ML18139B300

From kanterella
Jump to navigation Jump to search
Forwards Updated LERs 81-007/03X-1,80-037/03X-1 & 80-062/03X-1
Date released: 12/10/2018 Download: ML18139B300


Updated LER-80-062/03X-1:on 801019,w/Unit 1 Shutdown & defueled,RM-CC-105 & 106 Alarm Setpoints Found Contrary to Spec.Caused by Decreased Background Radiation Indications. Setpoints Reset to Value Less than Twice Background
ML18139B303
Person / Time
Site: Surry 
Issue date: 05/07/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139B303 (2)
Updated LER 80-037/03X-1:on 800711,while Performing Periodic Test 26.1,radiation Monitor RM-SV-111 Found Inoperative. Caused by Spare Lug Short Causing Erroneous Indications. Lug Removed.Monitor Returned to Svc
ML18139B302
Person / Time
Site: Surry 
Issue date: 05/07/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139B302 (2)
Updated LER 81-007/03X-1:on 810316,w/Unit 1 Defueled & 2 at 100% Power,Power for Several Radiation Monitors Lost.Caused by Shorting of Test Lead to Ground Causing Supply Fuse to Blow.Fuse Replaced.Monitors Returned to Svc
ML18139B301
Person / Time
Site: Surry 
Issue date: 05/07/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139B301 (2)
Forwards Updated LERs 81-007/03X-1,80-037/03X-1 & 80-062/03X-1
ML18139B299
Person / Time
Site: Surry 
Issue date: 05/07/1981
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139B299 (1)