LER 80-008/03L-0:on 800623,while Performing Periodic Test 26.1,found Air Ejector Monitor Alarm Setpoint Above Tech Spec Requirement.Caused by Instrument Drift.Alarm Setpoint Recalibr
ML18139A454
Person / Time
Site: Surry Dominion icon.png
Issue date: 07/11/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML18139A453 List:
References
LER-80-008-03L-01, LER-80-8-3L-1, NUDOCS 8007180327
Download: ML18139A454 (2)


Text

CON~'ROL BLOCK: 1 ,. l8 !PLEASE PRINT OR TV.LL REQUIRED INFORMATION) l 0 I 11' Iv IA I s IP Is I 210L..:Io-..i. . =. lo__,1_--1..l. . .::.o. . 1. l~o~l"'--o.L. .:o'I --'1'--""o_.. _l_-_._l-=--o""'--'lo~l0l 411 I 1 I 1 I 1101 I 10 7 8 9 LICENSEE CODE 14 15 LICENSE NUMBER 25 26 LICENSE. TYPE JO 57 CAT SE CON'T J o 1, I 7 8

~:~~~ L!J©I 60 61 oI 5 IoDOCKET I o INUMBER o I 2 I s I 16810169 o I 6EVENT 3 1s ~ a IG)I I 2 IDATE 74 75 O 7 1 I REPORT 1 IDATE 1 I 8 1 °J0 80 EVENT DESCRIPTION AND PROBABLE CONSEQUENCES@

I During the perfonnance of Perodic Test 26.1 it was discovered that the Air Ejector Jo j3 I . Monitor (RM-SV-211) Alarm Setpoint was above the Technical Specification requirement

,,'j Io I 4 I as stated in section 3.7.E Table 3.7.5. This is reportable as per Technical Io Is I Specification 6. 6. 2. b. The Air Ejectors were not in service at this time therefore lo Is I there was no release. The health and safety of the public were not affected.

0 7 0 8 8 9 m:

SYSTEM CAUSE CAUSE COMP. VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE a 9 IM I c!@ L!J@) l!_J@ I 1 IN Is IT I RI tr I@ LU ~@

8 9 10 11 12 13 18 19 20 SEQUENTIAL OCCURRENCE REPORT REVISION LE R/RO CV ENT YEAR REPORT NO. CODE TYPE NO.

@ ii~~~~ l,B I OJ l.::::J I OI OI 8 I I oI 3 ! L!:J L:=J LQJ 23 24 26 27 28 29 30 31 32 ACTION FUTURE EFFECT SHUTDOWN (:;;\ ATTACHMENT NiPRD-4 PRIME COMP. COMPONENT TAKEN ACTION ON PLANT METHOD HOURS ~ SUBMITTED FO!li!M SUB. SUPPLIER MANUFACTURER ul@~@

33 34

  • l3.J@

3!,

~

36

.I'::-_o. __I0_.__I0__,l.__0__.I 37 40 LU@)

41 l!U@

42

~

43 IV 44 j 1 I 1 I 5 ;l§

,c; CAUSE DESCRIPTION AND CORRECTIVE ACTIONS @

0 I This failure was caused by instrument drift in the high alarm setpoint. At no time were the limits of 10CFR20 Appendix B or Technical Specification 3.11.B.8 exceeded.

I The setpoint was readjusted and the monitor returned to service. 9

~...L--"'2_. - L - - - - - - - - - - - - ~ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - '

4 B 9 BO FACILITY STATUS  % POWER OTHER STATUS METHOD OF DISCOVERY DISCOVERY DESCRIPTION

@)32 5 W§ IO I O I O l@)!....___ NA_ _ ____, lJu@)IL-........::OLp-=-e-=-r-=a-=-t-=-o-=-rc....::O:.::b:..:s:..:e:..:r:..:v:..:a::.:t::.:i::..:o:.:n-=-----------~I.

B 9 10 12 1'3 ti ~ ~

ACTIVITY CONTENT ~

RELEASED OF RELEASE AMOUNT OF ACTIVITY ~ LOCATION OF RE~EASE @

D:I] uJ @) u.J@I NA NA B 9 10 11 45 80 PERSONNEL EXPOSURES r:;;:;,.

NUMBER ~ TYPE DESCRIPTION O I O j O k:0~@L..____NA_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _____.

B 9 11 1i 13 80 PERSONNEL *1NJURIES ~

NUMBER DESCRIPTION6 0 I O I O l@._______N_A_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ____,

B 9 11 1;;, BO LOSS OF OR DAMAGE TO FACILITY '4)\

TYPE DESCRIPTION ~

~@ . NA B 9 10 8(

PUBLICITY ISSUED~ DESCRIPTION~

~

NA NRC USE ONLY

~ 6"-:---=------------------------------..J I I I I I I I I I I t I li

~ oso 11 s fi 3~T 1

  • 1. L. Wilson 66 69 SC ;;

a NAME OF P R E P A R E R - - - - - - - - - - - - - - - - - - - PHONE:(804) 357-3184

ATTACHMENT 1

.. $UP~Y POWER STATION, UNIT DOCKET NO: 50-281 e e REPORT NO: 80-008/03L-0 EVENT DATE: 06-23-80 TITLE OF REPORT: RADIATION MONITOR (RM-SV-211) SET POINT DRIFT

1. Description of Event:

While performing Perodic Test 26.1 the Air Ejector Radiation Monitor Alarm Setpoint was found to be higher than allowed by Technical Specificatio~

3.7.E Table 3.7.5. This is reportable as per Technical specification 6.6.2.b.(4.

2. Probaole Consequences and Status of Redundant Systems:

The Air Ejectors for Unit two were not in service, therefore, there was no release and the health and safety of the public were not affected.

3. Cause:

The high alarm setpoint was caused by instrument drift in the Radiation Honitor (RM-SV-211).

4. Immediate Corrective Action:

Recalibrated Tuigh Alarm Setpoint.

5. Subsequent Corrective Action:

None required

6. Actions Taken to Prevent Recurrance No further action required. The Periodic Testing program is designed to lo:~::-=.

this type of failure.

7. Generic Implications None