Forwards IE Info Notice 80-05, Chloride Contamination of Safety-Related Piping & Components. No Written Response Required
ML18139A041
Person / Time
Site: Surry, North Anna  
Issue date: 02/08/1980
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Proffitt W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
References
NUDOCS 8003190456
Download: ML18139A041 (4)


Text

In Reply Refer To:

RII:JPO 50-338, 50-339 5~,_~

C::::::::.S::0-280, 50-28!_.;>

e UNITED STATES NUCLEAR REGULATORY COMMISSION REGION II 101 MARIETTA ST., N.W., SUITE 3100 ATLANTA, GEORGIA 30303 FEB 8 1980 Virginia Electric and Power Company Attn:

W. L. Proffitt Senior Vice President, Power P. 0. Box 26666 Richmond, Virginia Gentlemen:

23261 4

The enclosed IE Information Notice is forwarded to you for information.

No written response to this Information Notice is required.

If you have any questions relateo to tlie subJect, -please contact thfs office.

Enclosures:

1.

IE Information Notice No. 80-05

2.

List of Recently Issued IE Information Notices Sincerely,

~~&6

~James P. O'Reilly Director ll

~ \\

-* ~-

.i Virginia Electric and Power Company cc w/encl:

W.R. Cartwright, Station Manager Post Office Box 402 Mineral, Virginia 23117 P. G. Perry Senior Resident Engineer Post Office Box 38 Mineral, Virginia 23117 W. L. Stewart, Manager Post Office Box 315 Surry, Virginia 23883 t\\~*0::;:c:;;.,;:,-~_,_-:',.::,----*,--~.. ~- - ::-'.~_::.:* --.

4 FEB 8 1980

e UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 February 8, 1980 SSINS No.:

6870 Accession No.:

7912190673 IE Information Notice No. 80-05 CHLORIDE CONTAMINATION OF SAFETY RELATED PIPING AND COMPONENTS A Bechtel Power Corporation Study at the Wolf Creek Project has revealed that a fire retardent coating is potentially corrosive in contact with stainless steel.

Albi "Duraspray" is a fire retardent coating which contains magnesium oxychloride, and is used for fireproofing of exposed structural steel in some Nuclear Power Plants.

There appears to be no deleterious effect when it is applied over unprimed, inorganic zinc coated, or galvanized steel, however, it may be corrosive in contact with stainless steel, bare aluminum or copper.

Droppings or overspray of this material cannot be properly removed with water.

Diluted Nitric acid has been proven to be a useful cleanser, however, it presents a safety hazard.

Applicants and holders of construction permits and licensees of operating power reactors are advised to protect all stainless steel, copper and aluminum material from overspray and droppage of cementitious oxychloride materials and to remove accidently applied materials immediately and completely employing strict safety precautions during the process.

Special attention should be given to weld areas in any removal procedures.

No written response to this information notice is required.

If you require additional information regarding this matter contact the Director of the appropriate NRC Regional Office.

-_"!i,.

IE Information Notice No. 80-05 February 8, 1980 Information Notice No. 80-05 80-04 80-03 80-02 80-01 79-37 79-36 79-35 79-34 79-33 79-32 79-31 79-30 RECENTLY ISSUED IE INFORMATION NOTICES Subject Date Issued Chloride Contamination of 2/8/80 Safety Related Piping and Components BWR Fuel Exposure in 2/4/80 Excess of Limits Main Turbine Electro-1/31/80 Hydraulic Control System 8X8R Water Rod Lower---- -*

  • 1/25/80 End Plug Wear Fuel Handling Events 1/4/80 Cracking in Low Pressure 12/28/79 Turbine Discs Computer Code Defect in 12/31/79 Stress Analysis of Piping Elbow Control of Maintenance 12/31/79 and Essential Equipment Inadequate Design of -

12/27/79 Safety-Related Heat Exchangers Improper Closure of Primary 12/21/79 Containment Access Hatches Separation of Electrical 12/21/79 Cables for HPCI and ADS Use of Incorrect Amplified 12/13/79 Response Spectra (ARS)

Reporting of Defects and 12/6/79

.Noncompliance, 10 CFR Part 21.

Enclosure Issued To All holders of power reactor OLs and CPs All BWR's holding a power reactor OL or CP All holders of power reactor OLs and CPs All BWR Faciliti~s holder power reactor OLs or CPs All holders of power reactor OLs and CPs All power reactor OLs and CPs All power reactor OLs and CPs All power reactor facilities with an OL or CP All holders of power reactor OLs and CPs All power reactor facilities holding OLs and CPs All power reactor facilities holding OLs and CPs All holders of power reactor OLs and CPs All power reactor facilities holding OLs and CPs and vendors inspected by LCVIP