KOL,~~?. E'.,:.Cl-: 1 *,::: c.::~*;*c:R. Si. r. I.."

11-:-

63,0 n:::,T.R. DRl\\"::

NORFOLK, \\..A.

2 J.>02 HR *. Sr:"l>TT BOYD

'.'lRG I~: l,\\ ELC::C-:-R IC PO~ER CuMP:\\:;y STO~E t w::nsT:.R ::::-:c1~:EERI~lG C*>RPOR.ATlO~:

OR.I.WINO!,uRNIBHEO a, OUR ATLANTA PLA~T

  • AT THE REQUEST OF OUR

(

1 'iLC:!=: f!,\\'*'.:Olt.:R r-3 50 L'!:::* TER DR.

~~ORFO:..Y, \\'A.

s;: 329 Address your reply to our

  • :,:oRrOLK Sales Office at the above address.

Attention Mr.

Set' :T B1.>1D ATTACHED ARE_~..,_COPIES OF DRAWINGS:

e SiE A ~:;\\CH'!::0 PAGES FOR LI ST l ::G OF DP.,!. 1., r::cs:

. *~:.?;_'t'_ *:. :./ '.'?;:r'. ;.. \\

  • L~ ';, -~-~' ;_t,:*... ~~ ~

e

  • eoc.1KLETS

-*.,, ~.-:.

~f(~~~ ;.

"f*.

... '.\\*'

D.WORD

&OOVC.... ~~':IA~!II".::>** c:~.r:.~*.!A7i0N C.u>r'ltOVAL t DIIAWINGSAl':E a,-jlteL.,.... 1~;,P.y Cco:nr.;.C'~f.:, c;,:... ::'I WOIIK IS

~ Frt.[AS!"O F01' 0.. ;;.!:, f'F:I" P'll=>OUC.IOH t

~

t i ',..

t i i.

i -

I L

I I

(

~: i-I.

3TO::E.R:

VE'?CO Ct'ST. NO. S~l 329 1

---aa-

~'.l~O~~~:_S_U_R_R_Y_'~P~C~~-rR._S_T~A_T~l_O~~*:-=:-:c----:-::---------:,----------------c_-~_* ~~~~F371393 D%0U:.l> 3C05-30~ 0 (lD:TTIFlfS ALL un1s IN CO!\\TROL CE:,"Ti::R 1,,;lTH c..TS 480 E'LlED £lvicE THIS

~:o.

DER X.

X X

X X

JC X

X CORRESPtJ"'Jl~'G S'I'ARTi::R srz:::. DlAGRA:-!, ~EAT.C:R COILS, ::TC.)

120

  • PHASES 3 CYCL,ES
  • 60 co~~ROL VOLT_s ____ _

KSEE !,.P. 01: DEVICE FOR CAT. t:o.

llEr:EWAL OF COMPLETE DE\\'ICES, OBTAIN

~RTS LIST FROM LOCAL DlSTRlBL!TOR OR E'UB. NO *.

JOBBER.)

~ont3ctor: size~

I,;.I.Ur*.&.

~tarter: Size *l AlOC-1 *

  • 2 A1Cm.. t
  • Aln~.t
  • 4 Reversing S!ze *l ASOC.,1 *

~t.!rter:

2 A50D*l

  • COHPONEKI OR DEVICE PART NUMBE,!l

, inn*.**"*

re.: er to p'.l o.

.1473S for beater

.coils.

\\50C~OA.A50Ci\\'OA. *

~SCD~;OA. A50D:lVOA


,f-----------------+--------------------.,..

Power Jack vith terminals 128;.1291-5 z

X A 70-6673 A.'! FB/FA

  • ronversicn kit

,..nritl"nl rkt fu1;ina A640lil2-706 11,., JIV ITvn,:, *M

  • lOA
  • 600Vl

(Tv~e *.V.

  • 12076

~ontrol t,... nsfo-rmer*

A70-4206 t

'Unit 'mOUnted indic8tinsz: li11.bts,. 1n.t.cn Setl.*swi tches. etc.

2422AD

  • 1~

. '(.......

l f

t t I,-

t

' f,

i !j.

i. i t

.. ::~,t-~:.:

-~:.-

~.. '~.-

-....... ::.:*.*:.;-.. -.~

  • ....... -r-._,.,:.*.,_..
  • J

..-...:~;,,:"*;;:;*Sc*:;_* -J-.-.:._ __ __;.~------ll-~-4-;.._;..__;__--r. _______________ *'

---f---...-4....:._ ___________

.;_* --J------+-----=----------

~.,____. -=-*~---**---+-----l-----*

I*

---+---I----------4-----+'~ ~-------

_______. ___ _._ ________________._L __

~-~~~

I.

l

I i

L.. l.:..... :. -..

-
  • r * ' ' ; *, ~...=. *
  • J-~---l
  • C)

~.-..J...:.:J M I L W A U K E E,

V DATE:

FOR:

ATTENTJON:

JOB NAME:

. PURCHASER:

  • CONTRACTOR:

W. I S C O N S I N 5 2 Z O I

  • FEBR~..:..RY 18, l 9i7 Cl'TLF.R H.\\:!XER INC.

5 KOGER EXECuTivt CENTE~ S~ITE lli 6350.CE~ITER DRIVE NORFOLK, VA.

23502 MR. SCOTT BOYD -

VIRGI~aA ELECTRIC POWER Cm!PAXY STONE & WEBSTER E~GINEERING CORPORATION STD\\E & WEBSTER E~lGINEERING CORPOR.-UIO!,

(

ORA',*,ll',iuS FURN13HEO BT OUR ATLANTA PLANT AT Tl-IE REQUEST 01'" OUP CFTL~R H.\\:-I:*ER 6350 CENTER DRI~~

NORFOLK, I/A.

S,. 32 9..:..1_

(PUJIICHASE1'S CJltOEfll NO. I Address your reply to our

. NORFOLK Attention Mr.

SCOTT BOYD Sales Office at the above address.

ATTACHED ARE_2"'-_COPIES OF DRAVVINGS:

e SEE ATTACHED. PAGES FOR LISTI~ OF DRA,IH;GS:

~*,'.t}'f Jwt"

...~ ~*-::-,,:

. ; __. ~

~

  • /~f'
    • .-.... ~

. cJ

  • ri.

' ~itted By.-,.-... -... -.:-~ _-;:*:: __

D_._W_O_R_D ____ _

. \\

~ ~- ADDITIONAL *DISTRIBUTtON OI DRAWINGS: : '.::J;\\;~<.

-<~)-\\~{,

, ~,*: \\¥1t-~:\\?fr -:*_;}~y1.~{l~~~ ** * -*,:j}~ *". -

  • *:,.r~~-,:t\\**, *

-&>OKLETS.

.. *._),..

. a~~ '::.... !:..11.&1..11 P"';it

~ :s,.;:'.s*~a*;CN O AP?;::CVAI,.

  • .*.er"*: *s iii: "r _*:-':t.:,c,11 ':,...=!..:".-;,~*4 ""o:>~~1c**

i f

.. t

  • j i -.,

tl;57C;S~:

VEPCO CUST.NO. SN 329'"

?LlCA7l0~*:

VIRGINIA ELECTRIC PO'\\:ER C0:1P,\\N'S C-H NO.

6AFJ70910 Si.1.:'.ARY Dil.\\*"l~G:.OS~.01£.n 2950-2967 uo::~.ilFI Es ALL t:~ES lN cu:.-: ROL CE~iT:::?. WITH COR..~SPOh"DlNC STA RTE:\\ S1Z£, Dl.AGM!-!, !-!F..; TER COlLS, ETC.)

VCLTS liEO *.

PHASES 3

CYCLE~

60 CONTROL VOLTC::' 120 SUPPUl!>

DEVICE

~S.EE N.P. ON DEVICE.nn. CAT. t-0.

RE?,E~AL COMPO:iSNT

JN TRIS t.'O.

OF CO!-PLETE DEVICES." OBTAIN PARTS LIST OR DEVICE ORDH

{'ROH LOCAL DlSTRlSUTOR OR PUB. NO.

PAR't. Nu'MBER JOBBER.)

X STARTE~

SI2t:" 1.

1A 1nr.1.

A l('\\r'NnA X

  • SIZE 2 A lOQ.il. I A lC'fY~JnA..

X SIZE 3 A lOE*l I A lQE!i_QA X

Sl7i:' l.i.

!A 1n1:*.. 1.

AlOF~OA X

llEVERSlNG SIZE l.

ASOC.. l.

A50CNOA,A50CNVOA

\\

I PO'JER JACK WITH TERM 18-12Ql-"i I

A CIRCUIT BRE.A~RS A 70-6673 I l

11FA11TO "FB" CKT BKR EM FB/FA'.

CONVERSION JClT t

X Ct.Jh'TROL CKT FUSING Af>.l.10412-706;.

X R.EIAY (TV"?E M-ln~.600Vl

.. D26H.-1.

.I X

CONTROL TRAN fil'.Q.B,._"!E R A 7o-4,n6..,

I T

UNIT HOUNTED INDICATING LIGHTS 10459 SET'L. *SWITCHES. ETC.

I I

.i,

~

. :=.

~~

~.

  • -\\

~

L_

SECTION #3 QUALIFICATION REPORTS NUS CORPORATION

e DOR GUIDELINES "APPENDIX C" (REF. REPORT 1133)

Page 3a

1

  • 0 IntTQducti on.
2. a Discussion IE BULLETIN 79-0lB 3.0 Id~ntif.ie:!tion of eiass rt :,uiomeMt 4.0 Se!"'Vic! Condft'f ons 4.1 Service Conditions Inside Cont.:i~en~ for ! L~ss o~

~iant Acc,aent (LOt:;.)

1. Tem=e~!tur! and ~r!ssure St!!ffl Conditions
2.

itadhtion 4.Z Ser-,ic! Condit~ons -:-el"! ~i.~ Main St!~ !.~r.e 3~ak O~SlS}

.:.ns 'i:e C:r:u i ~e.ti:

l.

O,er;i ca 1 Sera vs 4,.3.1 Artu Subject tc I Seve!'"! t,,vi-.r:=ent u a ~esui-:*

of 1 "ian E~e?"":v ~ine S~aK (H:~SJ 4.3.Z Ar-!!S i(ne~ ~~ids tr! qeci~e-~1ate~ ~~ !~side

-~nta fo::-.e~t ~.:.e:a= 1 ;sn !.one*, tr:' :.:.!!'":!.,,CV ecre Cooi ina Followina I LOcX

2. ~diation
  • C'

~...

' 4.3.3 AM-!s Ho~,, v P'.at*.t1ine~ at itoom C:nc'itfons 5.0 Oua1ifi12tion ~ethods 5.1 Se1ection o~ Oua1ification Method S.Z Qualification bv Type Testina

1. Sfmulat!'d Servie! Conditions and iest Duration Z.

Test Soedmen

3. iest ~uenca
4. iest Soedmen Acina S.

Fun~iona1 iestina and F!i1ure Crit!~~!

6.

Ins~l1 ation Inte~aees 5.3 0-.:alification ova ~oinatior. of Methccs (ies~. ~va1u~ticn.

Ana 1 vs 'is )

5.0 Mar-ein 7.0 :.Ci!ia S.O Oe~w-:-..:e~taticn

~ppencix A - iypic:11 £~ui;:inent/r~nc~ions Ne!ded ~:~ ~iti;!ticn of I !.OCA or-HSU Accident A~;e.~dix 3

  • Guf~elines far Evaiuat~ng Radiation Ser--:iea C.:ncitions Inside Ccnuinment for I LOC.,. and,".Si..: ;.c:ident

~pendix C

  • The~.al a.nd ~diatian Aging*Oegn~a;icn o'f S!ieeted Hitarl1ls

itb1e C-1 {s 1-pa~ial 1is~ cf ~~~ria1s.which may be four.: in a nuciaar PQ'liller plant 1lon9 witti 1n indication of ;he mat!riai suse!!?~ibi1ity _to radiation a.nd t.her:nal 19in9.

Sus~tibil it"J to signif'f eat!t tha~..a i 19in9 in a t:'°C enviMnment and ncr:-.a.1 a'QQs;,here fer 10 er 40 yea.~ is indicated cy a.n (') 1n t.,e !P!'r--=-

priata c=l1.::1n.

Signifieznt aging d~radaticn is defined as ~,at amount

=1 ae,;r1<!.ation 'Ul!t would ~1ace in substan:iai douot the aoiiity of t-~ica1 eq~ii:ca-~t using tr.ese ~attriais to func:ior. in a hes~i1e

.s~sc~:~bili-:y :.o ~adia:icn ~-z;e is incicate~ :y ~he :ose 1evel and

~,e c:ser--1ed ~f1~~ i~"1tified fo t.~i e:,1i.J:ri heacet :.!.SIS.

n:e meaning of :::t t~ i.:s~ ~ c.-.ar-ac!~~zt ~,e dose effK-: is as 1'o1~ows:

senous degndltfcn occurs.

The f:lfor-.:ation in this appendix fS b!sed On I 1 f ten tu:, SUI"':., af SCl.:~IS

  • fne1u:ing t.',e Katienal ie,e.:,nie11 !nfo~tion Sel"'ViC! (N'i~S). t~e Na~io~ai

(

  • z
  • C:!':Sfdered a11 ira.ius1ve neit."ier is it to be usei: !S ! ~as~s for s;:edf'.1ing ~~rials tc be llSed fer s~eeific !;)p1 ie~tic:-:s within a nuc~e.:- pl ant. The list is *solely intended for use !:y the MRC staff in mking jud;E'.!ents as to the possibi1ity of! pai-tic:.i1ar ir.at.tria1 in I pa~ioilar,;,;iiat1on being susceptibie tc si;ni'l'ieant degradation due ~ ~dia~on or t.ie!""::'1!1 iging.

':9ne :!!ta ~ase for therma1 &nd n.diation.aging in engine~ring :iaterials is ~id1y er;a...,cing 1t t."'lis time.

~ idditiona1 ir:f::-:-.a";icn bee~

!vai1abie i~ie C.1 wi11 be tJ;)cat!d ae:cMing1y.

~-

I I l

i

/'

1*,' 1 I '-', ~, C ',,,I/

. !.. ' _..,(.~ -//.

I l'I~..

IE SUL' ~*L*,.:o,Q.o,a - ~'l';r'f'l~IJr~***

~

~"' li\\ 1, t.,, * ~

... -~ -~~

QUli.L!FlC.!.TlON OF CLASS lE E(i;JIP~£h-~

Referenced !, Bulletin was r-,!iied to you ~anuary i:, 19SO.

The at:ac:is:

TABLE C*l (4 pages) is to be 1r.c1ud:d ~dth Appen::x C! Enc1osur-e,.

e::.~I~

~~r'; __

2.Z: ____...;..;c;*;...,:.t./. __

G. L. ~~~~e~, O..~ef,

?.e!cto~ a,er::iv~s inc

~~::ear Su:;~rt Br~nc~

-~

e

  • MftllUALI Lift fllot'.!I Of' HUUll'IIKtn' CWlTIIIH 11111,,1 NATl!NIAI, ""' IIK t*uutn,,

N"l'lffl'l'lftL MtllATICIN l'Oft

~'IW"l'I U I I.ITV GltlHU'ICMff AfM MllNO IINUWN MNIII Mfl!ll I Al, M

lft Ylt!l

41) 'IRI CWN INIIO

,~tavr*t4'11 ctroultil i1c, 103 1'hl'Hl10l&I X

X X

N*,_,..

'"'-~r*1.S Clro*&ta CIC)

&04 X

C*l'I.IS ft'a1111htM'e 104 X

X X

DluJ.t1 10" X

X lllll:Gfl-0.ftlr&&l.S 104 X

X X

X X

,..euu.,,,

lnt*~r*ttd ClNhlL,1 cicn I* 104 Alhll09 X

I Yulcanl...S Plbet 101 I

I X

X *

,111,......,

la 10' IC I

  • 1l

~

ll'uly*U*r 109 X

  • X

'I

  • X X

Nyh,n 1'1 X * * * *

  • I I

~o X

X

  • I y

,u l,,uo1 rboMt.

11,'

X I

  • X Pulyl*lJe 10' I

X X

X X

X Chlu101uUeMtlMI hi,-

e,...lon 10' X

X

  • tl,y 1.,....

llun11*N IMN/Hl*

,o' X

JC IC ru..

111l;&,er J1ot'")Uted Cll'01llh CIC) 10' I(

I X

'M'L Dl*llyl Pht~l*t*

106 11 l l h1otw flulANr 1.:1.101

~

IC

I'

~

(h

~

.. \\,"*.:'

  • 1;;.,1-,,,. ';*

_, j11i~~.'~-::.,, '

.. M<Mrar* un CCOlfflNUID) nrmi cw ~111*Ml<tfT (WITHIN WlltCII MTv.klAI. MY ntt P'OlftlOJ tOl'fflffl"I.

MOIATION l"OR llfiJl.1'1'TI U 11,ffl lllflNlP'lf'"Nrl' --*-**

'""'° M:llll'J lfl,....

IW'tfl

,.,.Ml.

NI I* YIUJ 4fJ 'IIUI '"""'"'

2.10' tlltll........

X X

~ '

'~"l*1t1l1M*

  • ftftlel*

J11IO~

"llow*blo X

I X

I X

X X

'"' h 1ft 4,41110*. ""'**hold X

X

-r-,,...,,

,.,o'

" 1.0..

  • X uf 1Uon9&"1 tlon l'hMlulle P.*OH

,.1*0*

'l'hre*hold X

  • I I

I I

X

"" 11 llaotte 11&10'

~\\lowabl*

X X

, *.,...,111~ IAIIUt 101 re*hold ft,1 "'II,,lw Ch1,'\\llt* ere, 10' I

1:1*1.

1. Si1107 I

X I

  • II U41o.... I yt,IIH en...

2,41110' I

1.,.. 1e.. 11n*, Cir.ch cro-1 X

n Mo'\\ r.,lp*tor CJIAH 2 *** 10'-*

,.,.. 1 "'"**** Ornclo Ul"0-1 I

IC f*11 I yol hy I ont

  • .,.. o, llOIHlbl*

X X

X X

llo't1*1CIIIO, 4,S,cl07 l'hn*hold X I

I JC I

X I

I X

X I

X

  • tl'N
  • thylene-511101 X

I

  • rui'Jl811111

!\\IIJIJOI'

,~,1y,1...,.......

u,*

I X

X c,,.....,.,,... "

'1.d01 llowabl*

....,~, hyl~

"'" l*,r* *..,,.,.

111101 I

X

  • l

""'1:11 I Al, Afll//,J All


11----

~.,,......*

... 111\\M'I

  • Vl...... W

........,...... e....

.,......... llh*

.,~.......,, ten

  • o....,.

1',ttwt1tl tvra

  • UlaH*

, *.,,,,,111\\...... "'~

'":tV\\,.11.,..... u L""'

1.... 11,,11.0*, tit,tJet xn,e f":tV\\ T1Nt~OlUhfJ

.....,,.. l.11, ~....... llJQIII

"'*.,,..,....,.. 1:....,

1.*l tt,11.1',., C:*,1;.., XPI tll't\\11 ThoJ1'IIW'l11ettl11*1 1.,... t 11o11 ci11, Ch **lo ICl'C 111.,,~ Thu ""'-"'"t l lt"f 1,.,111l1t,1\\011, C:1,1Jo ICIC

'">'" Tf11H11tO*ult lll'J

'*'"""*tu~, 1110,h, XJCP

  • nil/\\ T11*11111ueuLtlnoJ 1,.,111111.1lu11, Credit XO

"'~ 1 IH*..... t*ll. I ncJ

,..,,..11.,n.,*,i, 1Jr111ln Cl

,,,:,.., '1iwrlllOllettl 1t1f 1..,... 11,o11.u11, nra'-'o C flO'l'M'l'IAI, IIOUt'll"Atff' AGltlf1 1n YM -1n YRS --

. ~.f '

-~~J*

  • , *,:~~:*;: :*.

.. ~.-..!:

Mfllft'l'ION fflltle.'r.M' 111 I I.ITV

,."".. ~

IIMID s.io1 ll~bl*

    • io1 ao' reehold IDI

,.,o*

Uovabl*

,.io*

.,.10*

u.,.io' .

O,S*to' 1.s.io' a.s.io9 11.1,110'

...,a10'.

"*'"'° 1:1.10*

I X

I nw.n..... P.\\llltrllP.NT (IIITllfN WIIYCII """""'"L MY IIP! P'lllllNf*J IC X

I X

I I

X X

I JI X

I I

  • x I

X

  • I X

JI X

X I

X X

X X

IC

  • 1 *.,

I I I j

J.

f l

i,.

j I I J

I H.\\Ttelll AL N~ T11,u*.*1>**tt1nof L,aalll*L"** Cu,J* L Nl::HA Tin, ni1oa11 t t l ftlJ i...airwt*** CcaJ* L2 Ht:HA Tl111 "'->ll*U 111(1 t..*&11*t11*, Cra.t.l,... 2 NU4A Th,uao1111c.Un41 r...ain*t*** Cr*d* rll-J II t:HA Tiu, n1oa II t t ! 119

..... ln*tu11, Cr*J* FM*4 Nt::HA ThdPIOa*ttiv w..ai11&t,u,, Cr*d* ra-10, NLHJ\\ Tltu 1.'r.lOol*t.l ll\\11 L&a.l.11.at*** Gr*J11 A Nl::HII Tl.. u*iu11ut t Lr,9 LJ~ln*t~*, ~r*d1> AA ULM.'\\ Thu1110llt1llli19 wailn.atua, Ca*.iJe C*J UCHA i*1tor1'U11wtl11"f

~r*irwL111, Gr*Ju O*U 11~:HI\\ *r11u1"111(,111u 1,..,

L.lra111.no11, cr.,t., Fll-5 IW11hLOO

  • I' n:.

Al.SO I l'Oft,ffJAL t*on IICNIFIC['N'\\'

I\\GlHr.

ICIIUWtl i----.----4 AS 10 Yllr.

40 YRS AAOlATIOH Utt:;O'J'1' IIU LITV UIUUI n1*1<111 c,r ~lll'tr.tff CWl'l111N Wllll.11 MTl:IIIM. ~, "" nu***

X I

X IC X

X.

X l------------.1..---..J..---"----'----"----_.11,._._1 _

_.--r.* ------*'--'--'--il...-,..t.--J..-_.Ji._ __..... _"-_ _.. __..__

e SECTION #4 CONCLUSION* SECTION, REFERENCE SECTION &

RESPONSE TO 10 DAY LETTER NUS CORPORATION

7.1.4 7.1.5 7.

1.6 CONCLUSION

SECTION 7 Source B - Cable obtained from North Anna Units 1 & 2 stock The cable obtained from the North Anna Units 1 & 2 supply was originally qualified as part of the North Anna Unit 1 IE Bulletin 79-01B 90 Day Review and North Anna Unit 2 NUREG-0588 Review.

This data has been included as part of our review.

Source C - Cable originally purchased for use on North Anna 3 & 4 Cerro Wire.& Cable Co.

(Rockbestos)

All deficiencies identified in VEPCO's November, 1980 submittal, and the NRC's SER Appendix B have been resolved.

Details are provided in the updated Component Evaluation Worksheets.

Complete qualification documentation has been, or will be assembled and available in the central file.

Amphenol (Electrical Containment Penetrations)

All deficiencies identified in VEPCO's November, 1980 submittal, and the ~RC's SER Appendix B have been resolved.

Details are provided in the updated Component Evaluation Worksheets.

Complete qualification documentation has been, or will be assembled and available in the central file~

Cutler-Hammer (480V Motor Control Center)

SEE SECTION 7.3.12 Westinghouse Electric Corporation

a.

H2 Recombiner Units Plant ID No.

2-GW-HC-2A 2-GW-HC-2B Worksheet Page No.

6-105 6-106

. I Rev. 4; 8/24/81 S2 7

6

e e

7,3,11 7,3.12 7.3.13 7.3.15 Kaiser Aluminum and Chemical Sales Inc.

(Spec.

Nos.

NUS 225.

NUS 365A, and NUS 217 Based on field test verification (special test 104) obtained subsequent to the February 1980 submittal, it was established that these cables have not been used in safety related applications in Surry Unit No.

1.

TI"lerefore, this has been deleted from the Master List.

Cutler-Hammer (480V Motor Control Center)

This equipment is not located in harsh environment and therefore the component evaluation worksheet has been deleted.

H2 Recombiner Power Supply This equipment is not located in a harsh environment and therefore the component evaluation sheet has been deleted.

Solenoid Operated Valves (Chemical and Volume Control)

SOV-1311 This valve will not be required during a LOCA because pressure and boration control are not necessary.

During an Auxiliary Building HELB, this valve will not be affected, since it is inside containment.

Solenoid Qperated Valves (Safety Injection)

SOV-SI-202A1 S0V-SI-202A2 sov-sI.:..202B1 SOV-SI-202B2 These valves serve to cross-connect the LHSI suction line from the Refueling Water Storage Tank (RWSI) in Unit 1, to supply the LHSI pump suctions for Unit 2.

If an HELB occurs in the MSVH for Unit 2

(Location of LHSI line from the RWST of (Unit 2), these valves can be operated to put the RWST of Unit 1 on service.

Due to the location of thse valves, thse valves will not see the effects of an Rev. 4; 8/24/81 S2 7

24

I

  • REFERENCE SECTION 8 NUS-VEPCO QDR Package 5437-MOV-2-01.

125.

Franklin Institue Research Laboratories Final Report F-C33D6-01 dated July, 1972., prepared for Collyer Company.

126.

NUS-VEPCO QDR Package 5437-MOV-2-02.

127, NUS-VEPCO QDR Package 5437-133-01.

128.

Automatic Dampers (Safety Related)

Qualification Report for Electric Actuators by RCS.

129, J.

F.

Kircher and R.

E.

Bowan, "Effects of Radiation on MOV-2-02.

and Components," Reinhold, 11964. 4.

130, REIC report No.

21, "The Effect of Nuclear Radiation in Elastomeric and Plastic Components and MOV-2-02.,"

Battelle Memorial Institute, 1964.

131.

W.

W.

Parkinson and O.

Sipman, "The Use of Plastics and Elastomers in Nuclear Radiation, "Gale Ridge National Laboratory, published in Nuclear Engineering and Design, Vol 17, 1971.

132, EPRI Research Project Report NP-1558, "A Review of Aging Theory and Technology," 1980.
133, Table C-1 "Thermal and Radiation Aging Degradation of Selected MOV-2-02.," Appended to DOR Guidelines, Enclosure 4 to IE Bulletin 79-01B.

Appended to DOR Guidelines, Enclosure 4 to IE Bulletin 79-01B.

13.5-01.

134.

NUS-VEPCO QDR Package 5437-~2 11 Q2.

135.

NUS-VEPCO QDR Package 5437-128-01.

136.

NUS-VEPCO QDR Package 5437-103-15, Rev. if: 8/24/81 S2

  • f **

8 13

... l,..,...*... '. '*,.'.. *. ':..

~~

REFERENCE SECTION 8 145.

Westinghouse letter no. NAW-3615 dated Oct. 30, 1980 to Mr. S. C. Brown of VEPCO. Ref. "NUREG-0588 -

Equipment Qualification on Charging Pump Motors."

146.

NUS-VEPCO QDR Package 5437-78-01

  • ViPCO SUBRY UNIT 2 APPENDIX B TO NBC-SER AUGUS'l' 24, 1981 DESIGNATION FOB DEFICIENCY II

- lladhtlon T

- Teaporaturo QT

- Quallfloatlon t1aa BT

- Bequlred tiao P

- Pro1111ure H

- Hualdlty CS

- Choalolll apray LEGEND A

- Halerlal M&1n1 evaluation, replaoeaent 1ohedule, on1otn1 equipaenl aurvaill1noe S

- Subaor1enca H

- Har111n I

- HELD evaluation outaide oontainaont not ooapleted QH

- Qualification aethod RPN - Equlpaent ralooatlon or replaoeaent, adequate eohedule not provided EIN - Exampled equipaont Juat1fioat1on inadequate SEN - Separate offeoto qualif1oat1on juetlf1oat1on inadequate QI

- Qualifioation lnforaatlon beln1 developed RPS - Equipment relocation or replaoement aohodule provided RESOLUTION OF DEFICIENCY I,

Componenta deleted froe th* *aatar llat

2.

C011po11enta roqulrln1 replaoe*ent or 110difloatlon

3.

Coaponent1 dotoraine to ba qualified

~-

C011ponenta detor*lned to be qualified 01oept for aaln1

SURRY-2 APPENDIX B

... **~***********************................ **************** ************ * ***** * ***********************

I NUH KE QUIPIIENT MANUFACTUHEII COMPONENT NUMBER DEFI

'Y RES REF COHHENTS STA

~........... ****************..... -........

I ***** * ***********************

I 279 0531 MOTOR OPERATED VALVE LIMITORQUE MOV-21158 OT,P,A 2 6-13 QDR-51137-HOV-2-01 BASED ON SURRY 1 INSP. WILL BE VERIFIED DURING OUTAGE.

280 0531 MOTOR OPERATED VALVI LIMITOIIQUI MOV-2115C QT,P,A,QI 3 6-1'1 QDR 51137-MOV-2-01 BASED ON SURRY 1 INSP. WILL BE VERIFIED DURING OUTAGE.

281 05]1 MOTOR OPERATED VALVE LIMITORQUI l!(>V-2115D QT,P,A 2 6-15 QDR 51137-HOV-2-01 282 05]1 MOTOR OPEIIATED VALVI LIMITOIIQUE MOV-2115£ QT,P,A,QI 3 6-16 QDR 51137-HOV-2-01 BASED ON SURRY 1 INSP. WILL BE VERIFIED DURING OUTAGE.

28] 0531 MOTOII OPERATED V&LVI LIMITOIIQUI MOV-22891 QT,&

3 6-17 QDR 51137-HOV-~-01 BASED ON SURRY 1 INSP. WILL BE VERIFIED DURING OUTAGE.

2811 05]1 MOTOR OPEIATED VALVE LIMITOIIQUE MOV-2289B QT,A

]

6-18 QDR 51137-ttOV-2-01 BASED ON SURRY 1 INSP. WILL BE VERIFIED DURING OUTAGE 285 01101 SOLENOID VALVE ISCO SOV-22011 11,QT,A 3 6-19 REF QDR-5q37-SOY-D2 286 01101 SOLENOID OPEIIATID VILVI ASCO sov-2200A 11,T,QT,P,H,CS,A 3 6-20 REF QDR-5q37-SOV-02 287 01101 SOLENOID OPEIITED VILVI Asco S0V-2200B R,T,QT,P,H,CS,A 3 6-21 REF QDR-5q37-SOV-02 288 0711 1180V MOTOR CONTROL CUTLKll-llltlMEI 2H1-2 SOUTH R,QT,A,QI 6-23 Ref QDR-5437-78-01 CENTER 289 0711 1180V MOTOR COIITROL CUTLIII-HIMMEI 2H1-2 NORTH R,QT,A,QI 6-211 CENTER 290 0711 qoov MOTOR CONTlioL

. CUTLER-HltllEII 2J1-2 WEST R,QT,A,QI 6-25 CENTER 291 0711 qoov MOTOR CONTROL CUTLER-HAMMEii 2J1-2 EAST R,QT,A,QI 6-26 CENTER

,v 292 1012 POWER PENETRATION CONll SPEC. NO. 21/

CS,A 3 6-27 REF QDR-5q37-117-01 CONAI TYPE 1C S2 B -

2