Forwards LERs 80-017/03L-0,80-019/03L-0 & 80-020/03L-0
Date released: 12/10/2018 Download: ML18139A527


LER 80-020/03L-0:on 800822 After Boric Acid Batching,Chemist Reported Concentration Above Tech Spec Requirements.Caused by Transfer of Batch Tank to Inservice Bast.Manual Shutdown Initiated & Boric Acid Diluted to Tech Spec Limits
ML18139A530
Person / Time
Site: Surry Dominion icon.png
Issue date: 09/19/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A530 (2)
LER 80-019/03L-0:on 800822,during Operation Trip Valve TV- SS-206B Would Not Stay Closed When Actuated from Control Room.Caused by Misadjusted Limit Switch.Valve Isolated & Position Limit Switch Readjusted
ML18139A529
Person / Time
Site: Surry Dominion icon.png
Issue date: 09/19/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A529 (2)
LER 80-017/03L-0:on 800820,during Unit 2 Startup at 18% Power,Control Room Surveillance Revealed Zero Reading from Main Steam Flow Transmitter.Caused by Partially Closed Equalizing Valve.Bistables Tripped & Valve Closed
ML18139A528
Person / Time
Site: Surry Dominion icon.png
Issue date: 09/19/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A528 (2)
Forwards LERs 80-017/03L-0,80-019/03L-0 & 80-020/03L-0
ML18139A526
Person / Time
Site: Surry Dominion icon.png
Issue date: 09/19/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18139A526 (1)