LR-N18-0054, Steam Generator Tube Inspection Report: Twenty-fifth Refueling Outage (1R25)
| ML18127A119 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 05/07/2018 |
| From: | Martino P Public Service Enterprise Group |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| LR-N18-0054 | |
| Download: ML18127A119 (58) | |
Text
PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, NJ 08038-0236 PSEG NudeaTLLC Technical Specification 6.9.1.1 0 LR-N 18-0054 MAY 07 2018 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington DC 20555-001
Subject:
Salem Nuclear Generating Station Unit 1 Facility Operating License No. DPR-70 NRC Docket No. 50-272 Steam Generator Tube Inspection Report-Twenty-fifth Refueling Outage (1 R25)
PSEG Nuclear, LLC (PSEG) hereby submits the Steam Generator Tube Inspection Report consistent with the requirements of Technical Specification (TS) 6.9.1.1 0. The report is being submitted within 180 days after the initial entry into HOT SHUTDOWN following completion of the inspection performed in accordance with Technical Specification 6.8.4.i, "Steam Generator (SG) Program." Salem Unit 1 entered HOT SHUTDOWN (Mode 4) on November 7, 2017, following the completion of its twenty-fifth refueling outage.
The following attachments are included in this letter:
Steam Generator Tube Inspection Report TS 6.9.1.1 0 Salem Unit 1 Model F SG Tube Support Arrangement and Terminology 1 R25 Tubes Plugged For Each Degradation Mechanism Total Number and percentage of Tubes Plugged to Date 1 R25 Nondestructive Examination Techniques 1 R25 Service Induced Indications (AVB Wear) 1 R25 Service Induced Indications (TSP Wear) 1 R25 Service Induced Indications (FBP Wear) 1 R25 Service Induced Indications (Foreign Object Wear)
There are no commitments contained in this letter.
Should you have any questions regarding this submittal, please contact Mr. Harry Balian at (856) 339-2173.
Sincerely, Patrick Martino Plant Manager-Salem Attachments (9)
Page2 LR-N 18-0054 cc:
Mr. D. Lew, Administrator, Region I, NRC Mr. J. Kim, Project Manager, NRC NRC Senior Resident Inspector, Salem Mr. P. Mulligan, Manager IV, NJBNE Mr. L. Marabella, Corporate Commitment Tracking Coordinator Mr. T. Cachaza, Salem Commitment Tracking Coordinator Mr. M. Washington, Chief Inspector-Occupational Safety and Health Bureau of Boiler and Pressure Vessel Compliance
LR-N18-0054 Steam Generator Tube Inspection Report TS 6.9.1.10 LR-N 18-0054 INTRODUCTION STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10 PSEG Nuclear LLC Salem Unit 1 In 1998 Salem Unit 1 commenced operating cycle 13 with the newly replaced steam generators from the canceled Seabrook-2 plant. Salem Unit 1 is a four (4) loop Westinghouse Pressurized Water Reactor (PWR) with Model F SGs that incorporate thermally treated lnconel 600 U-tubes.
The tube bundle consists of 5,626 tubes with an outside diameter (00) of 0.688 inches and a nominal tube wall thickness of 0.040 inches. During SG fabrication, the tubes were hydraulically expanded over the full tubesheet depth and the first ten tube rows were thermally stress relieved after U-bend formation. The seven (7) tube support plates (TSP) are fabricated from 405 stainless steel (SS) and have broached "quatrefoil" tube holes. A flow distribution baffle (FOB) plate, also 405SS, between the secondary face of the tubesheet and the first tube support plate, provides top-of-tubesheet (TTS) sludge pile control. Tube support within the U-bend region is provided by three V-shaped chrome-plated lnconel 600 antivibration bars (AVB's). Attachment 2 provides a general summary of the Salem Unit 1 Model F SG Tube Support Arrangement and Terminology.
Consistent with Technical Specification (TS) 6.9.1.1 0, this report is being submitted within 180 days after the initial entry into HOT SHUTDOWN following completion of inspection performed in accordance with the Specification 6.8.4.i, "Steam Generator Program".
This report includes:
- a.
The scope of inspections performed on each SG,
- b.
Degradation mechanisms found,
- c.
Nondestructive examination techniques utilized for each degradation mechanism,
- d.
Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- e.
Number of tubes plugged during the inspection outage for each degradation mechanism,
- f.
The number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator,
- g.
The results of condition monitoring, including the results of tube pulls and in-situ testing.
- h.
The primary to secondary leakage rate observed in each SG (if it is not practical to assign the leakage to an individual SG, the entire primary to secondary leakage should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report,
- i.
The calculated accident induced leakage rate from the portion of the tubes below 15.21 inches from the top of the tubesheet for the most limiting accident in the most limiting SG.
In addition, if the calculated accident induced leakage rate from the most limiting accident is less than 2.16 times the maximum operational primary to secondary leakage rate, the report should describe how it was determined,
- j.
The results of monitoring for tube axial displacement (slippage).
If slippage is discovered, the implications of the discovery and corrective action shall be provided.
Page 1 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10 EXPLANATION OF TERMS 1 R25:
AVB:
BET:
BHT:
BLG:
CL:
CM:
DNG:
DNT:
EPRI:
ETL:
ETSS:
FBC:
FBH:
FBP:
FOB:
HL:
NDE:
OA:
00:
OEX:
OXP:
PLP:
PWR:
SG:
TEC:
TEH:
TS:
TSC:
TSH:
TTS:
TSP:
TW:
Vpp:
Unit 1 25th Refueling Outage Anti-Vibration Bar Bottom Expansion Transition (synonymous with BHT)
Bottom Hydraulic Transition (synonymous with BET)
Bulge (Expansion (Per PSEG reporting requirement, these typically occur within the hydraulically expanded tubesheet)
Cold Leg Condition Monitoring Ding (Freespan region of the tube per PSEG reporting requirements)
Dent (At support structures per PSEG reporting requirements)
Electric Power Research Institute Expansion Transition Location (PSEG reporting requirements)
Examination Technique Specification Sheet Flow Baffle Cold leg (designates the Flow Distribution Baffle Plate on the Cold Leg)
Flow Baffle Hotleg (designates the Flow Distribution Baffle Plate on the Hot leg)
Flow Distribution Baffle Plate (synonymous with FOB)
Flow Distribution Baffle Plate (synonymous with FBP)
Hot Leg Non Destructive Examination Operational Assessment Outside Diameter Over Expansion (a localized variation in tube diameter within the hydraulically expandedtubesheeQ Over Expansion (hydraulic expansion occurring above the top of tubesheet)
Possible Loose Part Pressurized Water Reactor Steam Generator Tube End Coldleg Tube End Hotleg Technical Specification Tubesheet Cold Leg Tubesheet Hot Leg Top of Tubesheet Tube Support Plate Through-Wall Volts Peak to Peak SG inspections were performed in accordance with TS 6.8.4.i, "Steam Generator Program",
during Salem Unit 1 Outage 1 R25. Each reporting requirement of TS 6.9.1.1 0 is addressed below (items a through j).
Page 2 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10
- a. Technical Specification 6.9.1.1 O.a, "The scope of inspections performed on each SG" If not stated otherwise, the following inspections were performed on all four steam generators:
Bobbin Probe
- 1. A full-length (tube end to tube end) bobbin coil probe inspection was performed on 1 00°/o of the in-service tubes.
Array Probe (X-Probe)
- 1. 1 00°/o of the first 3 outer periphery tubes on both TTS hot leg (HL) and cold leg (CL); and the first 3 rows of no-tube lane on the HL and CL (SG 13 included 100% of all tubes on HL and CL). Inspection extent from TSH -15.21" (i.e.- 15.21 inches below the TTS) to the first tube support above the TTS (i.e. - 01 H), and TSC -2" to the first tube support above the TTS (i.e. - 01 C).
- 2. 50% HL TTS Expansion Transitions, TSH +3" to -15.21"
- 3. 100°/o OXP, ETL, BHT >= 0 or BHT <= -0.40 inches, TSH +3" to -15.21" and TSC +3" to
-2"
- 4. 50% HL BLG >= 18 volts and OEX > 0.25 inches, TSH +3" to -15.21"
- 5. Special Interest Inspections, including bounding locations with possible loose parts identified by eddy current or secondary side inspections.
Rotating Probe (+Point)
- 1. 50% HL DNT and DNG > 2 volts as reported from 1 R24, TSH to 07H (Includes 50°/o of the DNT and DNG > 5 volts)
- 2. 20% CL DNT and DNG > 5 volts as reported from 1 R24, TSC to 07C
- 3. 20% U-bend DNT and DNG > 2 volts, as reported from 1 R24, 07H to 07C (Includes 20%
of the DNT and DNG > 5 volts)
- 4. 20% Row 1 and Row 2 tubes, 07H to 07C
- 6. 1 00°/o of the HL FBP and TSP intersections, FBH to 07H, of the tubes screened for possible higher stress (i.e. - 2 Sigma Tubes).
- 7. Special Interest Inspections, including Bobbin "I" codes and sizing locations with foreign object wear.
- b. Technical Specification 6.9.1.1 O.b, "Degradation mechanisms found" The tube degradation mechanisms found during outage 1 R25 are AVB wear, TSP wear, FBP wear, and Foreign Object wear (Also referred to as Loose Part Wear).
- c. Technical Specification 6.9.1.1 O.c, "Nondestructive examination techniques utilized for each degradation mechanism" Page 3 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10 provides the Nondestructive examination techniques utilized for each degradation mechanism.
- d. Technical Specification 6.9.1.1 O.d, "Location, orientation (if linear), and measured sizes (if available) of service induced indications" The service induced indications detected during outage 1 R25 are AVB wear, TSP wear, FBP wear, and Foreign Object wear.
Attachments 6, 7, 8, and 9 provide information for the service induced indications. The TW sizing provided in Attachments 6, 7, and 8 is from EPRI ETSS 96041.1, 96004.1, and 96042.1; respectively. The TW sizing provided in Attachment 9 is from EPRI ETSS 27901.1 or 27902.1.
- e. Technical Specification 6.9.1.1 O.e, "Number of tubes plugged during the inspection outage for each degradation mechanism" provides the number of tubes plugged during the inspection outage for each degradation mechanism.
- f. Technical Specification 6.9.1.10.f, "Total number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator" provides the total number and percentage of tubes plugged to date in each steam generator. The plugging percentage and the effective plugging percentage are the same.
- g. Technical Specification 6.9.1.1 O.g, "The results of condition monitoring, including the results of tube pulls and in-situ testing" The largest depth of degradation detected during 1 R25 for AVB wear was 34°/o TW, TSP wear was 13°/o TW, FBP wear was 9°/o TW, and Foreign Object wear was 97% TW (reference response to 6.9.1.1 O.d for further details). The Foreign Object wear indication, in SG 13 Tube Row 2 Column 91 near TSP 03C, was identified as the tube responsible for primary to secondary side leakage initially identified in May 2017 (Also see NRC ML17332A603). This tube was full length in-situ pressure tested. All tubes eddy current inspected or in-situ pressure tested met the tube integrity performance criteria in TS 6.8.4.i.b. No tube pulls were required.
All tubes with detected foreign object wear were plugged (see response to 6.9.1.1 O.e and ).
Page 4 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10
- h. Technical Specification 6.9.1.1 O.h, "The primary to secondary leakage rate observed in each SG (if it is not practical to assign the leakage to an individual SG, the entire primary to secondary leakage should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report" On Monday May 15, 2017 at approximately 1800, operators in the Salem Unit 1 Control Room identified a rise in the primary-to-secondary leakage from radiation monitor indications. The small leak was identified in SG 13, and went below detection around May 28, 2017. Primary to secondary leak trend information provided in NRC ML17332A603 includes chemistry grab sample results for the duration of the leak event, up to the start of outage 1 R25 (October 12, 2017). Subsequent to May 28, 2017, the leak remained below detection.
- i. Technical Specification 6.9.1.1 O.i, "The calculated accident induced leakage rate from the portion of the tubes below 15.21 inches from the top of the tubesheet for the most limiting accident in the most limiting SG. In addition, if the calculated accident induced leakage rate from the most limiting accident is less than 2.16 times the maximum operational primary to secondary leakage rate, the report should describe how it was determined" Response to item h above provides SG 13 experienced an operational primary to secondary leak. The source of this leak was not associated the tubesheet (See response to 6.9.1.1 O.g).
PSEG did not observe any primary to secondary operational leakage, associated with the tubesheet, at or greater than the detection threshold of approximately one (1) gallon per day over the cycle preceding the inspection in any of the steam generators at Salem Unit 1.
Therefore, the calculated accident induced leakage rate from the most limiting accident would not be significant.
- j. Technical Specification 6.9.1.1 O.j, "The results of monitoring for tube axial displacement (slippage). If slippage is discovered, the implications of the discovery and corrective action shall be provided" 100% of all in-service tubes within the tubesheet, both HL and CL, were monitored for tube axial displacement (slippage) using Bobbin coil inspections. No indications of slippage were detected.
Page 5 of 5 LR-N18-0054 SALEM UNIT 1 MODEL F SG TUBE SUPPORT ARRANGEMENT AND TERMINOLOGY Tube Support Plate (TSP)
Tube Support ---..
Number Flow Distribution Baffle Plate (FOB)
Anti-Vibration Bars (AVB) 03H 02H OlH Top of Tubesheet (TTS)
Page 1 of 1 LR-N18-0054 1R25 TUBES PLUGGED FOR EACH DEGRADATION MECHANISM Steam Generator Location Tube Degradation 11 12 13 14 AVB Wear 0
0 0
0 TSP Wear 0
0 0
0 FBP Wear 0
0 0
0 All Foreign Object Wear 0
0 6
0 Total Tubes Plugged 0
0 6
0 Page 1 of 1 Total 0
0 0
6 6
LR-N18-0054 TOTAL NUMBER AND PERCENTAGE OF TUBES PLUGGED TO DATE Salem Unit 1 Steam Generator Tube Plu in Status SG 11 SG 12 SG 13 SG 14 51 57 113 36 0
0 6
0 51 57 119 36 0.91%)
1.01%>
2.12°/o 0.64%
1.17o/o Page 1 of 1 LR-N18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing Bobbin 96041.1 R5 Wear AVB None Yes Yes Bobbin 96042.1 R4 Wear Drilled TSP None Yes Yes Bobbin 96004.1 R13 Wear TSP and AVB None Yes Yes Bobbin 96004.3 Rl3 Wear TSP and AVB None Yes Yes Bobbin 27091.2 R2 Loose Part Freespan, PLP Loose Part Yes Size with +Point Volumetric W ear(part not Volumetric or Array present)
Wear with Part Present and Loose Parts Bobbin I-28411 R4 Axial Within non None Yes For CM/OA or ODSCC dented drilled Info Only TSP and within drilled TSP with dents:::; 2.0 Vpp Bobbin I-28412 R5 Axial Freespan with None Yes ForCM/OA or ODSCC or without dents Info Only
- 2.0 Vpp Bobbin I-28413 R5 Axial Within None Yes For CM/OA or ODSCC
- Freespan, Info Only Sludge Pile region and Broached TSP with or without dents :::; 2.0 Vpp
+Point 96910.1 R11 Wear Broached TSP FDB Wear&
Yes Yes-TSP Wear; Loose Part CMIOA or Info Wear with or Only for without part extended present applicability areas Page 1 of 5 LR-N18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing
+Point 27901.1 R1 Shape Freespan, TSP Detection of Yes Yes-Part Not 27902.1 R2 Dependent and Expansion foreign Present or 27903.1 R1 Volumetric Transition PLP material Removed 27904.1 R2 Indications Wear 27905.1 R2 Morphology For detection 27906.1 R1 Dependent-and sizing of 27907.1 R2 part not present PLP wear when part is present based on EPRI Report 1020631
+Point 10908.4 R1 AVB Wear U-bend None Yes Yes
+Point I-11524 RO Circ. PWSCC Expansion Dings, Dents, Yes See 20510.1 for Transition Tubesheet sizing (including OEX,BLG and OXP) and Non-dented support structures
+Point 20510.1 R7 Circ. PWSCC Expansion Dings, Dents, N/A ForCM/OAor Transition Tubesheet See I-11524 for Info Only (including detection OEX,BLG and OXP) and Non-dented support structures
+Point 96703.1 R17 Axial Dent or Ding Non-dented Yes ForCM/OA or PWSCC support Info Only structure and tubesheet
+Point 20511.1 R8 Axial Expansion Non-dented Yes For CMIOA or PWSCC Transition support Info Only structure and tubesheet
+Point 21410.1 R6 Circ. ODSCC Expansion
- Freespan, Yes For CMIOA or Transition Dings, Dented Info Only and Non-dented support structures, Sludge Pile, Tubesheet Page 2 of 5 LR-N 18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing
+Point I-28424 R4 Axial Sludge Pile; Expansion Yes N/A ODSCC within non Transition See I-28431 for dented drilled sizing TSP and within drilled TSP with dents (or Dings)
- S2.0 Vpp.
+Point I-28425 R4 Axial Freespan; within Expansion Yes N/A ODSCC non dented Transition See I-28432 for broached TSP sizing and within broached TSP with dents/ dings
- 2.0 Vpp.
+Point 21409.1 R7 Axial Support None Yes For CM/OA or ODSCC structures, Info Only freespan regions, sludge pile and tubesheet crevice
+Point I-28431R3 Axial Sizing None See I-28424 for Yes ODSCC Sludge Pile and detection Drilled TSP with or w/o Dents :::; 2 volts
+Point I-28432 R2 Axial Sizing None See I-28425 for Yes ODSCC
- Freespan, detection Broached TSP w/o Dents:::; 2 volts
+Point 22401.1 R4 Axial Dented Tube Dented AVB Yes For CM/OA or ODSCC Support and U-bend Info Only Structures dings (TSP/FDB)
+Point 96511.2 R16 Axial & Circ.
U-bend None Yes For CM/OA or PWSCC Info Only
+Point 10411.1 RO Axial U-bend Row 3-Ax and Circ Yes For CM/OA or 10411.2 RO ODSCC 5
- ODSCC, Information Only Row 1 and2 U-bends &
Higher Row U-bends (>R5)
+Point 13901.1 Rl Wear Tube to Tube N/A Yes Yes
+Point 21998.1 R4 Volumetric Freespan Sludge Pile Yes Yes Page 3 of 5 LR-N 18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing Array 11956.3 R2 Wear Broached TSP FDB Wear and Yes Yes (Ax. Sensitive)
Loose Part 11956.4 R2 Wear with Part (Circ.
Present Sensitive)
Array 17901.1 RO Shape Freespan part Detection of Yes Yes (Ax. Sensitive)
Dependent not present foreign (Part Not 17901.3 RO Volumetric material Present)
(Circ.
Indications Sensitive)
Detection of 17902.1 RO PLP wear (Ax. Sensitive) when part is 17902.3 RO present.
(Circ.
Sensitive) 17903.1 RO (Ax. Sensitive) 17903.3 RO (Circ.
Sensitive) 17904.1 RO (Ax. Sensitive) 17904.3 RO (Circ.
Sensitive) 17905.1 RO (Ax. Sensitive) 17905.3 RO (Circ.
Sensitive) 17906.1RO (Ax. Sensitive) 17906.3 RO (Circ.
Sensitive)
Array 17909.1 RO AVB Wear AVB Wear N/A Yes Yes (Ax. Sensitive)
Broached Mix 17909.4 RO (Circ.
Sensitive)
Array 20400.1 R5 Circ. ODSCC Expansion Axial ODSCC Yes N/A Transitions at Expansion Transition Circ ODSCC Freespan with/without Deposits (including sludge pile)
Page 4 of 5 LR-N18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing Array 20403.1 R 5 Axial Freespan - Not Freespan Yes N/A ODSCC associated with Deposits Deposits Present (including sludge pile)
Array 20500.1 R4 Ax. and Circ.
Expansion OEX,BLG Yes N/A 20501.1 R4 PWSCC Transition andOXP locations above and within the tubesheet Page 5 of 5 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 22 80 AV2
-0.2 11 11 22 80 AV1
-0.21 10 11 23 38 AV2 0.16 10 11 24 117 AV1
-0.02 10 11 24 117 AV6
-0.3 9
11 26 43 AV1
-0.16 13 11 26 43 AV2 0.1 16 11 26 43 AV5
-0.16 9
11 26 91 AV6 0.02 13 11 26 91 AV5
-0.07 9
11 26 91 AV1
-0.09 18 11 27 33 AV2
-0.14 13 11 27 33 AV5 0.08 10 11 27 33 AV6
-0.08 11 11 27 44 AV6 0.3 20 11 27 44 AV5
-0.14 11 11 27 44 AV2
-0.21 17 11 27 78 AV2 0.09 12 11 27 79 AV2
-0.28 8
11 27 80 AV2 0.04 20 11 27 115 AV6 0.2 11 11 28 10 AV2 0.04 10 11 28 10 AV1 0.01 11 11 28 114 AV6
-0.14 18 11 28 114 AV1 0.18 18 11 29 9
AV5
-0.22 25 11 29 9
AV2 0.11 14 11 29 54 AV2 0.01 11 11 29 54 AV1 0.01 10 11 29 112 AV5
-0.17 13 11 29 112 AV2
-0.5 21 11 29 114 AV6
-0.21 29 11 29 114 AV1 0.14 21 11 30 48 AV2 0.13 12 11 30 73 AV5
-0.42 12 11 30 86 AV2 0.11 12 11 30 86 AV1 0.61 10 11 31 109 AV6
-0.1 9
11 32 12 AV4
-0.04 13 Page 1 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 32 12 AV5 0.04 14 11 32 15 AV2 0.06 12 11 32 20 AV5
-0.07 8
11 32 31 AV2
-0.04 16 11 32 69 AV4 0.05 9
11 32 72 AV4
-0.16 14 11 32 72 AV3
-0.2 15 11 32 72 AV2 0.11 11 11 32 72 AV1
-0.22 13 11 32 84 AV4
-0.14 9
11 32 112 AV5 0.6 10 11 32 112 AV2
-0.6 8
11 33 107 AV6
-0.07 8
11 34 109 AV2
-0.2 21 11 34 111 AV6
-0.51 9
11 34 111 AV2
-0.59 9
11 35 13 AV6
-0.02 9
11 35 13 AV5
-0.06 13 11 35 44 AV6 0.25 14 11 35 44 AV5 0.14 23 11 35 44 AV4 0.06 18 11 35 44 AV1
-0.28 12 11 36 108 AV1
-0.5 10 11 36 109 AV6
-0.25 9
11 36 110 AV3
-0.07 10 11 37 48 AV2 0.04 9
11 37 65 AV2 0.02 10 11 37 67 AV1 0.47 10 11 37 68 AV5
-0.02 15 11 37 68 AV4 0.02 9
11 37 68 AV4
-0.25 12 11 37 68 AV3
-0.2 14 11 37 68 AV2 0.15 21 11 37 73 AV4 0.16 9
11 37 79 AV5 0.05 12 11 37 79 AV4 0.07 19 11 37 79 AV2 0.07 15 11 37 79 AV1 0.05 9
11 37 84 AV1 0.02 9
Page 2 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 37 100 AV5 0.09 9
11 37 100 AV4 0.02 10 11 37 100 AV2
-0.04 11 11 37 100 AV1
-0.02 9
11 38 15 AV2 0.08 10 11 38 15 AV1
-0.12 9
11 38 49 AV4 0.12 23 11 38 49 AV3 0.02 15 11 38 51 AV5 0.02 16 11 38 51 AV4
-0.2 17 11 38 51 AV2
-0.29 11 11 38 51 AV6 0.09 11 11 38 66 AV6 0.2 21 11 38 66 AV5
-0.23 25 11 38 66 AV4 0.09 8
11 38 66 AV3
-0.07 11 11 38 66 AV2 0.16 19 11 38 66 AV1
-0.11 9
11 38 74 AV3
-0.18 8
11 38 76 AV4 0.02 8
11 38 76 AV3 0.07 11 11 38 76 AV2 0.05 15 11 38 90 AV3
-0.09 11 11 38 105 AV6 0.02 12 11 38 105 AV5 0.11 24 11 38 105 AV4
-0.09 10 11 38 105 AV3
-0.27 21 11 38 105 AV2 0.02 21 11 38 108 AV5 0.38 7
11 38 108 AV4
-0.13 7
11 38 108 AV3
-0.23 12 11 39 17 AV5 0.06 15 11 39 37 AV6 0.12 12 11 39 41 AV2 0.04 12 11 39 55 AV5 0.04 9
11 39 55 AV3
-0.2 10 11 39 60 AV4 0.06 12 11 39 61 AV5
-0.18 16 11 39 61 AV4
-0.28 12 Page 3 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 39 61 AV6
-0.04 11 11 39 64 AV4 0.05 18 11 39 64 AV3 0.05 14 11 39 69 AV4
-0.29 11 11 39 69 AV2
-0.18 18 11 39 72 AV5 0.11 9
11 39 72 AV4 0.14 23 11 39 72 AV3
-0.11 18 11 39 72 AV2 0.15 21 11 39 72 AV1
-0.25 12 11 39 74 AV6 0.19 27 11 39 74 AV5 0.25 31 11 39 74 AV4
-0.31 23 11 39 74 AV3
-0.16 7
11 39 74 AV2
-0.21 9
11 39 99 AV5 0.02 17 11 39 99 AV3
-0.04 14 11 39 99 AV2
-0.27 31 11 39 107 AV4 0.22 9
11 40 19 AV3 0.04 13 11 40 20 AV4 0.04 17 11 40 20 AV3
-0.14 20 11 40 20 AV2 0.06 11 11 40 27 AV4
-0.14 9
11 40 37 AV2 0.08 10 11 40 40 AV2 0.06 10 11 40 40 AV1 0.04 9
11 40 42 AV4
-0.22 16 11 40 42 AV3 0.06 9
11 40 42 AV2 0.12 9
11 40 42 AV1 0.16 12 11 40 43 AV6 0.14 16 11 40 43 AV4 0.17 22 11 40 43 AV3 0.16 27 11 40 43 AV2
-0.23 29 11 40 43 AV1
-0.12 13 11 40 45 AV5
-0.02 13 11 40 45 AV4 0.02 12 11 40 48 AV6
-0.18 14 Page 4 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 40 48 AV4 0.02 12 11 40 48 AV3 0.02 14 11 40 48 AV2
-0.16 14 11 40 58 AV6 0.04 22 11 40 58 AV5 0.21 13 11 40 58 AV4 0.1 7
11 40 58 AV3 0.04 22 11 40 58 AV2 0.08 12 11 40 64 AV2
-0.18 11 11 40 77 AV3
-0.27 11 11 40 78 AV6
-0.18 10 11 40 78 AV5 0.33 28 11 40 78 AV4
-0.18 10 11 40 78 AV3
-0.27 31 11 40 78 AV2
-0.2 15 11 40 78 AV1 0.07 16 11 40 79 AV5
-0.04 13 11 40 79 AV3
-0.19 22 11 40 79 AV2 0.05 15 11 40 79 AV1
-0.67 9
11 40 84 AV6 0.07 15 11 40 84 AV5
-0.12 12 11 40 84 AV4 0.09 15 11 40 84 AV3 0.04 9
11 40 85 AV2 0.14 18 11 40 86 AV5 0.05 9
11 40 89 AV5
-0.02 12 11 40 89 AV4
-0.16 20 11 40 89 AV3 0.07 14 11 40 89 AV2
-0.25 8
11 40 91 AV1
-0.07 11 11 40 92 AV1
-0.07 11 11 40 98 AV5
-0.19 21 11 40 98 AV4 0.13 12 11 40 104 AV6
-0.16 10 11 40 104 AV5
-0.2 28 11 40 104 AV4
-0.22 27 11 40 104 AV3 0.07 14 11 40 105 AV6 0.07 31 Page 5 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 40 105 AVS 0.07 25 11 40 105 AV4
-0.22 24 11 40 105 AV3 0.06 33 11 40 105 AV2 0.05 16 11 40 106 AV6
-0.13 13 11 40 106 AVS 0.18 11 11 41 19 AV6 0.12 15 11 41 23 AV1 0.08 10 11 41 59 AV1
-0.24 11 11 41 73 AV1
-0.11 10 11 41 73 AV2
-0.07 9
11 41 82 AV4
-0.09 10 11 41 90 AVS 0.09 13 11 41 90 AV4 0.04 14 11 41 95 AV1
-0.16 11 11 41 100 AVS
-0.07 12 11 41 100 AV2 0.16 14 11 41 102 AV6
-0.04 12 11 41 102 AVS 0.02 14 11 41 102 AV2 0.09 13 11 41 102 AV1
-0.13 14 11 41 103 AVS
-0.04 21 11 41 103 AV4
-0.18 9
11 41 103 AV2 0.22 10 11 41 103 AV1 0.11 14 11 41 105 AV6
-0.45 9
11 41 105 AV1 0.36 7
11 42 33 AV3
-0.15 16 11 42 33 AV2 0.02 24 11 42 so AVS
-0.11 9
11 42 54 AVS
-0.18 11 11 42 78 AVS 0.2 10 11 42 95 AVS
-0.11 10 11 42 95 AV4
-0.09 11 11 42 95 AV3 0.07 11 11 42 97 AV3
-0.04 10 11 42 97 AV2
-0.09 10 11 42 97 AV1 0.02 15 11 42 99 AV4
-0.2 13 Page 6 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 42 99 AV2
-0.02 10 11 42 104 AV6 0.15 9
11 42 104 AV6
-0.16 10 11 43 20 AV5 0.1 21 11 43 22 AV4 0.08 27 11 43 22 AV3 0.08 10 11 43 25 AV5 0.21 27 11 43 25 AV4 0.22 21 11 43 25 AV3 0.02 12 11 43 33 AV2 0.05 11 11 43 38 AV3 0.08 30 11 43 38 AV2
-0.22 27 11 43 38 AV1 0.2 19 11 43 39 AV5
-0.08 13 11 43 39 AV2
-0.16 6
11 43 43 AV5 0.06 24 11 43 43 AV3
-0.12 19 11 43 43 AV2 0.06 26 11 43 44 AV6 0.2 11 11 43 44 AV5 0.1 21 11 43 44 AV4
-0.12 14 11 43 44 AV3
-0.21 22 11 43 44 AV2
-0.22 28 11 43 44 AV1
-0.16 12 11 43 46 AV6 0.38 21 11 43 46 AV5
-0.17 13 11 43 46 AV4 0.21 12 11 43 49 AV6
-0.02 9
11 43 49 AV4
-0.2 21 11 43 49 AV3
-0.13 12 11 43 52 AV2
-0.04 9
11 43 52 AV3 0.02 11 11 43 60 AV3
-0.08 11 11 43 62 AV2
-0.07 11 11 43 62 AV1 0.02 11 11 43 67 AV2
-0.16 11 11 43 67 AV1 0.04 11 11 43 75 AV3
-0.21 18 11 43 75 AV1
-0.29 19 Page 7 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 43 79 AV6 0.02 26 11 43 79 AV5 0.02 26 11 43 79 AV4
-0.05 16 11 43 79 AV2
-0.2 16 11 43 79 AV1
-0.29 9
11 43 81 AV5 0.35 8
11 43 82 AV5 0.15 12 11 43 82 AV4 0.07 10 11 43 83 AV3 0.02 12 11 43 83 AV2 0.02 11 11 43 83 AV5 0.18 13 11 43 83 AV4
-0.18 28 11 43 91 AV1 0.02 9
11 43 100 AV4 0.18 12 11 43 100 AV3 0.24 29 11 43 100 AV2
-0.18 19 11 43 100 AV1 0.02 11 11 43 103 AV6
-0.22 9
11 44 22 AV5 0.02 26 11 44 22 AV4
-0.02 13 11 44 41 AV3 0.01 8
11 44 41 AV4
-0.04 19 11 44 41 AV1 0.01 12 11 44 45 AV4 0.04 10 11 44 45 AV3
-0.06 16 11 44 45 AV2 0.06 9
11 44 58 AV4 0.06 22 11 44 58 AV3 0.08 18 11 44 59 AV4
-0.16 12 11 44 59 AV3
-0.12 16 11 44 59 AV2 0.17 11 11 44 59 AV1 0.06 10 11 44 60 AV4 0.06 24 11 44 60 AV3 0.06 18 11 44 60 AV2 0.02 10 11 44 61 AV3
-0.19 12 11 44 61 AV2
-0.13 10 11 44 68 AV6
-0.25 32 11 44 68 AV5
-0.21 26 Page 8 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 44 68 AV4
-0.24 16 11 44 68 AV3
-0.22 15 11 44 71 AV6 0.04 10 11 44 71 AV5
-0.21 9
11 44 71 AV4
-0.02 12 11 44 74 AV6
-0.31 13 11 44 74 AV5
-0.24 16 11 44 74 AV4 0.13 16 11 44 74 AV3 0.04 25 11 44 100 AV6
-0.06 9
11 44 100 AV5 0.15 29 11 44 100 AV4 0.05 10 11 44 100 AV3
-0.07 9
11 44 100 AV2
-0.07 7
11 44 102 AV6
-0.04 11 11 44 102 AV5 0.02 10 11 45 22 AV4 0.02 8
11 45 23 AV6
-0.18 16 11 45 23 AV2 0.19 11 11 45 26 AV3 0.04 12 11 45 26 AV2
-0.13 11 11 45 83 AV5
-0.22 11 11 45 100 AV6 0.11 11 11 47 43 AV5 0.04 9
11 47 99 AV3
-0.02 12 11 48 25 AV1 0.1 10 11 48 26 AV6
-0.2 9
11 48 26 AV5 0.06 15 11 48 47 AV5 0.1 14 11 48 80 AV1
-0.32 9
11 48 97 AV4 0.02 10 11 48 97 AV3
-0.04 12 11 49 27 AV1 0.04 12 11 49 29 AV5 0.12 27 11 49 29 AV4 0.02 9
11 49 36 AV4
-0.12 11 11 49 36 AV2
-0.19 15 11 49 39 AV4 0.06 17 11 49 39 AV2 0.08 19 Page 9 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 49 43 AV4 0.1 16 11 49 79 AV1
-0.53 12 11 49 84 AV1
-0.04 10 11 49 85 AV6 0.07 13 11 49 85 AVS 0.13 34 11 49 85 AV4 0.16 30 11 49 85 AV3 0.13 23 11 49 85 AV2 0.09 16 11 49 94 AV6
-0.17 11 11 49 96 AV6
-0.26 12 11 so 30 AV6
-0.06 12 11 so 65 AV2 0.11 12 11 so 90 AV1
-0.38 16 11 51 47 AVS 0.08 11 11 52 32 AV1 0.06 8
11 52 41 AV3
-0.06 10 11 52 89 AV4
-0.07 10 11 52 91 AVS
-0.02 11 11 52 91 AV2 0.18 11 11 54 39 AV6 0.02 11 11 54 65 AV4
-0.22 12 11 54 86 AV3 0.07 15 11 55 79 AV2
-0.07 11 11 55 82 AV2 0.11 9
11 55 83 AV6
-0.2 13 11 55 83 AVS 0.02 12 11 55 83 AV2 0.07 11 11 55 84 AV6
-0.15 14 11 55 84 AVS
-0.19 8
11 55 84 AV4
-0.02 9
11 56 41 AV6 0.01 13 11 56 78 AV2 0.01 11 11 56 79 AV2
-0.13 9
11 57 70 AV1
-0.07 12 11 57 75 AV2 0.06 8
11 57 77 AV6 0.02 10 11 57 77 AV2 0.02 15 11 57 77 AV6
-0.13 11 11 57 79 AV2 0.02 13 Page 10 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 58 61 AV6 0.12 10 11 58 62 AV6 0.19 10 11 58 62 AV1
-0.17 14 11 58 65 AV6 0.13 13 11 58 65 AV1
-0.09 10 11 59 58 AV6 0.23 13 12 21 84 AV1
-0.3 13 12 21 118 AV6 0.4 8
12 21 118 AV1 0.13 12 12 23 89 AV6
-0.07 20 12 23 89 AV2
-0.16 13 12 23 89 AV1
-0.39 9
12 23 91 AV1
-0.2 16 12 25 90 AV2
-0.09 11 12 25 116 AV1 0.36 9
12 26 38 AV6
-0.25 14 12 26 74 AV2
-0.33 20 12 26 74 AV5 0.02 13 12 26 83 AV1
-0.2 14 12 26 83 AV2 0.57 19 12 26 95 AV5 0.15 10 12 26 95 AV2
-0.24 9
12 26 103 AV2
-0.14 15 12 26 109 AV1 0.05 8
12 26 110 AV2
-0.22 8
12 27 8
AV1 0.33 22 12 27 8
AV1
-0.08 24 12 27 8
AV6 0.12 24 12 27 8
AV6
-0.21 11 12 27 36 AV5 0.26 9
12 27 102 AV2 0.02 9
12 27 112 AV2 0.14 20 12 27 115 AV6 0.07 31 12 27 115 AV1 0.02 16 12 28 109 AV5 0.12 12 12 29 13 AV6
-0.12 17 12 29 39 AV6
-0.18 10 12 29 39 AV5 0.02 21 12 29 39 AV2 0.2 21 Page 11 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 29 41 AV6
-0.2 15 12 29 41 AV5
-0.16 13 12 29 41 AV1 0.32 9
12 29 41 AV2 0.22 15 12 29 54 AV6 0.04 14 12 29 54 AV5
-0.02 20 12 29 54 AV2
-0.16 13 12 29 54 AV1 0.01 17 12 29 77 AV2
-0.11 12 12 29 86 AV6
-0.02 8
12 29 86 AV2 0.02 18 12 29 86 AV1
-0.27 11 12 29 89 AV2
-0.2 13 12 29 90 AV2 0.02 11 12 29 107 AV2 0.04 12 12 29 108 AV5 0.05 21 12 29 109 AV2 0.1 18 12 29 112 AVS 0.24 18 12 30 10 AV5 0.18 9
12 30 12 AV2
-0.18 12 12 30 13 AV2 0.07 19 12 30 104 AV5 0.09 15 12 30 111 AV6 0.09 15 12 30 111 AV3
-0.02 13 12 31 16 AV2
-0.22 11 12 31 113 AV5 0.26 7
12 31 113 AV2
-0.38 6
12 32 106 AV1 0.06 11 12 32 109 AV4 0.07 21 12 32 109 AV3
-0.11 11 12 32 110 AV2
-0.16 10 12 32 111 AV5 0.18 25 12 32 111 AV2 0.05 25 12 32 111 AV1 0.07 12 12 32 112 AV5 0.3 9
12 33 14 AV1
-0.69 9
12 33 108 AV5 0.11 21 12 33 108 AV3 0.02 22 12 34 110 AV4
-0.15 8
Page 12 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 35 108 AV5 0.02 9
12 35 108 AV3
-0.14 10 12 35 108 AV2
-0.18 11 12 35 110 AV6 0.04 10 12 36 15 AV6
-0.11 9
12 36 15 AV4 0.21 23 12 36 15 AV3 0.26 19 12 36 15 AV2
-0.05 12 12 36 110 AV3 0.11 14 12 38 15 AV3
-0.53 9
12 38 51 AV3
-0.16 13 12 38 51 AV2 0.09 14 12 38 70 AV4 0.2 10 12 38 70 AV3 0.09 11 12 38 104 AV5 0.02 10 12 38 104 AV2 0.02 20 12 38 107 AV3 0.13 25 12 38 107 AV2 0.07 26 12 38 107 AV1 0.02 13 12 39 48 AV5 0.48 9
12 39 48 AV4 0.12 11 12 39 48 AV6 0.38 20 12 39 54 AV6 0.13 24 12 39 55 AV5
-0.07 9
12 39 65 AV4 0.02 16 12 39 65 AV3 0.01 27 12 39 65 AV2 0.11 16 12 39 72 AV5
-0.01 16 12 39 72 AV4
-0.14 11 12 39 72 AV3 0.02 12 12 39 73 AV6
-0.15 21 12 39 73 AV5 0.29 21 12 39 73 AV4
-0.29 16 12 39 73 AV3
-0.48 27 12 39 73 AV2
-0.25 14 12 39 73 AV1
-0.15 18 12 39 75 AV1
-0.02 11 12 39 76 AV3
-0.18 12 12 39 96 AV5
-0.07 14 Page 13 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 39 96 AV4
-0.18 9
12 39 96 AV2
-0.15 12 12 39 98 AV6 0.05 9
12 39 100 AV5 0.04 11 12 39 107 AV4
-0.13 8
12 39 107 AV1 0.33 9
12 40 24 AV5 0.18 19 12 40 24 AV4 0.2 18 12 40 24 AV3 0.18 10 12 40 24 AV2 0.27 15 12 40 27 AV5 0.07 9
12 40 30 AV2 0.16 13 12 40 67 AV1
-0.07 10 12 40 69 AV2 0.01 16 12 40 75 AV1
-0.11 13 12 40 78 AV4 0.02 11 12 40 79 AV1 0.01 6
12 40 80 AV6 0.16 11 12 40 80 AV5 0.04 12 12 40 80 AV4 0.01 23 12 40 80 AV3 0.16 25 12 40 80 AV2 0.01 23 12 40 83 AV6 0.18 25 12 40 83 AV5
-0.05 32 12 40 83 AV4 0.15 27 12 40 83 AV3 0.1 31 12 40 83 AV2 0.21 29 12 40 83 AV1
-0.08 12 12 40 84 AV4
-0.07 13 12 40 85 AV1
-0.16 7
12 40 87 AV5 0.17 22 12 40 87 AV4
-0.02 16 12 40 87 AV3 0.21 20 12 40 87 AV2 0.23 21 12 40 87 AV1 0.21 12 12 40 88 AV5
-0.22 20 12 40 88 AV4 0.09 12 12 40 88 AV3 0.09 27 12 40 88 AV2
-0.22 19 Page 14 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 40 88 AV1 0.09 26 12 40 94 AV6
-0.14 17 12 40 94 AV5
-0.02 18 12 40 94 AV4
-0.22 17 12 40 94 AV3 0.2 28 12 40 94 AV2 0.05 22 12 40 94 AV1 0.02 9
12 40 95 AV6 0.07 8
12 40 95 AV5 0.16 25 12 40 95 AV4 0.05 17 12 40 95 AV3 0.02 18 12 40 95 AV2 0.05 31 12 40 95 AV1
-0.24 20 12 40 96 AV2 0.21 18 12 41 29 AV5
-0.17 12 12 41 29 AV4
-0.04 10 12 41 29 AV3 0.14 10 12 41 42 AV4
-0.22 9
12 41 56 AV3
-0.24 27 12 41 56 AV2
-0.24 19 12 41 82 AV3
-0.11 9
12 41 82 AV2 0.11 10 12 41 82 AV1
-0.29 18 12 41 83 AV4 0.07 8
12 41 83 AV2 0.2 10 12 41 85 AV4 0.13 17 12 41 85 AV3 0.22 24 12 41 85 AV2 0.02 15 12 41 85 AV1
-0.02 10 12 41 87 AV6 0.27 16 12 41 87 AV6
-0.1 11 12 41 87 AV5 0.02 31 12 41 87 AV4
-0.18 29 12 41 87 AV3 0.11 17 12 41 90 AV5 0.02 18 12 41 90 AV4 0.02 10 12 41 90 AV3 0.04 10 12 41 90 AV2 0.02 22 12 41 90 AV1 0.07 17 Page 15 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 41 93 AV4 0.1 17 12 41 93 AV2 0.04 8
12 41 94 AV5
-0.09 14 12 41 94 AV3 0.07 9
12 41 95 AV6 0.04 9
12 41 97 AV6 0.07 15 12 41 97 AV5
-0.09 13 12 41 97 AV4 0.15 22 12 41 97 AV3
-0.15 22 12 41 97 AV2 0.2 13 12 41 98 AV6
-0.15 22 12 41 98 AV5 0.11 17 12 41 98 AV4
-0.18 15 12 41 98 AV3
-0.15 19 12 41 98 AV2 0.02 27 12 41 99 AV4 0.02 9
12 41 100 AV6 0.15 10 12 41 100 AV3 0.05 25 12 41 100 AV2
-0.25 28 12 41 100 AV1
-0.04 17 12 41 101 AV6 0.2 31 12 41 101 AV5 0.13 32 12 41 101 AV4 0.15 11 12 41 101 AV3 0.04 11 12 41 101 AV2 0.2 29 12 41 101 AV1 0.22 18 12 41 102 AV6 0.02 10 12 41 102 AV5 0.07 20 12 41 102 AV4
-0.18 12 12 41 104 AV6 0.04 10 12 41 104 AV1
-0.11 10 12 41 105 AV2
-0.05 8
12 41 105 AV1 0.45 8
12 42 24 AV1 0.09 11 12 42 46 AV5
-0.2 25 12 42 51 AV6 0.11 21 12 42 51 AV4
-0.24 15 12 42 63 AV2
-0.31 10 12 42 100 AV3 0.16 12 Page 16 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 42 100 AV2 0.21 13 12 42 104 AV6
-0.02 9
12 43 27 AV2
-0.13 17 12 43 27 AV3 0.04 11 12 43 27 AV4 0.02 11 12 43 40 AV3 0.24 27 12 43 40 AV2 0.35 23 12 43 97 AV2 0.21 10 12 43 101 AV1
-0.04 9
12 44 26 AV6
-0.16 12 12 44 100 AV2
-0.2 12 12 45 23 AV5 0.02 12 12 45 67 AV1
-0.07 18 12 45 100 AV4
-0.09 10 12 45 100 AV2 0.02 9
12 46 80 AV2 0.01 9
12 46 91 AV5 0.07 11 12 46 91 AV4
-0.18 17 12 46 97 AV5 0.04 23 12 46 97 AV4 0.07 7
12 47 24 AV6 0.02 12 12 47 24 AV5 0.09 12 12 47 24 AV3 0.02 11 12 47 24 AV1 0.2 7
12 47 67 AV2 0.04 8
12 47 87 AV6 0.09 9
12 47 95 AV5 0.1 13 12 47 95 AV4 0.16 15 12 47 95 AV3 0.25 12 12 47 95 AV2 0.02 10 12 47 98 AV6 0.04 15 12 47 98 AV5 0.02 16 12 48 26 AV6
-0.11 11 12 48 79 AV3 0.11 12 12 48 79 AV2 0.01 15 12 48 79 AV1
-0.09 12 12 48 83 AV2
-0.18 16 12 48 86 AV2
-0.18 14 12 48 91 AV3 0.05 14 Page 17 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 48 91 AV2
-0.16 14 12 48 96 AV1
-0.04 10 12 48 98 AV4 0.02 18 12 49 35 AV3
-0.04 11 12 49 60 AV2
-0.15 11 12 49 95 AV6
-0.15 14 12 49 95 AV5 0.05 15 12 49 95 AV4
-0.2 11 12 49 96 AV5
-0.2 26 12 49 96 AV4
-0.33 11 12 49 96 AV6
-0.15 10 12 50 93 AV6
-0.17 10 12 50 95 AV1 0.07 11 12 51 67 AV2 0.01 14 12 51 67 AV1
-0.02 17 12 51 82 AV1
-0.17 21 12 51 85 AV2 0.05 8
12 52 32 AV3 0.02 11 12 52 62 AV2
-0.18 11 12 52 80 AV2 0.02 25 12 52 80 AV1
-0.07 19 12 52 80 AV3 0.02 12 12 52 89 AV5
-0.13 13 12 52 90 AV2 0.09 10 12 52 91 AV1 0.22 11 12 53 33 AV3 0.1 11 12 53 34 AV6 0.04 13 12 53 90 AV1
-0.15 9
12 53 90 AV5
-0.15 10 12 54 35 AV6
-0.16 15 12 54 38 AV4 0.04 11 12 54 38 AV2
-0.04 9
12 54 88 AV1 0.07 12 12 55 83 AV1 0.01 12 12 56 41 AV6 0.11 12 12 56 41 AV2 0.11 11 12 56 42 AV6 0.02 10 12 56 77 AV4
-0.28 12 12 57 44 AV6 0.02 13 Page 18 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 57 44 AV4
-0.09 13 12 57 46 AV1 0.02 11 12 57 53 AV2
-0.09 13 12 57 54 AV1
-0.11 12 12 57 79 AV1 0.04 12 12 58 52 AV6 0.04 14 12 58 52 AV3
-0.02 10 12 58 58 AV6 0.07 12 12 58 60 AV1
-0.16 9
12 58 72 AV6 0.01 11 13 12 2
AV6
-0.39 12 13 12 121 AV1 0.19 11 13 13 78 AV6
-0.31 9
13 15 67 AV1 0.12 10 13 15 67 AV6 0.19 15 13 15 101 AV1 0.32 10 13 16 72 AV1 0.26 8
13 19 53 AV1 0.02 13 13 19 78 AV1 0.14 12 13 19 80 AV1
-0.54 13 13 19 80 AV6
-0.04 27 13 20 81 AV2 0.62 9
13 21 116 AV1
-0.04 6
13 21 118 AV6 0.16 8
13 21 118 AV1 0.23 11 13 22 5
AV6
-0.24 20 13 22 117 AV1 0.55 10 13 23 112 AV1
-0.14 10 13 23 116 AV1 0.18 15 13 23 117 AV1 0.58 21 13 24 6
AV1
-0.25 16 13 24 6
AV1 0.44 10 13 24 6
AV6
-0.05 7
13 24 7
AV1 0.31 13 13 24 7
AV6
-0.28 17 13 24 8
AV1
-0.11 12 13 24 53 AV2 0.36 18 13 24 112 AV1
-0.08 14 13 24 113 AV6 0.12 9
Page 19 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 24 116 AV1 0.26 9
13 25 7
AV1
-0.16 17 13 25 7
AV1 0.15 10 13 25 7
AV6 0.09 24 13 25 9
AV2 0.17 9
13 25 31 AV2
-0.2 14 13 25 36 AV2 0.09 13 13 25 36 AVS
-0.02 10 13 25 38 AV2 0.11 17 13 25 115 AV6
-0.17 15 13 26 43 AV1 0.15 17 13 26 43 AV2 0.35 17 13 26 43 AVS 0.23 15 13 26 43 AV6 0.3 12 13 26 80 AV2 0.4 13 13 26 80 AVS 0.3 9
13 26 111 AVS
-0.07 9
13 26 111 AV6 0.14 9
13 26 115 AV1 0.28 10 13 26 115 AV6
-0.15 8
13 26 116 AV6
-0.47 8
13 27 10 AV1 0.05 10 13 27 10 AVS 0.21 12 13 27 11 AV2 0.12 14 13 27 11 AV6
-0.16 11 13 27 12 AV6
-0.07 10 13 27 103 AV2 0.12 8
13 28 52 AV2
-0.14 12 13 28 108 AV1 0.07 13 13 28 108 AV2 0.29 9
13 28 109 AV1
-0.02 9
13 29 80 AV2
-0.1 14 13 29 99 AV2 0.1 9
13 30 11 AV6 0.25 14 13 30 46 AV2 0.37 22 13 30 47 AV1
-0.2 11 13 30 47 AV2
-0.16 16 13 30 47 AVS 0.21 11 13 30 66 AV2 0.14 9
Page 20 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 31 10 AV5 0.21 10 13 31 32 AV2
-0.15 9
13 31 32 AV5
-0.18 19 13 31 55 AV2 0.09 10 13 31 61 AV5 0.15 8
13 31 104 AV5 0.02 11 13 32 14 AV6 0.18 14 13 32 15 AV2
-0.11 25 13 32 16 AV2 0.24 23 13 32 16 AV5 0.13 11 13 32 19 AV2
-0.08 11 13 32 48 AV2
-0.16 15 13 32 61 AV1 0.61 17 13 32 80 AV3 0.18 12 13 32 101 AV5 0.18 9
13 32 103 AV2
-0.02 10 13 32 108 AV5 0.11 12 13 33 15 AV2
-0.05 13 13 33 15 AV4
-0.2 12 13 33 15 AV5 0.09 13 13 33 111 AV6 0.14 13 13 34 48 AV1 0.33 22 13 34 48 AV2 0.21 14 13 34 48 AV3 0.16 10 13 34 48 AV4
-0.25 27 13 34 48 AV5 0.02 14 13 34 48 AV6
-0.2 9
13 34 111 AV1
-0.14 20 13 34 111 AV5 0.29 17 13 34 111 AV6
-0.16 11 13 35 81 AV4
-0.09 15 13 36 14 AV6
-0.27 7
13 36 43 AV2
-0.09 14 13 36 43 AV4 0.09 12 13 36 43 AV5 0.22 12 13 36 43 AV6
-0.22 10 13 36 80 AV3
-0.13 31 13 36 80 AV4
-0.19 19 13 36 80 AV5 0.2 17 Page 21 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 36 87 AV1 0.07 9
13 36 87 AV2 0.07 20 13 36 87 AV3
-0.04 18 13 36 87 AV4 0.02 9
13 36 87 AV6
-0.05 20 13 36 88 AV1 0.2 12 13 36 88 AV2 0.14 17 13 36 88 AV3
-0.07 14 13 36 88 AV4 0.05 25 13 36 88 AV5 0.02 18 13 36 88 AV6
-0.05 19 13 36 89 AV2 0.18 16 13 36 89 AV3 0.14 14 13 36 89 AV4 0.02 19 13 36 89 AV5 0.13 14 13 36 97 AV1 0.11 11 13 36 97 AV2 0.16 14 13 36 97 AV3 0.18 18 13 36 97 AV5 0.13 13 13 36 110 AV6 0.02 16 13 37 60 AV4 0.11 14 13 38 15 AV4
-0.23 10 13 38 26 AV2 0.14 12 13 38 26 AV3
-0.21 13 13 38 28 AV2 0.23 15 13 38 28 AV3 0.16 17 13 38 28 AV4 0.09 12 13 38 28 AV6
-0.07 8
13 38 53 AV1 0.02 12 13 I
38 53 AV2
-0.16 29 13 38 53 AV3
-0.07 14 13 38 53 AV4
-0.13 17 13 38 53 AV5 0.43 20 13 38 58 AV5
-0.16 18 13 38 58 AV6 0.1 14 13 38 63 AV2
-0.53 10 13 38 63 AV3 0.22 10 13 38 63 AV4 0.11 11 13 38 63 AV5
-0.11 13 Page 22 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 38 67 AV3
-0.41 16 13 38 67 AV4
-0.11 12 13 38 67 AV6 0.09 10 13 38 69 AV2 0.05 16 13 38 69 AV3
-0.02 10 13 38 72 AV2 0.21 27 13 38 72 AV3 0.15 24 13 38 72 AV4 0.23 28 13 38 72 AV5 0.16 11 13 38 73 AV2
-0.12 8
13 38 73 AV3
-0.29 10 13 38 81 AV5
-0.12 14 13 38 81 AV6 0.13 14 13 38 82 AV3 0.29 14 13 38 83 AV2 0.13 12 13 38 83 AV3
-0.13 23 13 38 83 AV4
-0.09 17 13 38 83 AV5 0.34 24 13 38 85 AV1 0.02 10 13 38 85 AV3 0.02 14 13 38 85 AV4 0.23 18 13 38 85 AV5 0.16 11 13 38 88 AV2 0.04 10 13 38 88 AV3 0.04 18 13 38 88 AV4 0.05 9
13 38 91 AV2 0.13 18 13 38 91 AV3 0.15 14 13 38 91 AV4 0.05 15 13 38 91 AV5
-0.12 25 13 38 91 AV6 0.07 16 13 38 92 AV2 0.22 17 13 38 92 AV4
-0.14 19 13 38 92 AV5 0.2 20 13 38 98 AV2 0.22 20 13 38 98 AV3 0.02 21 13 38 98 AV5 0.16 13 13 38 98 AV6 0.17 17 13 38 101 AV3
-0.19 10 13 38 101 AV5 0.25 16 Page 23 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 39 16 AV1 0.39 7
13 39 16 AV6
-0.52 10 13 39 20 AV5
-0.07 16 13 39 22 AV2
-0.07 15 13 39 22 AV3 0.11 15 13 39 22 AV4
-0.16 11 13 39 22 AV5 0.2 12 13 39 23 AV5
-0.02 10 13 39 35 AV2
-0.09 11 13 39 35 AV3 0.16 16 13 39 35 AV5 0.29 24 13 39 38 AV1
-0.15 13 13 39 38 AV2 0.16 20 13 39 38 AV3
-0.16 24 13 39 38 AV5
-0.21 23 13 39 38 AV6
-0.11 14 13 39 46 AV2
-0.27 16 13 39 53 AV3
-0.09 11 13 39 53 AV4
-0.07 11 13 39 54 AV3 0.22 22 13 39 54 AV4 0.2 20 13 39 54 AV5
-0.16 8
13 39 54 AV6 0.4 8
13 39 64 AV2
-0.27 8
13 39 64 AV3 0.02 13 13 39 65 AV1 0.2 14 13 39 65 AV2
-0.22 25 13 39 65 AV4
-0.09 16 13 39 65 AV5
-0.21 12 13 39 65 AV3
-0.07 9
13 39 65 AV3 0.2 9
13 39 80 AV2
-0.16 21 13 39 80 AV3 0.25 13 13 39 80 AV4 0.11 13 13 39 80 AV5
-0.11 12 13 39 80 AV6 0.05 10 13 39 87 AV5 0.25 14 13 39 87 AV6 0.18 15 13 39 100 AV5
-0.05 10 Page 24 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 40 19 AV3
-0.21 14 13 40 57 AV2
-0.09 11 13 40 100 AV4
-0.11 7
13 40 100 AV5 0.02 18 13 41 31 AV4
-0.02 22 13 41 31 AV5
-0.22 19 13 41 33 AV2 0.19 13 13 41 33 AV3 0.2 15 13 41 66 AV4 0.15 7
13 41 79 AV2
-0.09 8
13 41 79 AV5 0.18 8
13 41 96 AV2
-0.09 13 13 41 96 AV3 0.18 23 13 41 105 AV2 0.2 16 13 42 19 AV3 0.16 9
13 42 19 AV4 0.12 8
13 42 38 AV2 0.12 13 13 42 38 AV3
-0.23 23 13 42 38 AV4
-0.2 28 13 42 38 AV5 0.38 17 13 42 38 AV6
-0.04 14 13 42 46 AV2 0.36 6
13 42 53 AV1
-0.02 8
13 42 53 AV4
-0.12 9
13 42 98 AV4 0.18 12 13 42 100 AV6
-0.06 15 13 42 103 AV5 0.15 13 13 42 104 AV1 0.36 12 13 42 104 AV2 0.16 14 13 43 23 AV3 0.16 13 13 43 47 AV3 0.04 9
13 43 56 AV2 0.16 7
13 43 57 AV4
-0.23 13 13 43 57 AV5 0.26 9
13 43 62 AV5
-0.04 15 13 43 62 AV6
-0.25 8
13 43 64 AV3 0.18 14 13 43 64 AV4 0.24 28 13 43 64 AV5
-0.02 8
Page 25 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 43 69 AV3 0.12 10 13 43 69 AV4 0.2 12 13 43 69 AV5 0.24 15 13 43 69 AV6
-0.18 10 13 43 71 AV2 0.07 10 13 43 71 AV5 0.22 12 13 43 72 AV4 0.19 13 13 43 72 AV5 0.18 10 13 43 72 AV6 0.2 21 13 43 73 AV3
-0.22 16 13 43 73 AV5 0.19 13 13 43 73 AV6 0.16 10 13 43 75 AV3 0.35 12 13 43 75 AV5 0.2 22 13 43 75 AV6 0.18 15 13 43 75 AV4 0.54 10 13 43 77 AV4
-0.18 9
13 43 77 AV5
-0.13 13 13 43 79 AV1
-0.15 9
13 43 80 AV1 0.11 12 13 43 80 AV2 0.21 24 13 43 80 AV3
-0.14 29 13 43 80 AV4
-0.04 27 13 43 80 AV5 0.24 24 13 43 81 AV1 0.18 7
13 43 81 AV2 0.22 24 13 43 81 AV3 0.48 15 13 43 81 AV4 0.21 12 13 43 81 AV5
-0.12 17 13 43 81 AV6
-0.18 27 13 43 83 AV1 0.22 11 13 43 85 AV2 0.32 16 13 43 87 AV1 0.09 13 13 43 91 AV3 0.22 16 13 43 91 AV4
-0.11 17 13 43 91 AV5
-0.02 14 13 43 93 AV2
-0.09 14 13 43 96 AV3 0.17 10 13 43 96 AV4 0.14 12 Page 26 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 43 96 AV6
-0.05 12 13 44 25 AV2
-0.12 13 13 44 25 AV3
-0.02 10 13 44 26 AV2
-0.02 17 13 44 26 AV3
-0.04 9
13 44 26 AV4
-0.02 9
13 44 59 AV2 0.2 13 13 44 59 AV3
-0.09 10 13 44 60 AV3
-0.1 17 13 44 67 AV5 0.18 10 13 44 68 AV1 0.21 25 13 44 68 AV2
-0.14 23 13 44 68 AV3 0.02 21 13 44 68 AV4 0.04 21 13 44 68 AV5 0.28 23 13 44 71 AV2 0.16 16 13 44 76 AV3
-0.51 19 13 44 77 AV2 0.01 12 13 44 77 AV3
-0.14 15 13 44 77 AV4 0.17 10 13 44 85 AV4
-0.38 7
13 44 91 AV5
-0.11 10 13 44 95 AV4 0.15 13 13 44 100 AV5 0.18 12 13 44 101 AV5 0.18 12 13 45 23 AV6
-0.36 9
13 45 64 AV6 0.3 6
13 45 66 AV2 0.02 9
13 45 66 AV1
-0.02 8
13 45 79 AV2 0.04 10 13 45 97 AV4
-0.11 22 13 45 97 AV6 0.2 20 13 45 100 AV2 0.2 14 13 45 100 AV4 0.07 10 13 46 24 AV5
-0.07 22 13 46 24 AV6 0.13 11 13 46 73 AV2
-0.36 21 13 46 73 AV3 0.35 12 13 46 77 AV4 0.17 8
Page 27 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 46 77 AVS
-0.06 9
13 47 25 AV4
-0.07 11 13 47 25 AVS 0.18 18 13 47 25 AV6
-0.04 15 13 47 26 AVS 0.09 10 13 47 26 AV6 0.09 14 13 47 97 AV6 0.13 15 13 48 25 AV2
-0.13 18 13 48 25 AV4
-0.23 9
13 48 41 AV2 0.09 9
13 48 94 AV2 0.13 11 13 48 95 AV3 0.14 14 13 48 98 AV6
-0.16 13 13 49 27 AV1 0.44 10 13 49 27 AV6
-0.09 9
13 49 32 AV4
-0.05 12 13 49 32 AVS
-0.16 11 13 49 53 AVS 0.22 13 13 49 57 AV6
-0.09 10 13 49 92 AV4 0.17 13 13 49 93 AVS 0.13 10 13 49 93 AV6 0.07 14 13 49 94 AVS 0.2 20 13 49 94 AV6 0.15 31 13 49 95 AV4 0.13 23 13 so 56 AV1 0.7 8
13 so 87 AVS 0.13 11 13 so 93 AVS 0.15 30 13 so 94 AV1 0.2 24 13 so 94 AV2 0.2 31 13 so 94 AV6
-0.07 14 13 51 so AV4
-0.18 16 13 51 so AVS
-0.04 17 13 51 so AV6
-0.02 17 13 51 55 AV4
-0.02 11 13 51 55 AVS
-0.1 26 13 51 55 AV6
-0.12 15 13 51 57 AVS 0.2 9
13 51 79 AV1
-0.13 9
Page 28 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 51 79 AV2 0.11 12 13 51 91 AV3 0.15 15 13 51 91 AV4 0.02 28 13 51 91 AV5
-0.14 12 13 51 92 AV2
-0.14 16 13 51 92 AV4 0.16 17 13 51 92 AV5
-0.18 30 13 52 32 AV3 0.04 8
13 52 34 AV5
-0.03 6
13 52 34 AV6
-0.02 18 13 52 89 AV1
-0.04 12 13 52 89 AV2 0.2 26 13 52 89 AV3
-0.11 25 13 52 89 AV5 0.15 19 13 52 89 AV6 0.19 12 13 53 57 AV1
-0.39 12 13 53 57 AV2 0.14 14 13 53 57 AV3 0.17 22 13 53 57 AV4 0.18 16 13 53 58 AV2
-0.06 13 13 53 69 AV2 0.1 10 13 53 72 AV4 0.22 21 13 53 72 AV5 0.17 10 13 53 88 AV4 0.24 16 13 53 88 AV5 0.22 24 13 53 89 AV4 0.2 10 13 53 89 AV5 0.13 20 13 53 89 AV6
-0.09 14 13 54 36 AV5 0.02 12 13 54 37 AV2
-0.04 10 13 54 37 AV3
-0.14 21 13 54 37 AV4
-0.14 22 13 54 37 AV5
-0.14 16 13 54 37 AV6 0.18 9
13 54 38 AV2 0.04 11 13 54 43 AV4 0.2 14 13 54 71 AV5
-0.04 13 13 54 72 AV2
-0.05 12 13 54 72 AV5
-0.01 20 Page 29 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 54 72 AV6
-0.02 15 13 54 76 AV1 0.14 13 13 54 85 AV2
-0.23 11 13 54 86 AV1 0.11 9
13 54 86 AV3 0.16 12 13 54 88 AV4 0.07 12 13 55 56 AV2 0.16 11 13 55 56 AV5 0.11 11 13 55 83 AV1 0.02 11 13 55 83 AV3 0.04 10 13 55 83 AV4
-0.04 7
13 55 84 AV4
-0.09 12 13 55 84 AV5 0.13 13 13 56 41 AV2 0.11 11 13 56 42 AV2 0.06 11 13 56 66 AV3 0.02 9
13 56 81 AV6 0.11 8
13 57 72 AV5 0.11 9
13 57 73 AV3
-0.13 8
13 57 73 AV5
-0.09 11 13 57 78 AV1 0.14 9
13 57 78 AV2 0.15 10 13 57 78 AV6
-0.14 9
13 57 79 AV2
-0.05 9
13 57 79 AV6
-0.02 12 13 58 52 AV6 0.1 14 13 58 55 AV1
-0.18 13 13 58 67 AV1
-0.05 7
13 58 73 AV6 0.02 13 13 58 75 AV2
-0.11 8
13 58 75 AV3 0.07 16 13 58 76 AV3 0.18 10 13 58 76 AV5 0.22 11 13 58 76 AV6 0.19 10 13 59 61 AV1
-0.27 10 13 59 61 AV6 0.23 11 13 59 66 AV6 0.15 12 14 16 60 AV6
+0.07 12 14 16 91 AV6
-0.14 10 Page 30 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 20 5
AV1
-0.49 10 14 21 7
AV1
-0.14 11 14 23 6
AV1
+0.64 16 14 24 6
AV1
+0.02 22 14 24 7
AV6
-0.28 12 14 24 7
AV1
-0.23 11 14 24 8
AV1
-0.23 18 14 24 116 AV1
-0.16 27 14 24 116 AV6
+0.50 17 14 24 117 AV6
+0.54 6
14 25 7
AV1
-0.04 17 14 25 7
AV6
-0.36 20 14 25 8
AV1
-0.30 32 14 25 9
AV5
+0.12 12 14 25 26 AV6
-0.07 7
14 25 35 AV6
-0.38 11 14 25 36 AV6
-0.35 19 14 25 44 AV5
+0.21 20 14 25 88 AV5
-0.16 11 14 25 89 AV2
+0.14 9
14 25 109 AV6
+0.18 13 14 25 115 AV6
+0.18 22 14 26 7
AV6
-0.10 15 14 26 7
AV1
-0.07 23 14 26 84 AV5
-0.02 10 14 26 109 AV5
+0.11 11 14 26 113 AV5
+0.04 12 14 26 114 AV2
-0.19 12 14 26 115 AV1
+0.21 30 14 26 115 AV5
+0.02 14 14 26 115 AV6
+0.09 17 14 26 116 AV1
-0.16 15 14 26 116 AV6
+0.68 11 14 27 8
AV6
+0.09 13 14 27 8
AV6
-0.27 16 14 27 8
AV1
+0.27 15 14 27 8
AV1
-0.21 28 14 27 79 AV6
+0.11 15 14 27 79 AV5
+0.05 25 Page 31 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 27 79 AV2
+0.13 23 14 27 114 AV2
-0.21 17 14 28 9
AV5
-0.35 27 14 28 9
AV2
+0.31 26 14 28 9
AV6
+0.22 13 14 28 12 AV6
+0.09 14 14 28 14 AV6
+0.05 12 14 28 38 AV5
+0.22 16 14 28 38 AV2
+0.23 21 14 28 81 AV5
+0.04 14 14 28 109 AV1
+0.14 12 14 28 111 AV5
+0.02 11 14 28 111 AV2
+0.18 13 14 28 113 AV6
+0.07 10 14 28 113 AV5
+0.13 18 14 28 113 AV2
-0.26 13 14 29 11 AV6
-0.05 12 14 29 109 AV6
-0.18 13 14 29 109 AV2
-0.07 11 14 29 110 AV5
-0.18 17 14 29 110 AV2
+0.02 12 14 29 110 AV1
-0.16 9
14 29 111 AV5
-0.19 18 14 29 111 AV1
+0.02 12 14 30 14 AV6
+0.12 9
14 30 18 AV6
-0.18 9
14 30 67 AV5
+0.11 16 14 30 72 AV6
+0.02 11 14 30 72 AV2
+0.09 20 14 30 76 AV5
-0.33 14 14 30 107 AV1
+0.05 9
14 30 107 AV5
+0.16 16 14 30 109 AV6
-0.07 8
14 30 111 AV2
+0.02 15 14 30 114 AV2
-0.59 10 14 31 11 AV6
-0.11 19 14 32 12 AV5
+0.07 25 14 32 12 AV4
-0.02 21 14 32 84 AV3
-0.39 10 Page 32 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 32 84 AV2
+0.11 22 14 32 84 AV5
-0.20 20 14 32 109 AV2
+0.05 15 14 32 112 AV5
+0.51 9
14 33 12 AV6
+0.16 20 14 33 12 AV5
+0.14 23 14 33 12 AV2
+0.15 24 14 33 12 AV1
-0.06 14 14 34 91 AV4
+0.02 9
14 34 108 AV1
+0.04 7
14 34 108 AV2
+0.02 10 14 34 108 AV3
+0.09 18 14 34 108 AV4
-0.13 23 14 34 108 AV6
-0.15 10 14 34 111 AV6
+0.30 9
14 34 111 AV2
-0.67 12 14 37 102 AV5
+0.07 7
14 37 103 AV5
+0.05 13 14 38 21 AV5
+0.02 12 14 38 21 AV2
+0.08 9
14 38 32 AV4
-0.16 10 14 38 32 AV3
+0.16 13 14 38 92 AV3
+0.11 10 14 38 99 AV5
-0.20 15 14 38 101 AV2
+0.16 15 14 38 101 AV3
+0.02 27 14 38 101 AV4
+0.02 23 14 38 101 AV5
+0.07 17 14 38 103 AV2
+0.09 15 14 38 103 AV4
+0.02 12 14 38 103 AV5
+0.02 10 14 38 104 AV4
-0.20 18 14 38 108 AV6
+0.18 10 14 38 108 AV3
-0.11 9
14 38 108 AV2
-0.39 12 14 38 108 AV5
+0.25 7
14 39 56 AV5
-0.22 16 14 39 56 AV4
+0.20 19 14 39 56 AV3
+0.08 23 Page 33 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 39 68 AV6
-0.36 22 14 39 68 AV5
+0.10 11 14 39 68 AV3
+0.11 22 14 39 68 AV2
+0.07 15 14 39 71 AV1
-0.21 10 14 39 77 AV4
-0.38 22 14 39 77 AV3
-0.25 19 14 39 77 AV2
-0.18 16 14 39 78 AV3
+0.33 8
14 39 78 AV2
-0.16 11 14 39 79 AV3
-0.27 16 14 39 81 AV2
-0.27 12 14 39 82 AV4
-0.11 9
14 39 82 AV3
+0.11 9
14 39 89 AV5
+0.02 8
14 39 89 AV4
-0.10 12 14 39 89 AV3
+0.16 12 14 39 95 AV3
+0.07 9
14 39 95 AV2
+0.04 10 14 39 96 AV1
-0.26 11 14 39 96 AV2
+0.20 23 14 39 96 AV3
+0.04 21 14 39 96 AV4
+0.02 15 14 39 97 AV3
+0.02 21 14 39 98 AV5
+0.02 12 14 39 98 AV3
-0.16 15 14 39 100 AV5
+0.04 11 14 39 100 AV4
-0.13 11 14 39 100 AV2
+0.04 20 14 39 100 AV3
+0.07 22 14 40 33 AV2
+0.12 11 14 40 48 AV6
-0.24 23 14 40 48 AV5
-0.19 23 14 40 48 AV4
-0.35 22 14 40 48 AV3
+0.14 18 14 40 48 AV2
+0.19 9
14 40 48 AV1
-0.21 24 14 40 58 AV4
-0.18 13 14 40 58 AV2
-0.28 17 Page 34 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 40 58 AV1
+0.04 11 14 40 60 AV6
+0.06 12 14 40 60 AV4
+0.35 12 14 40 60 AV4
-0.20 16 14 40 60 AV3
-0.30 18 14 40 60 AV2
-0.36 11 14 40 60 AV1
-0.18 15 14 40 66 AV4
+0.02 11 14 40 78 AVS
+0.17 11 14 40 78 AV4
-0.02 12 14 40 80 AV1
+0.07 8
14 40 80 AV2
+0.20 19 14 40 80 AV3
-0.24 18 14 40 80 AV4
-0.07 25 14 40 80 AV4
+0.34 11 14 40 80 AVS
-0.20 9
14 40 80 AVS
+0.24 26 14 40 80 AV6
-0.28 9
14 40 80 AV6
+0.11 18 14 40 87 AV6
+0.13 17 14 40 87 AVS
+0.20 28 14 40 87 AV4
+0.16 23 14 40 87 AV3
-0.16 26 14 40 87 AV2
+0.05 10 14 40 106 AV6
+0.11 13 14 40 106 AVS
+0.31 9
14 40 106 AV3
+0.13 11 14 40 106 AV1
+0.11 10 14 41 61 AV1
+0.04 10 14 41 100 AV3
+0.02 15 14 41 100 AVS
+0.02 12 14 41 105 AVS
+0.22 12 14 41 105 AV3
-0.04 11 14 41 105 AV1
-0.02 9
14 42 19 AV2
-0.53 11 14 42 19 AV1
+0.02 11 14 42 21 AV4
-0.14 12 14 42 21 AV3
+0.22 24 14 42 21 AV2
-0.11 11 Page 35 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 42 21 AV1
-0.10 11 14 42 30 AV4
+0.27 29 14 42 30 AV3
+0.17 23 14 42 30 AV2
+0.19 22 14 42 30 AV1
+0.11 8
14 42 30 AVS
+0.20 23 14 42 39 AV6
-0.04 10 14 42 39 AVS
-0.08 12 14 42 39 AV2
-0.15 11 14 42 39 AV3
-0.04 12 14 42 104 AV6
-0.07 11 14 42 104 AVS
+0.04 10 14 43 53 AVS
-0.33 27 14 43 53 AV4
+0.25 25 14 43 53 AV3
+0.08 34 14 43 53 AV2
+0.22 13 14 43 53 AV2
-0.11 18 14 43 53 AV1
-0.18 8
14 43 100 AV3
+0.02 6
14 43 103 AV3
-0.11 13 14 44 21 AVS
+0.20 9
14 44 so AV6
-0.04 10 14 44 102 AV6
-0.13 10 14 44 102 AV3
-0.11 13 14 44 102 AV2
-0.16 13 14 45 22 AVS
+0.06 12 14 45 22 AV4
+0.04 11 14 45 101 AVS
+0.13 8
14 45 101 AV6
-0.04 10 14 46 24 AV6
+0.06 12 14 46 29 AVS
-0.02 11 14 47 34 AV6
-0.02 11 14 47 43 AV4
+0.06 12 14 47 43 AV3
+0.06 17 14 47 43 AV2
+0.04 8
14 47 43 AV1
-0.10 9
14 47 57 AVS
+0.18 13 14 47 57 AV3
+0.16 14 14 47 57 AV2
+0.14 14 Page 36 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 47 57 AV6
+0.06 11 14 47 88 AV4
+0.07 12 14 48 26 AV2
-0.36 12 14 48 86 AV3
+0.13 10 14 48 97 AV6
-0.07 13 14 49 27 AVS
+0.02 13 14 49 27 AV3
-0.04 12 14 49 28 AVS
+0.01 12 14 49 95 AV3
+0.07 9
14 49 96 AV6
+0.15 17 14 so 28 AV6
-0.24 27 14 so 28 AVS
+0.15 19 14 so 93 AV6
-0.11 8
14 so 94 AV3
-0.04 16 14 so 95 AV2
-0.04 10 14 51 31 AV6
-0.30 13 14 51 31 AVS
-0.18 10 14 51 31 AV4
-0.06 12 14 51 92 AVS
-0.07 11 14 52 32 AVS
-0.06 13 14 52 32 AV4
-0.18 12 14 52 32 AV3
+0.14 12 14 52 34 AV6
-0.04 12 14 52 34 AVS
+0.02 13 14 52 34 AV4
-0.12 10 14 52 39 AV6
-0.18 12 14 52 88 AV3
-0.02 8
14 52 90 AV2
-0.07 10 14 52 91 AVS
-0.02 11 14 52 91 AV2
-0.02 11 14 53 33 AV3
+0.06 10 14 53 33 AVS
+0.25 23 14 53 33 AV4
-0.20 16 14 53 34 AV6
+0.18 14 14 53 34 AVS
-0.02 11 14 53 34 AV4
+0.20 13 14 53 35 AV6
-0.18 10 14 53 37 AV6
-0.10 9
14 53 38 AV6
-0.24 18 Page 37 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 53 38 AV4
-0.16 17 14 53 38 AVS
+0.01 11 14 53 38 AV3
+0.04 16 14 53 39 AV6
-0.14 7
14 53 71 AVS
-0.02 10 14 53 89 AV3
+0.02 9
14 53 90 AV6
+0.09 14 14 54 35 AV6
+0.11 13 14 54 35 AVS
-0.06 11 14 54 36 AV6
-0.22 10 14 54 37 AV4
+0.04 9
14 54 38 AV3
+0.09 12 14 54 47 AV6
+0.02 10 14 54 47 AVS
+0.02 12 14 54 56 AV6
-0.02 10 14 54 56 AV2
+0.04 9
14 54 56 AVS
-0.02 9
14 54 86 AV2
-0.09 15 14 54 87 AV6
+0.06 12 14 54 87 AV3
+0.04 9
14 54 87 AVS
+0.10 16 14 54 87 AV2
+0.13 11 14 55 42 AV6
-0.02 13 14 55 82 AV2
+0.02 11 14 55 83 AV6
+0.20 24 14 55 83 AV4
+0.17 12 14 55 83 AV2
+0.12 13 14 56 49 AV6
+0.04 8
14 56 so AV6
-0.02 12 14 56 57 AV6
+0.13 7
14 56 58 AV6
-0.02 13 14 56 71 AVS
-0.02 13 14 56 71 AV2
-0.11 10 14 56 81 AV1
-0.02 12 14 56 81 AV2
+0.02 11 14 56 81 AV3
-0.04 8
14 56 82 AV6
-0.02 8
14 56 82 AV2
+0.02 11 14 57 44 AV2
-0.09 12 Page 38 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 57 46 AV6
+0.08 13 14 57 46 AV3
+0.02 10 14 57 46 AV2
-0.19 15 14 57 61 AV6
+0.11 15 14 57 70 AV6
-0.30 11 14 57 70 AVS
-0.07 12 14 57 70 AV2
-0.07 11 14 57 72 AV6
-0.02 12 14 57 79 AV3
-0.02 11 14 57 79 AV2
+0.07 11 14 58 47 AVS
-0.02 12 14 58 so AV1
+0.06 11 14 58 52 AV6
+0.04 13 14 58 54 AV1
-0.06 12 14 58 57 AV6
+0.08 15 14 58 61 AV1
+0.04 10 14 58 63 AV2
-0.07 11 14 58 64 AV1
-0.07 11 14 58 64 AV6
-0.02 13 14 58 64 AV2
-0.13 11 14 58 65 AV6
-0.02 13 14 58 70 AV1
+0.02 10 14 58 72 AV1
-0.04 7
14 58 74 AV2
-0.13 11 14 58 74 AV1
-0.13 12 14 58 76 AV2
+0.12 14 14 59 55 AV6
+0.08 20 14 59 55 AV2
+0.40 16 14 59 55 AV1
-0.35 12 14 59 57 AV1
-0.52 12 14 59 59 AV3
-0.09 12 14 59 60 AV1
+0.13 11 14 59 63 AV6
+0.11 12 14 59 64 AV1
-0.04 13 Page 39 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (TSP WEAR)
SG Row Column Location
%TW 11 8
41 01H 6
11 47 24 03C 6
12 44 22 07C 4
12 53 33 03C 5
13 16 119 02C 6
13 20 5
02C 6
13 30 11 03C 10 13 53 85 01C 13 14 13 94 04H 5
14 17 119 02C 4
14 18 5
01C 5
14 18 5
02C 11 14 18 6
02C 6
14 26 116 02C 9
14 31 113 02C 10 14 33 111 02C 10 14 59 56 03C 8
Page 1 of 1 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (FBP WEAR)
SG Row Column Location 0/oTW 11 53 34 FBC 9
13 55 83 FBH 6
14 20 118 FBC 7
Page 1 of 1 LR-N 18-0054 SG 13 13 13 13 13 13 1 R25 SERVICE INDUCED INDICATIONS (FOREIGN OBJECT WEAR)
Axial Circumferential Row Column Location Length Extent (inches)
(Degrees) 2 91 03C -0.72 0.26 75 15 117 FBH +0.55 0.19 55 16 118 FBH +0.71 0.27 60 17 117 FBH +0.57 0.38 60 24 89 05C -0.78 0.23 55 55 53 TSC +0.19 0.29 60 Page 1 of 1 0/oTW 98 11 11 23 16 24
PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, NJ 08038-0236 PSEG NudeaTLLC Technical Specification 6.9.1.1 0 LR-N 18-0054 MAY 07 2018 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington DC 20555-001
Subject:
Salem Nuclear Generating Station Unit 1 Facility Operating License No. DPR-70 NRC Docket No. 50-272 Steam Generator Tube Inspection Report-Twenty-fifth Refueling Outage (1 R25)
PSEG Nuclear, LLC (PSEG) hereby submits the Steam Generator Tube Inspection Report consistent with the requirements of Technical Specification (TS) 6.9.1.1 0. The report is being submitted within 180 days after the initial entry into HOT SHUTDOWN following completion of the inspection performed in accordance with Technical Specification 6.8.4.i, "Steam Generator (SG) Program." Salem Unit 1 entered HOT SHUTDOWN (Mode 4) on November 7, 2017, following the completion of its twenty-fifth refueling outage.
The following attachments are included in this letter:
Steam Generator Tube Inspection Report TS 6.9.1.1 0 Salem Unit 1 Model F SG Tube Support Arrangement and Terminology 1 R25 Tubes Plugged For Each Degradation Mechanism Total Number and percentage of Tubes Plugged to Date 1 R25 Nondestructive Examination Techniques 1 R25 Service Induced Indications (AVB Wear) 1 R25 Service Induced Indications (TSP Wear) 1 R25 Service Induced Indications (FBP Wear) 1 R25 Service Induced Indications (Foreign Object Wear)
There are no commitments contained in this letter.
Should you have any questions regarding this submittal, please contact Mr. Harry Balian at (856) 339-2173.
Sincerely, Patrick Martino Plant Manager-Salem Attachments (9)
Page2 LR-N 18-0054 cc:
Mr. D. Lew, Administrator, Region I, NRC Mr. J. Kim, Project Manager, NRC NRC Senior Resident Inspector, Salem Mr. P. Mulligan, Manager IV, NJBNE Mr. L. Marabella, Corporate Commitment Tracking Coordinator Mr. T. Cachaza, Salem Commitment Tracking Coordinator Mr. M. Washington, Chief Inspector-Occupational Safety and Health Bureau of Boiler and Pressure Vessel Compliance
LR-N18-0054 Steam Generator Tube Inspection Report TS 6.9.1.10 LR-N 18-0054 INTRODUCTION STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10 PSEG Nuclear LLC Salem Unit 1 In 1998 Salem Unit 1 commenced operating cycle 13 with the newly replaced steam generators from the canceled Seabrook-2 plant. Salem Unit 1 is a four (4) loop Westinghouse Pressurized Water Reactor (PWR) with Model F SGs that incorporate thermally treated lnconel 600 U-tubes.
The tube bundle consists of 5,626 tubes with an outside diameter (00) of 0.688 inches and a nominal tube wall thickness of 0.040 inches. During SG fabrication, the tubes were hydraulically expanded over the full tubesheet depth and the first ten tube rows were thermally stress relieved after U-bend formation. The seven (7) tube support plates (TSP) are fabricated from 405 stainless steel (SS) and have broached "quatrefoil" tube holes. A flow distribution baffle (FOB) plate, also 405SS, between the secondary face of the tubesheet and the first tube support plate, provides top-of-tubesheet (TTS) sludge pile control. Tube support within the U-bend region is provided by three V-shaped chrome-plated lnconel 600 antivibration bars (AVB's). Attachment 2 provides a general summary of the Salem Unit 1 Model F SG Tube Support Arrangement and Terminology.
Consistent with Technical Specification (TS) 6.9.1.1 0, this report is being submitted within 180 days after the initial entry into HOT SHUTDOWN following completion of inspection performed in accordance with the Specification 6.8.4.i, "Steam Generator Program".
This report includes:
- a.
The scope of inspections performed on each SG,
- b.
Degradation mechanisms found,
- c.
Nondestructive examination techniques utilized for each degradation mechanism,
- d.
Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- e.
Number of tubes plugged during the inspection outage for each degradation mechanism,
- f.
The number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator,
- g.
The results of condition monitoring, including the results of tube pulls and in-situ testing.
- h.
The primary to secondary leakage rate observed in each SG (if it is not practical to assign the leakage to an individual SG, the entire primary to secondary leakage should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report,
- i.
The calculated accident induced leakage rate from the portion of the tubes below 15.21 inches from the top of the tubesheet for the most limiting accident in the most limiting SG.
In addition, if the calculated accident induced leakage rate from the most limiting accident is less than 2.16 times the maximum operational primary to secondary leakage rate, the report should describe how it was determined,
- j.
The results of monitoring for tube axial displacement (slippage).
If slippage is discovered, the implications of the discovery and corrective action shall be provided.
Page 1 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10 EXPLANATION OF TERMS 1 R25:
AVB:
BET:
BHT:
BLG:
CL:
CM:
DNG:
DNT:
EPRI:
ETL:
ETSS:
FBC:
FBH:
FBP:
FOB:
HL:
NDE:
OA:
00:
OEX:
OXP:
PLP:
PWR:
SG:
TEC:
TEH:
TS:
TSC:
TSH:
TTS:
TSP:
TW:
Vpp:
Unit 1 25th Refueling Outage Anti-Vibration Bar Bottom Expansion Transition (synonymous with BHT)
Bottom Hydraulic Transition (synonymous with BET)
Bulge (Expansion (Per PSEG reporting requirement, these typically occur within the hydraulically expanded tubesheet)
Cold Leg Condition Monitoring Ding (Freespan region of the tube per PSEG reporting requirements)
Dent (At support structures per PSEG reporting requirements)
Electric Power Research Institute Expansion Transition Location (PSEG reporting requirements)
Examination Technique Specification Sheet Flow Baffle Cold leg (designates the Flow Distribution Baffle Plate on the Cold Leg)
Flow Baffle Hotleg (designates the Flow Distribution Baffle Plate on the Hot leg)
Flow Distribution Baffle Plate (synonymous with FOB)
Flow Distribution Baffle Plate (synonymous with FBP)
Hot Leg Non Destructive Examination Operational Assessment Outside Diameter Over Expansion (a localized variation in tube diameter within the hydraulically expandedtubesheeQ Over Expansion (hydraulic expansion occurring above the top of tubesheet)
Possible Loose Part Pressurized Water Reactor Steam Generator Tube End Coldleg Tube End Hotleg Technical Specification Tubesheet Cold Leg Tubesheet Hot Leg Top of Tubesheet Tube Support Plate Through-Wall Volts Peak to Peak SG inspections were performed in accordance with TS 6.8.4.i, "Steam Generator Program",
during Salem Unit 1 Outage 1 R25. Each reporting requirement of TS 6.9.1.1 0 is addressed below (items a through j).
Page 2 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10
- a. Technical Specification 6.9.1.1 O.a, "The scope of inspections performed on each SG" If not stated otherwise, the following inspections were performed on all four steam generators:
Bobbin Probe
- 1. A full-length (tube end to tube end) bobbin coil probe inspection was performed on 1 00°/o of the in-service tubes.
Array Probe (X-Probe)
- 1. 1 00°/o of the first 3 outer periphery tubes on both TTS hot leg (HL) and cold leg (CL); and the first 3 rows of no-tube lane on the HL and CL (SG 13 included 100% of all tubes on HL and CL). Inspection extent from TSH -15.21" (i.e.- 15.21 inches below the TTS) to the first tube support above the TTS (i.e. - 01 H), and TSC -2" to the first tube support above the TTS (i.e. - 01 C).
- 2. 50% HL TTS Expansion Transitions, TSH +3" to -15.21"
- 3. 100°/o OXP, ETL, BHT >= 0 or BHT <= -0.40 inches, TSH +3" to -15.21" and TSC +3" to
-2"
- 4. 50% HL BLG >= 18 volts and OEX > 0.25 inches, TSH +3" to -15.21"
- 5. Special Interest Inspections, including bounding locations with possible loose parts identified by eddy current or secondary side inspections.
Rotating Probe (+Point)
- 1. 50% HL DNT and DNG > 2 volts as reported from 1 R24, TSH to 07H (Includes 50°/o of the DNT and DNG > 5 volts)
- 2. 20% CL DNT and DNG > 5 volts as reported from 1 R24, TSC to 07C
- 3. 20% U-bend DNT and DNG > 2 volts, as reported from 1 R24, 07H to 07C (Includes 20%
of the DNT and DNG > 5 volts)
- 4. 20% Row 1 and Row 2 tubes, 07H to 07C
- 6. 1 00°/o of the HL FBP and TSP intersections, FBH to 07H, of the tubes screened for possible higher stress (i.e. - 2 Sigma Tubes).
- 7. Special Interest Inspections, including Bobbin "I" codes and sizing locations with foreign object wear.
- b. Technical Specification 6.9.1.1 O.b, "Degradation mechanisms found" The tube degradation mechanisms found during outage 1 R25 are AVB wear, TSP wear, FBP wear, and Foreign Object wear (Also referred to as Loose Part Wear).
- c. Technical Specification 6.9.1.1 O.c, "Nondestructive examination techniques utilized for each degradation mechanism" Page 3 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10 provides the Nondestructive examination techniques utilized for each degradation mechanism.
- d. Technical Specification 6.9.1.1 O.d, "Location, orientation (if linear), and measured sizes (if available) of service induced indications" The service induced indications detected during outage 1 R25 are AVB wear, TSP wear, FBP wear, and Foreign Object wear.
Attachments 6, 7, 8, and 9 provide information for the service induced indications. The TW sizing provided in Attachments 6, 7, and 8 is from EPRI ETSS 96041.1, 96004.1, and 96042.1; respectively. The TW sizing provided in Attachment 9 is from EPRI ETSS 27901.1 or 27902.1.
- e. Technical Specification 6.9.1.1 O.e, "Number of tubes plugged during the inspection outage for each degradation mechanism" provides the number of tubes plugged during the inspection outage for each degradation mechanism.
- f. Technical Specification 6.9.1.10.f, "Total number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator" provides the total number and percentage of tubes plugged to date in each steam generator. The plugging percentage and the effective plugging percentage are the same.
- g. Technical Specification 6.9.1.1 O.g, "The results of condition monitoring, including the results of tube pulls and in-situ testing" The largest depth of degradation detected during 1 R25 for AVB wear was 34°/o TW, TSP wear was 13°/o TW, FBP wear was 9°/o TW, and Foreign Object wear was 97% TW (reference response to 6.9.1.1 O.d for further details). The Foreign Object wear indication, in SG 13 Tube Row 2 Column 91 near TSP 03C, was identified as the tube responsible for primary to secondary side leakage initially identified in May 2017 (Also see NRC ML17332A603). This tube was full length in-situ pressure tested. All tubes eddy current inspected or in-situ pressure tested met the tube integrity performance criteria in TS 6.8.4.i.b. No tube pulls were required.
All tubes with detected foreign object wear were plugged (see response to 6.9.1.1 O.e and ).
Page 4 of 5 LR-N18-0054 STEAM GENERATOR TUBE INSPECTION REPORT TS 6.9.1.10
- h. Technical Specification 6.9.1.1 O.h, "The primary to secondary leakage rate observed in each SG (if it is not practical to assign the leakage to an individual SG, the entire primary to secondary leakage should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report" On Monday May 15, 2017 at approximately 1800, operators in the Salem Unit 1 Control Room identified a rise in the primary-to-secondary leakage from radiation monitor indications. The small leak was identified in SG 13, and went below detection around May 28, 2017. Primary to secondary leak trend information provided in NRC ML17332A603 includes chemistry grab sample results for the duration of the leak event, up to the start of outage 1 R25 (October 12, 2017). Subsequent to May 28, 2017, the leak remained below detection.
- i. Technical Specification 6.9.1.1 O.i, "The calculated accident induced leakage rate from the portion of the tubes below 15.21 inches from the top of the tubesheet for the most limiting accident in the most limiting SG. In addition, if the calculated accident induced leakage rate from the most limiting accident is less than 2.16 times the maximum operational primary to secondary leakage rate, the report should describe how it was determined" Response to item h above provides SG 13 experienced an operational primary to secondary leak. The source of this leak was not associated the tubesheet (See response to 6.9.1.1 O.g).
PSEG did not observe any primary to secondary operational leakage, associated with the tubesheet, at or greater than the detection threshold of approximately one (1) gallon per day over the cycle preceding the inspection in any of the steam generators at Salem Unit 1.
Therefore, the calculated accident induced leakage rate from the most limiting accident would not be significant.
- j. Technical Specification 6.9.1.1 O.j, "The results of monitoring for tube axial displacement (slippage). If slippage is discovered, the implications of the discovery and corrective action shall be provided" 100% of all in-service tubes within the tubesheet, both HL and CL, were monitored for tube axial displacement (slippage) using Bobbin coil inspections. No indications of slippage were detected.
Page 5 of 5 LR-N18-0054 SALEM UNIT 1 MODEL F SG TUBE SUPPORT ARRANGEMENT AND TERMINOLOGY Tube Support Plate (TSP)
Tube Support ---..
Number Flow Distribution Baffle Plate (FOB)
Anti-Vibration Bars (AVB) 03H 02H OlH Top of Tubesheet (TTS)
Page 1 of 1 LR-N18-0054 1R25 TUBES PLUGGED FOR EACH DEGRADATION MECHANISM Steam Generator Location Tube Degradation 11 12 13 14 AVB Wear 0
0 0
0 TSP Wear 0
0 0
0 FBP Wear 0
0 0
0 All Foreign Object Wear 0
0 6
0 Total Tubes Plugged 0
0 6
0 Page 1 of 1 Total 0
0 0
6 6
LR-N18-0054 TOTAL NUMBER AND PERCENTAGE OF TUBES PLUGGED TO DATE Salem Unit 1 Steam Generator Tube Plu in Status SG 11 SG 12 SG 13 SG 14 51 57 113 36 0
0 6
0 51 57 119 36 0.91%)
1.01%>
2.12°/o 0.64%
1.17o/o Page 1 of 1 LR-N18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing Bobbin 96041.1 R5 Wear AVB None Yes Yes Bobbin 96042.1 R4 Wear Drilled TSP None Yes Yes Bobbin 96004.1 R13 Wear TSP and AVB None Yes Yes Bobbin 96004.3 Rl3 Wear TSP and AVB None Yes Yes Bobbin 27091.2 R2 Loose Part Freespan, PLP Loose Part Yes Size with +Point Volumetric W ear(part not Volumetric or Array present)
Wear with Part Present and Loose Parts Bobbin I-28411 R4 Axial Within non None Yes For CM/OA or ODSCC dented drilled Info Only TSP and within drilled TSP with dents:::; 2.0 Vpp Bobbin I-28412 R5 Axial Freespan with None Yes ForCM/OA or ODSCC or without dents Info Only
- 2.0 Vpp Bobbin I-28413 R5 Axial Within None Yes For CM/OA or ODSCC
- Freespan, Info Only Sludge Pile region and Broached TSP with or without dents :::; 2.0 Vpp
+Point 96910.1 R11 Wear Broached TSP FDB Wear&
Yes Yes-TSP Wear; Loose Part CMIOA or Info Wear with or Only for without part extended present applicability areas Page 1 of 5 LR-N18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing
+Point 27901.1 R1 Shape Freespan, TSP Detection of Yes Yes-Part Not 27902.1 R2 Dependent and Expansion foreign Present or 27903.1 R1 Volumetric Transition PLP material Removed 27904.1 R2 Indications Wear 27905.1 R2 Morphology For detection 27906.1 R1 Dependent-and sizing of 27907.1 R2 part not present PLP wear when part is present based on EPRI Report 1020631
+Point 10908.4 R1 AVB Wear U-bend None Yes Yes
+Point I-11524 RO Circ. PWSCC Expansion Dings, Dents, Yes See 20510.1 for Transition Tubesheet sizing (including OEX,BLG and OXP) and Non-dented support structures
+Point 20510.1 R7 Circ. PWSCC Expansion Dings, Dents, N/A ForCM/OAor Transition Tubesheet See I-11524 for Info Only (including detection OEX,BLG and OXP) and Non-dented support structures
+Point 96703.1 R17 Axial Dent or Ding Non-dented Yes ForCM/OA or PWSCC support Info Only structure and tubesheet
+Point 20511.1 R8 Axial Expansion Non-dented Yes For CMIOA or PWSCC Transition support Info Only structure and tubesheet
+Point 21410.1 R6 Circ. ODSCC Expansion
- Freespan, Yes For CMIOA or Transition Dings, Dented Info Only and Non-dented support structures, Sludge Pile, Tubesheet Page 2 of 5 LR-N 18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing
+Point I-28424 R4 Axial Sludge Pile; Expansion Yes N/A ODSCC within non Transition See I-28431 for dented drilled sizing TSP and within drilled TSP with dents (or Dings)
- S2.0 Vpp.
+Point I-28425 R4 Axial Freespan; within Expansion Yes N/A ODSCC non dented Transition See I-28432 for broached TSP sizing and within broached TSP with dents/ dings
- 2.0 Vpp.
+Point 21409.1 R7 Axial Support None Yes For CM/OA or ODSCC structures, Info Only freespan regions, sludge pile and tubesheet crevice
+Point I-28431R3 Axial Sizing None See I-28424 for Yes ODSCC Sludge Pile and detection Drilled TSP with or w/o Dents :::; 2 volts
+Point I-28432 R2 Axial Sizing None See I-28425 for Yes ODSCC
- Freespan, detection Broached TSP w/o Dents:::; 2 volts
+Point 22401.1 R4 Axial Dented Tube Dented AVB Yes For CM/OA or ODSCC Support and U-bend Info Only Structures dings (TSP/FDB)
+Point 96511.2 R16 Axial & Circ.
U-bend None Yes For CM/OA or PWSCC Info Only
+Point 10411.1 RO Axial U-bend Row 3-Ax and Circ Yes For CM/OA or 10411.2 RO ODSCC 5
- ODSCC, Information Only Row 1 and2 U-bends &
Higher Row U-bends (>R5)
+Point 13901.1 Rl Wear Tube to Tube N/A Yes Yes
+Point 21998.1 R4 Volumetric Freespan Sludge Pile Yes Yes Page 3 of 5 LR-N 18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing Array 11956.3 R2 Wear Broached TSP FDB Wear and Yes Yes (Ax. Sensitive)
Loose Part 11956.4 R2 Wear with Part (Circ.
Present Sensitive)
Array 17901.1 RO Shape Freespan part Detection of Yes Yes (Ax. Sensitive)
Dependent not present foreign (Part Not 17901.3 RO Volumetric material Present)
(Circ.
Indications Sensitive)
Detection of 17902.1 RO PLP wear (Ax. Sensitive) when part is 17902.3 RO present.
(Circ.
Sensitive) 17903.1 RO (Ax. Sensitive) 17903.3 RO (Circ.
Sensitive) 17904.1 RO (Ax. Sensitive) 17904.3 RO (Circ.
Sensitive) 17905.1 RO (Ax. Sensitive) 17905.3 RO (Circ.
Sensitive) 17906.1RO (Ax. Sensitive) 17906.3 RO (Circ.
Sensitive)
Array 17909.1 RO AVB Wear AVB Wear N/A Yes Yes (Ax. Sensitive)
Broached Mix 17909.4 RO (Circ.
Sensitive)
Array 20400.1 R5 Circ. ODSCC Expansion Axial ODSCC Yes N/A Transitions at Expansion Transition Circ ODSCC Freespan with/without Deposits (including sludge pile)
Page 4 of 5 LR-N18-0054 1R25 NONDESTRUCTIVE EXAMINATION TECHNIQUES Demonstrated Extended Site-Specific Review Probe Industry Damage Deemed Acceptable Qualification Mechanism Applicability Applicability Detection Sizing Array 20403.1 R 5 Axial Freespan - Not Freespan Yes N/A ODSCC associated with Deposits Deposits Present (including sludge pile)
Array 20500.1 R4 Ax. and Circ.
Expansion OEX,BLG Yes N/A 20501.1 R4 PWSCC Transition andOXP locations above and within the tubesheet Page 5 of 5 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 22 80 AV2
-0.2 11 11 22 80 AV1
-0.21 10 11 23 38 AV2 0.16 10 11 24 117 AV1
-0.02 10 11 24 117 AV6
-0.3 9
11 26 43 AV1
-0.16 13 11 26 43 AV2 0.1 16 11 26 43 AV5
-0.16 9
11 26 91 AV6 0.02 13 11 26 91 AV5
-0.07 9
11 26 91 AV1
-0.09 18 11 27 33 AV2
-0.14 13 11 27 33 AV5 0.08 10 11 27 33 AV6
-0.08 11 11 27 44 AV6 0.3 20 11 27 44 AV5
-0.14 11 11 27 44 AV2
-0.21 17 11 27 78 AV2 0.09 12 11 27 79 AV2
-0.28 8
11 27 80 AV2 0.04 20 11 27 115 AV6 0.2 11 11 28 10 AV2 0.04 10 11 28 10 AV1 0.01 11 11 28 114 AV6
-0.14 18 11 28 114 AV1 0.18 18 11 29 9
AV5
-0.22 25 11 29 9
AV2 0.11 14 11 29 54 AV2 0.01 11 11 29 54 AV1 0.01 10 11 29 112 AV5
-0.17 13 11 29 112 AV2
-0.5 21 11 29 114 AV6
-0.21 29 11 29 114 AV1 0.14 21 11 30 48 AV2 0.13 12 11 30 73 AV5
-0.42 12 11 30 86 AV2 0.11 12 11 30 86 AV1 0.61 10 11 31 109 AV6
-0.1 9
11 32 12 AV4
-0.04 13 Page 1 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 32 12 AV5 0.04 14 11 32 15 AV2 0.06 12 11 32 20 AV5
-0.07 8
11 32 31 AV2
-0.04 16 11 32 69 AV4 0.05 9
11 32 72 AV4
-0.16 14 11 32 72 AV3
-0.2 15 11 32 72 AV2 0.11 11 11 32 72 AV1
-0.22 13 11 32 84 AV4
-0.14 9
11 32 112 AV5 0.6 10 11 32 112 AV2
-0.6 8
11 33 107 AV6
-0.07 8
11 34 109 AV2
-0.2 21 11 34 111 AV6
-0.51 9
11 34 111 AV2
-0.59 9
11 35 13 AV6
-0.02 9
11 35 13 AV5
-0.06 13 11 35 44 AV6 0.25 14 11 35 44 AV5 0.14 23 11 35 44 AV4 0.06 18 11 35 44 AV1
-0.28 12 11 36 108 AV1
-0.5 10 11 36 109 AV6
-0.25 9
11 36 110 AV3
-0.07 10 11 37 48 AV2 0.04 9
11 37 65 AV2 0.02 10 11 37 67 AV1 0.47 10 11 37 68 AV5
-0.02 15 11 37 68 AV4 0.02 9
11 37 68 AV4
-0.25 12 11 37 68 AV3
-0.2 14 11 37 68 AV2 0.15 21 11 37 73 AV4 0.16 9
11 37 79 AV5 0.05 12 11 37 79 AV4 0.07 19 11 37 79 AV2 0.07 15 11 37 79 AV1 0.05 9
11 37 84 AV1 0.02 9
Page 2 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 37 100 AV5 0.09 9
11 37 100 AV4 0.02 10 11 37 100 AV2
-0.04 11 11 37 100 AV1
-0.02 9
11 38 15 AV2 0.08 10 11 38 15 AV1
-0.12 9
11 38 49 AV4 0.12 23 11 38 49 AV3 0.02 15 11 38 51 AV5 0.02 16 11 38 51 AV4
-0.2 17 11 38 51 AV2
-0.29 11 11 38 51 AV6 0.09 11 11 38 66 AV6 0.2 21 11 38 66 AV5
-0.23 25 11 38 66 AV4 0.09 8
11 38 66 AV3
-0.07 11 11 38 66 AV2 0.16 19 11 38 66 AV1
-0.11 9
11 38 74 AV3
-0.18 8
11 38 76 AV4 0.02 8
11 38 76 AV3 0.07 11 11 38 76 AV2 0.05 15 11 38 90 AV3
-0.09 11 11 38 105 AV6 0.02 12 11 38 105 AV5 0.11 24 11 38 105 AV4
-0.09 10 11 38 105 AV3
-0.27 21 11 38 105 AV2 0.02 21 11 38 108 AV5 0.38 7
11 38 108 AV4
-0.13 7
11 38 108 AV3
-0.23 12 11 39 17 AV5 0.06 15 11 39 37 AV6 0.12 12 11 39 41 AV2 0.04 12 11 39 55 AV5 0.04 9
11 39 55 AV3
-0.2 10 11 39 60 AV4 0.06 12 11 39 61 AV5
-0.18 16 11 39 61 AV4
-0.28 12 Page 3 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 39 61 AV6
-0.04 11 11 39 64 AV4 0.05 18 11 39 64 AV3 0.05 14 11 39 69 AV4
-0.29 11 11 39 69 AV2
-0.18 18 11 39 72 AV5 0.11 9
11 39 72 AV4 0.14 23 11 39 72 AV3
-0.11 18 11 39 72 AV2 0.15 21 11 39 72 AV1
-0.25 12 11 39 74 AV6 0.19 27 11 39 74 AV5 0.25 31 11 39 74 AV4
-0.31 23 11 39 74 AV3
-0.16 7
11 39 74 AV2
-0.21 9
11 39 99 AV5 0.02 17 11 39 99 AV3
-0.04 14 11 39 99 AV2
-0.27 31 11 39 107 AV4 0.22 9
11 40 19 AV3 0.04 13 11 40 20 AV4 0.04 17 11 40 20 AV3
-0.14 20 11 40 20 AV2 0.06 11 11 40 27 AV4
-0.14 9
11 40 37 AV2 0.08 10 11 40 40 AV2 0.06 10 11 40 40 AV1 0.04 9
11 40 42 AV4
-0.22 16 11 40 42 AV3 0.06 9
11 40 42 AV2 0.12 9
11 40 42 AV1 0.16 12 11 40 43 AV6 0.14 16 11 40 43 AV4 0.17 22 11 40 43 AV3 0.16 27 11 40 43 AV2
-0.23 29 11 40 43 AV1
-0.12 13 11 40 45 AV5
-0.02 13 11 40 45 AV4 0.02 12 11 40 48 AV6
-0.18 14 Page 4 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 40 48 AV4 0.02 12 11 40 48 AV3 0.02 14 11 40 48 AV2
-0.16 14 11 40 58 AV6 0.04 22 11 40 58 AV5 0.21 13 11 40 58 AV4 0.1 7
11 40 58 AV3 0.04 22 11 40 58 AV2 0.08 12 11 40 64 AV2
-0.18 11 11 40 77 AV3
-0.27 11 11 40 78 AV6
-0.18 10 11 40 78 AV5 0.33 28 11 40 78 AV4
-0.18 10 11 40 78 AV3
-0.27 31 11 40 78 AV2
-0.2 15 11 40 78 AV1 0.07 16 11 40 79 AV5
-0.04 13 11 40 79 AV3
-0.19 22 11 40 79 AV2 0.05 15 11 40 79 AV1
-0.67 9
11 40 84 AV6 0.07 15 11 40 84 AV5
-0.12 12 11 40 84 AV4 0.09 15 11 40 84 AV3 0.04 9
11 40 85 AV2 0.14 18 11 40 86 AV5 0.05 9
11 40 89 AV5
-0.02 12 11 40 89 AV4
-0.16 20 11 40 89 AV3 0.07 14 11 40 89 AV2
-0.25 8
11 40 91 AV1
-0.07 11 11 40 92 AV1
-0.07 11 11 40 98 AV5
-0.19 21 11 40 98 AV4 0.13 12 11 40 104 AV6
-0.16 10 11 40 104 AV5
-0.2 28 11 40 104 AV4
-0.22 27 11 40 104 AV3 0.07 14 11 40 105 AV6 0.07 31 Page 5 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 40 105 AVS 0.07 25 11 40 105 AV4
-0.22 24 11 40 105 AV3 0.06 33 11 40 105 AV2 0.05 16 11 40 106 AV6
-0.13 13 11 40 106 AVS 0.18 11 11 41 19 AV6 0.12 15 11 41 23 AV1 0.08 10 11 41 59 AV1
-0.24 11 11 41 73 AV1
-0.11 10 11 41 73 AV2
-0.07 9
11 41 82 AV4
-0.09 10 11 41 90 AVS 0.09 13 11 41 90 AV4 0.04 14 11 41 95 AV1
-0.16 11 11 41 100 AVS
-0.07 12 11 41 100 AV2 0.16 14 11 41 102 AV6
-0.04 12 11 41 102 AVS 0.02 14 11 41 102 AV2 0.09 13 11 41 102 AV1
-0.13 14 11 41 103 AVS
-0.04 21 11 41 103 AV4
-0.18 9
11 41 103 AV2 0.22 10 11 41 103 AV1 0.11 14 11 41 105 AV6
-0.45 9
11 41 105 AV1 0.36 7
11 42 33 AV3
-0.15 16 11 42 33 AV2 0.02 24 11 42 so AVS
-0.11 9
11 42 54 AVS
-0.18 11 11 42 78 AVS 0.2 10 11 42 95 AVS
-0.11 10 11 42 95 AV4
-0.09 11 11 42 95 AV3 0.07 11 11 42 97 AV3
-0.04 10 11 42 97 AV2
-0.09 10 11 42 97 AV1 0.02 15 11 42 99 AV4
-0.2 13 Page 6 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 42 99 AV2
-0.02 10 11 42 104 AV6 0.15 9
11 42 104 AV6
-0.16 10 11 43 20 AV5 0.1 21 11 43 22 AV4 0.08 27 11 43 22 AV3 0.08 10 11 43 25 AV5 0.21 27 11 43 25 AV4 0.22 21 11 43 25 AV3 0.02 12 11 43 33 AV2 0.05 11 11 43 38 AV3 0.08 30 11 43 38 AV2
-0.22 27 11 43 38 AV1 0.2 19 11 43 39 AV5
-0.08 13 11 43 39 AV2
-0.16 6
11 43 43 AV5 0.06 24 11 43 43 AV3
-0.12 19 11 43 43 AV2 0.06 26 11 43 44 AV6 0.2 11 11 43 44 AV5 0.1 21 11 43 44 AV4
-0.12 14 11 43 44 AV3
-0.21 22 11 43 44 AV2
-0.22 28 11 43 44 AV1
-0.16 12 11 43 46 AV6 0.38 21 11 43 46 AV5
-0.17 13 11 43 46 AV4 0.21 12 11 43 49 AV6
-0.02 9
11 43 49 AV4
-0.2 21 11 43 49 AV3
-0.13 12 11 43 52 AV2
-0.04 9
11 43 52 AV3 0.02 11 11 43 60 AV3
-0.08 11 11 43 62 AV2
-0.07 11 11 43 62 AV1 0.02 11 11 43 67 AV2
-0.16 11 11 43 67 AV1 0.04 11 11 43 75 AV3
-0.21 18 11 43 75 AV1
-0.29 19 Page 7 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 43 79 AV6 0.02 26 11 43 79 AV5 0.02 26 11 43 79 AV4
-0.05 16 11 43 79 AV2
-0.2 16 11 43 79 AV1
-0.29 9
11 43 81 AV5 0.35 8
11 43 82 AV5 0.15 12 11 43 82 AV4 0.07 10 11 43 83 AV3 0.02 12 11 43 83 AV2 0.02 11 11 43 83 AV5 0.18 13 11 43 83 AV4
-0.18 28 11 43 91 AV1 0.02 9
11 43 100 AV4 0.18 12 11 43 100 AV3 0.24 29 11 43 100 AV2
-0.18 19 11 43 100 AV1 0.02 11 11 43 103 AV6
-0.22 9
11 44 22 AV5 0.02 26 11 44 22 AV4
-0.02 13 11 44 41 AV3 0.01 8
11 44 41 AV4
-0.04 19 11 44 41 AV1 0.01 12 11 44 45 AV4 0.04 10 11 44 45 AV3
-0.06 16 11 44 45 AV2 0.06 9
11 44 58 AV4 0.06 22 11 44 58 AV3 0.08 18 11 44 59 AV4
-0.16 12 11 44 59 AV3
-0.12 16 11 44 59 AV2 0.17 11 11 44 59 AV1 0.06 10 11 44 60 AV4 0.06 24 11 44 60 AV3 0.06 18 11 44 60 AV2 0.02 10 11 44 61 AV3
-0.19 12 11 44 61 AV2
-0.13 10 11 44 68 AV6
-0.25 32 11 44 68 AV5
-0.21 26 Page 8 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 44 68 AV4
-0.24 16 11 44 68 AV3
-0.22 15 11 44 71 AV6 0.04 10 11 44 71 AV5
-0.21 9
11 44 71 AV4
-0.02 12 11 44 74 AV6
-0.31 13 11 44 74 AV5
-0.24 16 11 44 74 AV4 0.13 16 11 44 74 AV3 0.04 25 11 44 100 AV6
-0.06 9
11 44 100 AV5 0.15 29 11 44 100 AV4 0.05 10 11 44 100 AV3
-0.07 9
11 44 100 AV2
-0.07 7
11 44 102 AV6
-0.04 11 11 44 102 AV5 0.02 10 11 45 22 AV4 0.02 8
11 45 23 AV6
-0.18 16 11 45 23 AV2 0.19 11 11 45 26 AV3 0.04 12 11 45 26 AV2
-0.13 11 11 45 83 AV5
-0.22 11 11 45 100 AV6 0.11 11 11 47 43 AV5 0.04 9
11 47 99 AV3
-0.02 12 11 48 25 AV1 0.1 10 11 48 26 AV6
-0.2 9
11 48 26 AV5 0.06 15 11 48 47 AV5 0.1 14 11 48 80 AV1
-0.32 9
11 48 97 AV4 0.02 10 11 48 97 AV3
-0.04 12 11 49 27 AV1 0.04 12 11 49 29 AV5 0.12 27 11 49 29 AV4 0.02 9
11 49 36 AV4
-0.12 11 11 49 36 AV2
-0.19 15 11 49 39 AV4 0.06 17 11 49 39 AV2 0.08 19 Page 9 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 49 43 AV4 0.1 16 11 49 79 AV1
-0.53 12 11 49 84 AV1
-0.04 10 11 49 85 AV6 0.07 13 11 49 85 AVS 0.13 34 11 49 85 AV4 0.16 30 11 49 85 AV3 0.13 23 11 49 85 AV2 0.09 16 11 49 94 AV6
-0.17 11 11 49 96 AV6
-0.26 12 11 so 30 AV6
-0.06 12 11 so 65 AV2 0.11 12 11 so 90 AV1
-0.38 16 11 51 47 AVS 0.08 11 11 52 32 AV1 0.06 8
11 52 41 AV3
-0.06 10 11 52 89 AV4
-0.07 10 11 52 91 AVS
-0.02 11 11 52 91 AV2 0.18 11 11 54 39 AV6 0.02 11 11 54 65 AV4
-0.22 12 11 54 86 AV3 0.07 15 11 55 79 AV2
-0.07 11 11 55 82 AV2 0.11 9
11 55 83 AV6
-0.2 13 11 55 83 AVS 0.02 12 11 55 83 AV2 0.07 11 11 55 84 AV6
-0.15 14 11 55 84 AVS
-0.19 8
11 55 84 AV4
-0.02 9
11 56 41 AV6 0.01 13 11 56 78 AV2 0.01 11 11 56 79 AV2
-0.13 9
11 57 70 AV1
-0.07 12 11 57 75 AV2 0.06 8
11 57 77 AV6 0.02 10 11 57 77 AV2 0.02 15 11 57 77 AV6
-0.13 11 11 57 79 AV2 0.02 13 Page 10 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 11 58 61 AV6 0.12 10 11 58 62 AV6 0.19 10 11 58 62 AV1
-0.17 14 11 58 65 AV6 0.13 13 11 58 65 AV1
-0.09 10 11 59 58 AV6 0.23 13 12 21 84 AV1
-0.3 13 12 21 118 AV6 0.4 8
12 21 118 AV1 0.13 12 12 23 89 AV6
-0.07 20 12 23 89 AV2
-0.16 13 12 23 89 AV1
-0.39 9
12 23 91 AV1
-0.2 16 12 25 90 AV2
-0.09 11 12 25 116 AV1 0.36 9
12 26 38 AV6
-0.25 14 12 26 74 AV2
-0.33 20 12 26 74 AV5 0.02 13 12 26 83 AV1
-0.2 14 12 26 83 AV2 0.57 19 12 26 95 AV5 0.15 10 12 26 95 AV2
-0.24 9
12 26 103 AV2
-0.14 15 12 26 109 AV1 0.05 8
12 26 110 AV2
-0.22 8
12 27 8
AV1 0.33 22 12 27 8
AV1
-0.08 24 12 27 8
AV6 0.12 24 12 27 8
AV6
-0.21 11 12 27 36 AV5 0.26 9
12 27 102 AV2 0.02 9
12 27 112 AV2 0.14 20 12 27 115 AV6 0.07 31 12 27 115 AV1 0.02 16 12 28 109 AV5 0.12 12 12 29 13 AV6
-0.12 17 12 29 39 AV6
-0.18 10 12 29 39 AV5 0.02 21 12 29 39 AV2 0.2 21 Page 11 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 29 41 AV6
-0.2 15 12 29 41 AV5
-0.16 13 12 29 41 AV1 0.32 9
12 29 41 AV2 0.22 15 12 29 54 AV6 0.04 14 12 29 54 AV5
-0.02 20 12 29 54 AV2
-0.16 13 12 29 54 AV1 0.01 17 12 29 77 AV2
-0.11 12 12 29 86 AV6
-0.02 8
12 29 86 AV2 0.02 18 12 29 86 AV1
-0.27 11 12 29 89 AV2
-0.2 13 12 29 90 AV2 0.02 11 12 29 107 AV2 0.04 12 12 29 108 AV5 0.05 21 12 29 109 AV2 0.1 18 12 29 112 AVS 0.24 18 12 30 10 AV5 0.18 9
12 30 12 AV2
-0.18 12 12 30 13 AV2 0.07 19 12 30 104 AV5 0.09 15 12 30 111 AV6 0.09 15 12 30 111 AV3
-0.02 13 12 31 16 AV2
-0.22 11 12 31 113 AV5 0.26 7
12 31 113 AV2
-0.38 6
12 32 106 AV1 0.06 11 12 32 109 AV4 0.07 21 12 32 109 AV3
-0.11 11 12 32 110 AV2
-0.16 10 12 32 111 AV5 0.18 25 12 32 111 AV2 0.05 25 12 32 111 AV1 0.07 12 12 32 112 AV5 0.3 9
12 33 14 AV1
-0.69 9
12 33 108 AV5 0.11 21 12 33 108 AV3 0.02 22 12 34 110 AV4
-0.15 8
Page 12 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 35 108 AV5 0.02 9
12 35 108 AV3
-0.14 10 12 35 108 AV2
-0.18 11 12 35 110 AV6 0.04 10 12 36 15 AV6
-0.11 9
12 36 15 AV4 0.21 23 12 36 15 AV3 0.26 19 12 36 15 AV2
-0.05 12 12 36 110 AV3 0.11 14 12 38 15 AV3
-0.53 9
12 38 51 AV3
-0.16 13 12 38 51 AV2 0.09 14 12 38 70 AV4 0.2 10 12 38 70 AV3 0.09 11 12 38 104 AV5 0.02 10 12 38 104 AV2 0.02 20 12 38 107 AV3 0.13 25 12 38 107 AV2 0.07 26 12 38 107 AV1 0.02 13 12 39 48 AV5 0.48 9
12 39 48 AV4 0.12 11 12 39 48 AV6 0.38 20 12 39 54 AV6 0.13 24 12 39 55 AV5
-0.07 9
12 39 65 AV4 0.02 16 12 39 65 AV3 0.01 27 12 39 65 AV2 0.11 16 12 39 72 AV5
-0.01 16 12 39 72 AV4
-0.14 11 12 39 72 AV3 0.02 12 12 39 73 AV6
-0.15 21 12 39 73 AV5 0.29 21 12 39 73 AV4
-0.29 16 12 39 73 AV3
-0.48 27 12 39 73 AV2
-0.25 14 12 39 73 AV1
-0.15 18 12 39 75 AV1
-0.02 11 12 39 76 AV3
-0.18 12 12 39 96 AV5
-0.07 14 Page 13 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 39 96 AV4
-0.18 9
12 39 96 AV2
-0.15 12 12 39 98 AV6 0.05 9
12 39 100 AV5 0.04 11 12 39 107 AV4
-0.13 8
12 39 107 AV1 0.33 9
12 40 24 AV5 0.18 19 12 40 24 AV4 0.2 18 12 40 24 AV3 0.18 10 12 40 24 AV2 0.27 15 12 40 27 AV5 0.07 9
12 40 30 AV2 0.16 13 12 40 67 AV1
-0.07 10 12 40 69 AV2 0.01 16 12 40 75 AV1
-0.11 13 12 40 78 AV4 0.02 11 12 40 79 AV1 0.01 6
12 40 80 AV6 0.16 11 12 40 80 AV5 0.04 12 12 40 80 AV4 0.01 23 12 40 80 AV3 0.16 25 12 40 80 AV2 0.01 23 12 40 83 AV6 0.18 25 12 40 83 AV5
-0.05 32 12 40 83 AV4 0.15 27 12 40 83 AV3 0.1 31 12 40 83 AV2 0.21 29 12 40 83 AV1
-0.08 12 12 40 84 AV4
-0.07 13 12 40 85 AV1
-0.16 7
12 40 87 AV5 0.17 22 12 40 87 AV4
-0.02 16 12 40 87 AV3 0.21 20 12 40 87 AV2 0.23 21 12 40 87 AV1 0.21 12 12 40 88 AV5
-0.22 20 12 40 88 AV4 0.09 12 12 40 88 AV3 0.09 27 12 40 88 AV2
-0.22 19 Page 14 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 40 88 AV1 0.09 26 12 40 94 AV6
-0.14 17 12 40 94 AV5
-0.02 18 12 40 94 AV4
-0.22 17 12 40 94 AV3 0.2 28 12 40 94 AV2 0.05 22 12 40 94 AV1 0.02 9
12 40 95 AV6 0.07 8
12 40 95 AV5 0.16 25 12 40 95 AV4 0.05 17 12 40 95 AV3 0.02 18 12 40 95 AV2 0.05 31 12 40 95 AV1
-0.24 20 12 40 96 AV2 0.21 18 12 41 29 AV5
-0.17 12 12 41 29 AV4
-0.04 10 12 41 29 AV3 0.14 10 12 41 42 AV4
-0.22 9
12 41 56 AV3
-0.24 27 12 41 56 AV2
-0.24 19 12 41 82 AV3
-0.11 9
12 41 82 AV2 0.11 10 12 41 82 AV1
-0.29 18 12 41 83 AV4 0.07 8
12 41 83 AV2 0.2 10 12 41 85 AV4 0.13 17 12 41 85 AV3 0.22 24 12 41 85 AV2 0.02 15 12 41 85 AV1
-0.02 10 12 41 87 AV6 0.27 16 12 41 87 AV6
-0.1 11 12 41 87 AV5 0.02 31 12 41 87 AV4
-0.18 29 12 41 87 AV3 0.11 17 12 41 90 AV5 0.02 18 12 41 90 AV4 0.02 10 12 41 90 AV3 0.04 10 12 41 90 AV2 0.02 22 12 41 90 AV1 0.07 17 Page 15 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 41 93 AV4 0.1 17 12 41 93 AV2 0.04 8
12 41 94 AV5
-0.09 14 12 41 94 AV3 0.07 9
12 41 95 AV6 0.04 9
12 41 97 AV6 0.07 15 12 41 97 AV5
-0.09 13 12 41 97 AV4 0.15 22 12 41 97 AV3
-0.15 22 12 41 97 AV2 0.2 13 12 41 98 AV6
-0.15 22 12 41 98 AV5 0.11 17 12 41 98 AV4
-0.18 15 12 41 98 AV3
-0.15 19 12 41 98 AV2 0.02 27 12 41 99 AV4 0.02 9
12 41 100 AV6 0.15 10 12 41 100 AV3 0.05 25 12 41 100 AV2
-0.25 28 12 41 100 AV1
-0.04 17 12 41 101 AV6 0.2 31 12 41 101 AV5 0.13 32 12 41 101 AV4 0.15 11 12 41 101 AV3 0.04 11 12 41 101 AV2 0.2 29 12 41 101 AV1 0.22 18 12 41 102 AV6 0.02 10 12 41 102 AV5 0.07 20 12 41 102 AV4
-0.18 12 12 41 104 AV6 0.04 10 12 41 104 AV1
-0.11 10 12 41 105 AV2
-0.05 8
12 41 105 AV1 0.45 8
12 42 24 AV1 0.09 11 12 42 46 AV5
-0.2 25 12 42 51 AV6 0.11 21 12 42 51 AV4
-0.24 15 12 42 63 AV2
-0.31 10 12 42 100 AV3 0.16 12 Page 16 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 42 100 AV2 0.21 13 12 42 104 AV6
-0.02 9
12 43 27 AV2
-0.13 17 12 43 27 AV3 0.04 11 12 43 27 AV4 0.02 11 12 43 40 AV3 0.24 27 12 43 40 AV2 0.35 23 12 43 97 AV2 0.21 10 12 43 101 AV1
-0.04 9
12 44 26 AV6
-0.16 12 12 44 100 AV2
-0.2 12 12 45 23 AV5 0.02 12 12 45 67 AV1
-0.07 18 12 45 100 AV4
-0.09 10 12 45 100 AV2 0.02 9
12 46 80 AV2 0.01 9
12 46 91 AV5 0.07 11 12 46 91 AV4
-0.18 17 12 46 97 AV5 0.04 23 12 46 97 AV4 0.07 7
12 47 24 AV6 0.02 12 12 47 24 AV5 0.09 12 12 47 24 AV3 0.02 11 12 47 24 AV1 0.2 7
12 47 67 AV2 0.04 8
12 47 87 AV6 0.09 9
12 47 95 AV5 0.1 13 12 47 95 AV4 0.16 15 12 47 95 AV3 0.25 12 12 47 95 AV2 0.02 10 12 47 98 AV6 0.04 15 12 47 98 AV5 0.02 16 12 48 26 AV6
-0.11 11 12 48 79 AV3 0.11 12 12 48 79 AV2 0.01 15 12 48 79 AV1
-0.09 12 12 48 83 AV2
-0.18 16 12 48 86 AV2
-0.18 14 12 48 91 AV3 0.05 14 Page 17 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 48 91 AV2
-0.16 14 12 48 96 AV1
-0.04 10 12 48 98 AV4 0.02 18 12 49 35 AV3
-0.04 11 12 49 60 AV2
-0.15 11 12 49 95 AV6
-0.15 14 12 49 95 AV5 0.05 15 12 49 95 AV4
-0.2 11 12 49 96 AV5
-0.2 26 12 49 96 AV4
-0.33 11 12 49 96 AV6
-0.15 10 12 50 93 AV6
-0.17 10 12 50 95 AV1 0.07 11 12 51 67 AV2 0.01 14 12 51 67 AV1
-0.02 17 12 51 82 AV1
-0.17 21 12 51 85 AV2 0.05 8
12 52 32 AV3 0.02 11 12 52 62 AV2
-0.18 11 12 52 80 AV2 0.02 25 12 52 80 AV1
-0.07 19 12 52 80 AV3 0.02 12 12 52 89 AV5
-0.13 13 12 52 90 AV2 0.09 10 12 52 91 AV1 0.22 11 12 53 33 AV3 0.1 11 12 53 34 AV6 0.04 13 12 53 90 AV1
-0.15 9
12 53 90 AV5
-0.15 10 12 54 35 AV6
-0.16 15 12 54 38 AV4 0.04 11 12 54 38 AV2
-0.04 9
12 54 88 AV1 0.07 12 12 55 83 AV1 0.01 12 12 56 41 AV6 0.11 12 12 56 41 AV2 0.11 11 12 56 42 AV6 0.02 10 12 56 77 AV4
-0.28 12 12 57 44 AV6 0.02 13 Page 18 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 12 57 44 AV4
-0.09 13 12 57 46 AV1 0.02 11 12 57 53 AV2
-0.09 13 12 57 54 AV1
-0.11 12 12 57 79 AV1 0.04 12 12 58 52 AV6 0.04 14 12 58 52 AV3
-0.02 10 12 58 58 AV6 0.07 12 12 58 60 AV1
-0.16 9
12 58 72 AV6 0.01 11 13 12 2
AV6
-0.39 12 13 12 121 AV1 0.19 11 13 13 78 AV6
-0.31 9
13 15 67 AV1 0.12 10 13 15 67 AV6 0.19 15 13 15 101 AV1 0.32 10 13 16 72 AV1 0.26 8
13 19 53 AV1 0.02 13 13 19 78 AV1 0.14 12 13 19 80 AV1
-0.54 13 13 19 80 AV6
-0.04 27 13 20 81 AV2 0.62 9
13 21 116 AV1
-0.04 6
13 21 118 AV6 0.16 8
13 21 118 AV1 0.23 11 13 22 5
AV6
-0.24 20 13 22 117 AV1 0.55 10 13 23 112 AV1
-0.14 10 13 23 116 AV1 0.18 15 13 23 117 AV1 0.58 21 13 24 6
AV1
-0.25 16 13 24 6
AV1 0.44 10 13 24 6
AV6
-0.05 7
13 24 7
AV1 0.31 13 13 24 7
AV6
-0.28 17 13 24 8
AV1
-0.11 12 13 24 53 AV2 0.36 18 13 24 112 AV1
-0.08 14 13 24 113 AV6 0.12 9
Page 19 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 24 116 AV1 0.26 9
13 25 7
AV1
-0.16 17 13 25 7
AV1 0.15 10 13 25 7
AV6 0.09 24 13 25 9
AV2 0.17 9
13 25 31 AV2
-0.2 14 13 25 36 AV2 0.09 13 13 25 36 AVS
-0.02 10 13 25 38 AV2 0.11 17 13 25 115 AV6
-0.17 15 13 26 43 AV1 0.15 17 13 26 43 AV2 0.35 17 13 26 43 AVS 0.23 15 13 26 43 AV6 0.3 12 13 26 80 AV2 0.4 13 13 26 80 AVS 0.3 9
13 26 111 AVS
-0.07 9
13 26 111 AV6 0.14 9
13 26 115 AV1 0.28 10 13 26 115 AV6
-0.15 8
13 26 116 AV6
-0.47 8
13 27 10 AV1 0.05 10 13 27 10 AVS 0.21 12 13 27 11 AV2 0.12 14 13 27 11 AV6
-0.16 11 13 27 12 AV6
-0.07 10 13 27 103 AV2 0.12 8
13 28 52 AV2
-0.14 12 13 28 108 AV1 0.07 13 13 28 108 AV2 0.29 9
13 28 109 AV1
-0.02 9
13 29 80 AV2
-0.1 14 13 29 99 AV2 0.1 9
13 30 11 AV6 0.25 14 13 30 46 AV2 0.37 22 13 30 47 AV1
-0.2 11 13 30 47 AV2
-0.16 16 13 30 47 AVS 0.21 11 13 30 66 AV2 0.14 9
Page 20 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 31 10 AV5 0.21 10 13 31 32 AV2
-0.15 9
13 31 32 AV5
-0.18 19 13 31 55 AV2 0.09 10 13 31 61 AV5 0.15 8
13 31 104 AV5 0.02 11 13 32 14 AV6 0.18 14 13 32 15 AV2
-0.11 25 13 32 16 AV2 0.24 23 13 32 16 AV5 0.13 11 13 32 19 AV2
-0.08 11 13 32 48 AV2
-0.16 15 13 32 61 AV1 0.61 17 13 32 80 AV3 0.18 12 13 32 101 AV5 0.18 9
13 32 103 AV2
-0.02 10 13 32 108 AV5 0.11 12 13 33 15 AV2
-0.05 13 13 33 15 AV4
-0.2 12 13 33 15 AV5 0.09 13 13 33 111 AV6 0.14 13 13 34 48 AV1 0.33 22 13 34 48 AV2 0.21 14 13 34 48 AV3 0.16 10 13 34 48 AV4
-0.25 27 13 34 48 AV5 0.02 14 13 34 48 AV6
-0.2 9
13 34 111 AV1
-0.14 20 13 34 111 AV5 0.29 17 13 34 111 AV6
-0.16 11 13 35 81 AV4
-0.09 15 13 36 14 AV6
-0.27 7
13 36 43 AV2
-0.09 14 13 36 43 AV4 0.09 12 13 36 43 AV5 0.22 12 13 36 43 AV6
-0.22 10 13 36 80 AV3
-0.13 31 13 36 80 AV4
-0.19 19 13 36 80 AV5 0.2 17 Page 21 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 36 87 AV1 0.07 9
13 36 87 AV2 0.07 20 13 36 87 AV3
-0.04 18 13 36 87 AV4 0.02 9
13 36 87 AV6
-0.05 20 13 36 88 AV1 0.2 12 13 36 88 AV2 0.14 17 13 36 88 AV3
-0.07 14 13 36 88 AV4 0.05 25 13 36 88 AV5 0.02 18 13 36 88 AV6
-0.05 19 13 36 89 AV2 0.18 16 13 36 89 AV3 0.14 14 13 36 89 AV4 0.02 19 13 36 89 AV5 0.13 14 13 36 97 AV1 0.11 11 13 36 97 AV2 0.16 14 13 36 97 AV3 0.18 18 13 36 97 AV5 0.13 13 13 36 110 AV6 0.02 16 13 37 60 AV4 0.11 14 13 38 15 AV4
-0.23 10 13 38 26 AV2 0.14 12 13 38 26 AV3
-0.21 13 13 38 28 AV2 0.23 15 13 38 28 AV3 0.16 17 13 38 28 AV4 0.09 12 13 38 28 AV6
-0.07 8
13 38 53 AV1 0.02 12 13 I
38 53 AV2
-0.16 29 13 38 53 AV3
-0.07 14 13 38 53 AV4
-0.13 17 13 38 53 AV5 0.43 20 13 38 58 AV5
-0.16 18 13 38 58 AV6 0.1 14 13 38 63 AV2
-0.53 10 13 38 63 AV3 0.22 10 13 38 63 AV4 0.11 11 13 38 63 AV5
-0.11 13 Page 22 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 38 67 AV3
-0.41 16 13 38 67 AV4
-0.11 12 13 38 67 AV6 0.09 10 13 38 69 AV2 0.05 16 13 38 69 AV3
-0.02 10 13 38 72 AV2 0.21 27 13 38 72 AV3 0.15 24 13 38 72 AV4 0.23 28 13 38 72 AV5 0.16 11 13 38 73 AV2
-0.12 8
13 38 73 AV3
-0.29 10 13 38 81 AV5
-0.12 14 13 38 81 AV6 0.13 14 13 38 82 AV3 0.29 14 13 38 83 AV2 0.13 12 13 38 83 AV3
-0.13 23 13 38 83 AV4
-0.09 17 13 38 83 AV5 0.34 24 13 38 85 AV1 0.02 10 13 38 85 AV3 0.02 14 13 38 85 AV4 0.23 18 13 38 85 AV5 0.16 11 13 38 88 AV2 0.04 10 13 38 88 AV3 0.04 18 13 38 88 AV4 0.05 9
13 38 91 AV2 0.13 18 13 38 91 AV3 0.15 14 13 38 91 AV4 0.05 15 13 38 91 AV5
-0.12 25 13 38 91 AV6 0.07 16 13 38 92 AV2 0.22 17 13 38 92 AV4
-0.14 19 13 38 92 AV5 0.2 20 13 38 98 AV2 0.22 20 13 38 98 AV3 0.02 21 13 38 98 AV5 0.16 13 13 38 98 AV6 0.17 17 13 38 101 AV3
-0.19 10 13 38 101 AV5 0.25 16 Page 23 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 39 16 AV1 0.39 7
13 39 16 AV6
-0.52 10 13 39 20 AV5
-0.07 16 13 39 22 AV2
-0.07 15 13 39 22 AV3 0.11 15 13 39 22 AV4
-0.16 11 13 39 22 AV5 0.2 12 13 39 23 AV5
-0.02 10 13 39 35 AV2
-0.09 11 13 39 35 AV3 0.16 16 13 39 35 AV5 0.29 24 13 39 38 AV1
-0.15 13 13 39 38 AV2 0.16 20 13 39 38 AV3
-0.16 24 13 39 38 AV5
-0.21 23 13 39 38 AV6
-0.11 14 13 39 46 AV2
-0.27 16 13 39 53 AV3
-0.09 11 13 39 53 AV4
-0.07 11 13 39 54 AV3 0.22 22 13 39 54 AV4 0.2 20 13 39 54 AV5
-0.16 8
13 39 54 AV6 0.4 8
13 39 64 AV2
-0.27 8
13 39 64 AV3 0.02 13 13 39 65 AV1 0.2 14 13 39 65 AV2
-0.22 25 13 39 65 AV4
-0.09 16 13 39 65 AV5
-0.21 12 13 39 65 AV3
-0.07 9
13 39 65 AV3 0.2 9
13 39 80 AV2
-0.16 21 13 39 80 AV3 0.25 13 13 39 80 AV4 0.11 13 13 39 80 AV5
-0.11 12 13 39 80 AV6 0.05 10 13 39 87 AV5 0.25 14 13 39 87 AV6 0.18 15 13 39 100 AV5
-0.05 10 Page 24 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 40 19 AV3
-0.21 14 13 40 57 AV2
-0.09 11 13 40 100 AV4
-0.11 7
13 40 100 AV5 0.02 18 13 41 31 AV4
-0.02 22 13 41 31 AV5
-0.22 19 13 41 33 AV2 0.19 13 13 41 33 AV3 0.2 15 13 41 66 AV4 0.15 7
13 41 79 AV2
-0.09 8
13 41 79 AV5 0.18 8
13 41 96 AV2
-0.09 13 13 41 96 AV3 0.18 23 13 41 105 AV2 0.2 16 13 42 19 AV3 0.16 9
13 42 19 AV4 0.12 8
13 42 38 AV2 0.12 13 13 42 38 AV3
-0.23 23 13 42 38 AV4
-0.2 28 13 42 38 AV5 0.38 17 13 42 38 AV6
-0.04 14 13 42 46 AV2 0.36 6
13 42 53 AV1
-0.02 8
13 42 53 AV4
-0.12 9
13 42 98 AV4 0.18 12 13 42 100 AV6
-0.06 15 13 42 103 AV5 0.15 13 13 42 104 AV1 0.36 12 13 42 104 AV2 0.16 14 13 43 23 AV3 0.16 13 13 43 47 AV3 0.04 9
13 43 56 AV2 0.16 7
13 43 57 AV4
-0.23 13 13 43 57 AV5 0.26 9
13 43 62 AV5
-0.04 15 13 43 62 AV6
-0.25 8
13 43 64 AV3 0.18 14 13 43 64 AV4 0.24 28 13 43 64 AV5
-0.02 8
Page 25 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 43 69 AV3 0.12 10 13 43 69 AV4 0.2 12 13 43 69 AV5 0.24 15 13 43 69 AV6
-0.18 10 13 43 71 AV2 0.07 10 13 43 71 AV5 0.22 12 13 43 72 AV4 0.19 13 13 43 72 AV5 0.18 10 13 43 72 AV6 0.2 21 13 43 73 AV3
-0.22 16 13 43 73 AV5 0.19 13 13 43 73 AV6 0.16 10 13 43 75 AV3 0.35 12 13 43 75 AV5 0.2 22 13 43 75 AV6 0.18 15 13 43 75 AV4 0.54 10 13 43 77 AV4
-0.18 9
13 43 77 AV5
-0.13 13 13 43 79 AV1
-0.15 9
13 43 80 AV1 0.11 12 13 43 80 AV2 0.21 24 13 43 80 AV3
-0.14 29 13 43 80 AV4
-0.04 27 13 43 80 AV5 0.24 24 13 43 81 AV1 0.18 7
13 43 81 AV2 0.22 24 13 43 81 AV3 0.48 15 13 43 81 AV4 0.21 12 13 43 81 AV5
-0.12 17 13 43 81 AV6
-0.18 27 13 43 83 AV1 0.22 11 13 43 85 AV2 0.32 16 13 43 87 AV1 0.09 13 13 43 91 AV3 0.22 16 13 43 91 AV4
-0.11 17 13 43 91 AV5
-0.02 14 13 43 93 AV2
-0.09 14 13 43 96 AV3 0.17 10 13 43 96 AV4 0.14 12 Page 26 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 43 96 AV6
-0.05 12 13 44 25 AV2
-0.12 13 13 44 25 AV3
-0.02 10 13 44 26 AV2
-0.02 17 13 44 26 AV3
-0.04 9
13 44 26 AV4
-0.02 9
13 44 59 AV2 0.2 13 13 44 59 AV3
-0.09 10 13 44 60 AV3
-0.1 17 13 44 67 AV5 0.18 10 13 44 68 AV1 0.21 25 13 44 68 AV2
-0.14 23 13 44 68 AV3 0.02 21 13 44 68 AV4 0.04 21 13 44 68 AV5 0.28 23 13 44 71 AV2 0.16 16 13 44 76 AV3
-0.51 19 13 44 77 AV2 0.01 12 13 44 77 AV3
-0.14 15 13 44 77 AV4 0.17 10 13 44 85 AV4
-0.38 7
13 44 91 AV5
-0.11 10 13 44 95 AV4 0.15 13 13 44 100 AV5 0.18 12 13 44 101 AV5 0.18 12 13 45 23 AV6
-0.36 9
13 45 64 AV6 0.3 6
13 45 66 AV2 0.02 9
13 45 66 AV1
-0.02 8
13 45 79 AV2 0.04 10 13 45 97 AV4
-0.11 22 13 45 97 AV6 0.2 20 13 45 100 AV2 0.2 14 13 45 100 AV4 0.07 10 13 46 24 AV5
-0.07 22 13 46 24 AV6 0.13 11 13 46 73 AV2
-0.36 21 13 46 73 AV3 0.35 12 13 46 77 AV4 0.17 8
Page 27 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 46 77 AVS
-0.06 9
13 47 25 AV4
-0.07 11 13 47 25 AVS 0.18 18 13 47 25 AV6
-0.04 15 13 47 26 AVS 0.09 10 13 47 26 AV6 0.09 14 13 47 97 AV6 0.13 15 13 48 25 AV2
-0.13 18 13 48 25 AV4
-0.23 9
13 48 41 AV2 0.09 9
13 48 94 AV2 0.13 11 13 48 95 AV3 0.14 14 13 48 98 AV6
-0.16 13 13 49 27 AV1 0.44 10 13 49 27 AV6
-0.09 9
13 49 32 AV4
-0.05 12 13 49 32 AVS
-0.16 11 13 49 53 AVS 0.22 13 13 49 57 AV6
-0.09 10 13 49 92 AV4 0.17 13 13 49 93 AVS 0.13 10 13 49 93 AV6 0.07 14 13 49 94 AVS 0.2 20 13 49 94 AV6 0.15 31 13 49 95 AV4 0.13 23 13 so 56 AV1 0.7 8
13 so 87 AVS 0.13 11 13 so 93 AVS 0.15 30 13 so 94 AV1 0.2 24 13 so 94 AV2 0.2 31 13 so 94 AV6
-0.07 14 13 51 so AV4
-0.18 16 13 51 so AVS
-0.04 17 13 51 so AV6
-0.02 17 13 51 55 AV4
-0.02 11 13 51 55 AVS
-0.1 26 13 51 55 AV6
-0.12 15 13 51 57 AVS 0.2 9
13 51 79 AV1
-0.13 9
Page 28 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 51 79 AV2 0.11 12 13 51 91 AV3 0.15 15 13 51 91 AV4 0.02 28 13 51 91 AV5
-0.14 12 13 51 92 AV2
-0.14 16 13 51 92 AV4 0.16 17 13 51 92 AV5
-0.18 30 13 52 32 AV3 0.04 8
13 52 34 AV5
-0.03 6
13 52 34 AV6
-0.02 18 13 52 89 AV1
-0.04 12 13 52 89 AV2 0.2 26 13 52 89 AV3
-0.11 25 13 52 89 AV5 0.15 19 13 52 89 AV6 0.19 12 13 53 57 AV1
-0.39 12 13 53 57 AV2 0.14 14 13 53 57 AV3 0.17 22 13 53 57 AV4 0.18 16 13 53 58 AV2
-0.06 13 13 53 69 AV2 0.1 10 13 53 72 AV4 0.22 21 13 53 72 AV5 0.17 10 13 53 88 AV4 0.24 16 13 53 88 AV5 0.22 24 13 53 89 AV4 0.2 10 13 53 89 AV5 0.13 20 13 53 89 AV6
-0.09 14 13 54 36 AV5 0.02 12 13 54 37 AV2
-0.04 10 13 54 37 AV3
-0.14 21 13 54 37 AV4
-0.14 22 13 54 37 AV5
-0.14 16 13 54 37 AV6 0.18 9
13 54 38 AV2 0.04 11 13 54 43 AV4 0.2 14 13 54 71 AV5
-0.04 13 13 54 72 AV2
-0.05 12 13 54 72 AV5
-0.01 20 Page 29 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 13 54 72 AV6
-0.02 15 13 54 76 AV1 0.14 13 13 54 85 AV2
-0.23 11 13 54 86 AV1 0.11 9
13 54 86 AV3 0.16 12 13 54 88 AV4 0.07 12 13 55 56 AV2 0.16 11 13 55 56 AV5 0.11 11 13 55 83 AV1 0.02 11 13 55 83 AV3 0.04 10 13 55 83 AV4
-0.04 7
13 55 84 AV4
-0.09 12 13 55 84 AV5 0.13 13 13 56 41 AV2 0.11 11 13 56 42 AV2 0.06 11 13 56 66 AV3 0.02 9
13 56 81 AV6 0.11 8
13 57 72 AV5 0.11 9
13 57 73 AV3
-0.13 8
13 57 73 AV5
-0.09 11 13 57 78 AV1 0.14 9
13 57 78 AV2 0.15 10 13 57 78 AV6
-0.14 9
13 57 79 AV2
-0.05 9
13 57 79 AV6
-0.02 12 13 58 52 AV6 0.1 14 13 58 55 AV1
-0.18 13 13 58 67 AV1
-0.05 7
13 58 73 AV6 0.02 13 13 58 75 AV2
-0.11 8
13 58 75 AV3 0.07 16 13 58 76 AV3 0.18 10 13 58 76 AV5 0.22 11 13 58 76 AV6 0.19 10 13 59 61 AV1
-0.27 10 13 59 61 AV6 0.23 11 13 59 66 AV6 0.15 12 14 16 60 AV6
+0.07 12 14 16 91 AV6
-0.14 10 Page 30 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 20 5
AV1
-0.49 10 14 21 7
AV1
-0.14 11 14 23 6
AV1
+0.64 16 14 24 6
AV1
+0.02 22 14 24 7
AV6
-0.28 12 14 24 7
AV1
-0.23 11 14 24 8
AV1
-0.23 18 14 24 116 AV1
-0.16 27 14 24 116 AV6
+0.50 17 14 24 117 AV6
+0.54 6
14 25 7
AV1
-0.04 17 14 25 7
AV6
-0.36 20 14 25 8
AV1
-0.30 32 14 25 9
AV5
+0.12 12 14 25 26 AV6
-0.07 7
14 25 35 AV6
-0.38 11 14 25 36 AV6
-0.35 19 14 25 44 AV5
+0.21 20 14 25 88 AV5
-0.16 11 14 25 89 AV2
+0.14 9
14 25 109 AV6
+0.18 13 14 25 115 AV6
+0.18 22 14 26 7
AV6
-0.10 15 14 26 7
AV1
-0.07 23 14 26 84 AV5
-0.02 10 14 26 109 AV5
+0.11 11 14 26 113 AV5
+0.04 12 14 26 114 AV2
-0.19 12 14 26 115 AV1
+0.21 30 14 26 115 AV5
+0.02 14 14 26 115 AV6
+0.09 17 14 26 116 AV1
-0.16 15 14 26 116 AV6
+0.68 11 14 27 8
AV6
+0.09 13 14 27 8
AV6
-0.27 16 14 27 8
AV1
+0.27 15 14 27 8
AV1
-0.21 28 14 27 79 AV6
+0.11 15 14 27 79 AV5
+0.05 25 Page 31 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 27 79 AV2
+0.13 23 14 27 114 AV2
-0.21 17 14 28 9
AV5
-0.35 27 14 28 9
AV2
+0.31 26 14 28 9
AV6
+0.22 13 14 28 12 AV6
+0.09 14 14 28 14 AV6
+0.05 12 14 28 38 AV5
+0.22 16 14 28 38 AV2
+0.23 21 14 28 81 AV5
+0.04 14 14 28 109 AV1
+0.14 12 14 28 111 AV5
+0.02 11 14 28 111 AV2
+0.18 13 14 28 113 AV6
+0.07 10 14 28 113 AV5
+0.13 18 14 28 113 AV2
-0.26 13 14 29 11 AV6
-0.05 12 14 29 109 AV6
-0.18 13 14 29 109 AV2
-0.07 11 14 29 110 AV5
-0.18 17 14 29 110 AV2
+0.02 12 14 29 110 AV1
-0.16 9
14 29 111 AV5
-0.19 18 14 29 111 AV1
+0.02 12 14 30 14 AV6
+0.12 9
14 30 18 AV6
-0.18 9
14 30 67 AV5
+0.11 16 14 30 72 AV6
+0.02 11 14 30 72 AV2
+0.09 20 14 30 76 AV5
-0.33 14 14 30 107 AV1
+0.05 9
14 30 107 AV5
+0.16 16 14 30 109 AV6
-0.07 8
14 30 111 AV2
+0.02 15 14 30 114 AV2
-0.59 10 14 31 11 AV6
-0.11 19 14 32 12 AV5
+0.07 25 14 32 12 AV4
-0.02 21 14 32 84 AV3
-0.39 10 Page 32 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 32 84 AV2
+0.11 22 14 32 84 AV5
-0.20 20 14 32 109 AV2
+0.05 15 14 32 112 AV5
+0.51 9
14 33 12 AV6
+0.16 20 14 33 12 AV5
+0.14 23 14 33 12 AV2
+0.15 24 14 33 12 AV1
-0.06 14 14 34 91 AV4
+0.02 9
14 34 108 AV1
+0.04 7
14 34 108 AV2
+0.02 10 14 34 108 AV3
+0.09 18 14 34 108 AV4
-0.13 23 14 34 108 AV6
-0.15 10 14 34 111 AV6
+0.30 9
14 34 111 AV2
-0.67 12 14 37 102 AV5
+0.07 7
14 37 103 AV5
+0.05 13 14 38 21 AV5
+0.02 12 14 38 21 AV2
+0.08 9
14 38 32 AV4
-0.16 10 14 38 32 AV3
+0.16 13 14 38 92 AV3
+0.11 10 14 38 99 AV5
-0.20 15 14 38 101 AV2
+0.16 15 14 38 101 AV3
+0.02 27 14 38 101 AV4
+0.02 23 14 38 101 AV5
+0.07 17 14 38 103 AV2
+0.09 15 14 38 103 AV4
+0.02 12 14 38 103 AV5
+0.02 10 14 38 104 AV4
-0.20 18 14 38 108 AV6
+0.18 10 14 38 108 AV3
-0.11 9
14 38 108 AV2
-0.39 12 14 38 108 AV5
+0.25 7
14 39 56 AV5
-0.22 16 14 39 56 AV4
+0.20 19 14 39 56 AV3
+0.08 23 Page 33 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 39 68 AV6
-0.36 22 14 39 68 AV5
+0.10 11 14 39 68 AV3
+0.11 22 14 39 68 AV2
+0.07 15 14 39 71 AV1
-0.21 10 14 39 77 AV4
-0.38 22 14 39 77 AV3
-0.25 19 14 39 77 AV2
-0.18 16 14 39 78 AV3
+0.33 8
14 39 78 AV2
-0.16 11 14 39 79 AV3
-0.27 16 14 39 81 AV2
-0.27 12 14 39 82 AV4
-0.11 9
14 39 82 AV3
+0.11 9
14 39 89 AV5
+0.02 8
14 39 89 AV4
-0.10 12 14 39 89 AV3
+0.16 12 14 39 95 AV3
+0.07 9
14 39 95 AV2
+0.04 10 14 39 96 AV1
-0.26 11 14 39 96 AV2
+0.20 23 14 39 96 AV3
+0.04 21 14 39 96 AV4
+0.02 15 14 39 97 AV3
+0.02 21 14 39 98 AV5
+0.02 12 14 39 98 AV3
-0.16 15 14 39 100 AV5
+0.04 11 14 39 100 AV4
-0.13 11 14 39 100 AV2
+0.04 20 14 39 100 AV3
+0.07 22 14 40 33 AV2
+0.12 11 14 40 48 AV6
-0.24 23 14 40 48 AV5
-0.19 23 14 40 48 AV4
-0.35 22 14 40 48 AV3
+0.14 18 14 40 48 AV2
+0.19 9
14 40 48 AV1
-0.21 24 14 40 58 AV4
-0.18 13 14 40 58 AV2
-0.28 17 Page 34 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 40 58 AV1
+0.04 11 14 40 60 AV6
+0.06 12 14 40 60 AV4
+0.35 12 14 40 60 AV4
-0.20 16 14 40 60 AV3
-0.30 18 14 40 60 AV2
-0.36 11 14 40 60 AV1
-0.18 15 14 40 66 AV4
+0.02 11 14 40 78 AVS
+0.17 11 14 40 78 AV4
-0.02 12 14 40 80 AV1
+0.07 8
14 40 80 AV2
+0.20 19 14 40 80 AV3
-0.24 18 14 40 80 AV4
-0.07 25 14 40 80 AV4
+0.34 11 14 40 80 AVS
-0.20 9
14 40 80 AVS
+0.24 26 14 40 80 AV6
-0.28 9
14 40 80 AV6
+0.11 18 14 40 87 AV6
+0.13 17 14 40 87 AVS
+0.20 28 14 40 87 AV4
+0.16 23 14 40 87 AV3
-0.16 26 14 40 87 AV2
+0.05 10 14 40 106 AV6
+0.11 13 14 40 106 AVS
+0.31 9
14 40 106 AV3
+0.13 11 14 40 106 AV1
+0.11 10 14 41 61 AV1
+0.04 10 14 41 100 AV3
+0.02 15 14 41 100 AVS
+0.02 12 14 41 105 AVS
+0.22 12 14 41 105 AV3
-0.04 11 14 41 105 AV1
-0.02 9
14 42 19 AV2
-0.53 11 14 42 19 AV1
+0.02 11 14 42 21 AV4
-0.14 12 14 42 21 AV3
+0.22 24 14 42 21 AV2
-0.11 11 Page 35 of 39 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 42 21 AV1
-0.10 11 14 42 30 AV4
+0.27 29 14 42 30 AV3
+0.17 23 14 42 30 AV2
+0.19 22 14 42 30 AV1
+0.11 8
14 42 30 AVS
+0.20 23 14 42 39 AV6
-0.04 10 14 42 39 AVS
-0.08 12 14 42 39 AV2
-0.15 11 14 42 39 AV3
-0.04 12 14 42 104 AV6
-0.07 11 14 42 104 AVS
+0.04 10 14 43 53 AVS
-0.33 27 14 43 53 AV4
+0.25 25 14 43 53 AV3
+0.08 34 14 43 53 AV2
+0.22 13 14 43 53 AV2
-0.11 18 14 43 53 AV1
-0.18 8
14 43 100 AV3
+0.02 6
14 43 103 AV3
-0.11 13 14 44 21 AVS
+0.20 9
14 44 so AV6
-0.04 10 14 44 102 AV6
-0.13 10 14 44 102 AV3
-0.11 13 14 44 102 AV2
-0.16 13 14 45 22 AVS
+0.06 12 14 45 22 AV4
+0.04 11 14 45 101 AVS
+0.13 8
14 45 101 AV6
-0.04 10 14 46 24 AV6
+0.06 12 14 46 29 AVS
-0.02 11 14 47 34 AV6
-0.02 11 14 47 43 AV4
+0.06 12 14 47 43 AV3
+0.06 17 14 47 43 AV2
+0.04 8
14 47 43 AV1
-0.10 9
14 47 57 AVS
+0.18 13 14 47 57 AV3
+0.16 14 14 47 57 AV2
+0.14 14 Page 36 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 47 57 AV6
+0.06 11 14 47 88 AV4
+0.07 12 14 48 26 AV2
-0.36 12 14 48 86 AV3
+0.13 10 14 48 97 AV6
-0.07 13 14 49 27 AVS
+0.02 13 14 49 27 AV3
-0.04 12 14 49 28 AVS
+0.01 12 14 49 95 AV3
+0.07 9
14 49 96 AV6
+0.15 17 14 so 28 AV6
-0.24 27 14 so 28 AVS
+0.15 19 14 so 93 AV6
-0.11 8
14 so 94 AV3
-0.04 16 14 so 95 AV2
-0.04 10 14 51 31 AV6
-0.30 13 14 51 31 AVS
-0.18 10 14 51 31 AV4
-0.06 12 14 51 92 AVS
-0.07 11 14 52 32 AVS
-0.06 13 14 52 32 AV4
-0.18 12 14 52 32 AV3
+0.14 12 14 52 34 AV6
-0.04 12 14 52 34 AVS
+0.02 13 14 52 34 AV4
-0.12 10 14 52 39 AV6
-0.18 12 14 52 88 AV3
-0.02 8
14 52 90 AV2
-0.07 10 14 52 91 AVS
-0.02 11 14 52 91 AV2
-0.02 11 14 53 33 AV3
+0.06 10 14 53 33 AVS
+0.25 23 14 53 33 AV4
-0.20 16 14 53 34 AV6
+0.18 14 14 53 34 AVS
-0.02 11 14 53 34 AV4
+0.20 13 14 53 35 AV6
-0.18 10 14 53 37 AV6
-0.10 9
14 53 38 AV6
-0.24 18 Page 37 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 53 38 AV4
-0.16 17 14 53 38 AVS
+0.01 11 14 53 38 AV3
+0.04 16 14 53 39 AV6
-0.14 7
14 53 71 AVS
-0.02 10 14 53 89 AV3
+0.02 9
14 53 90 AV6
+0.09 14 14 54 35 AV6
+0.11 13 14 54 35 AVS
-0.06 11 14 54 36 AV6
-0.22 10 14 54 37 AV4
+0.04 9
14 54 38 AV3
+0.09 12 14 54 47 AV6
+0.02 10 14 54 47 AVS
+0.02 12 14 54 56 AV6
-0.02 10 14 54 56 AV2
+0.04 9
14 54 56 AVS
-0.02 9
14 54 86 AV2
-0.09 15 14 54 87 AV6
+0.06 12 14 54 87 AV3
+0.04 9
14 54 87 AVS
+0.10 16 14 54 87 AV2
+0.13 11 14 55 42 AV6
-0.02 13 14 55 82 AV2
+0.02 11 14 55 83 AV6
+0.20 24 14 55 83 AV4
+0.17 12 14 55 83 AV2
+0.12 13 14 56 49 AV6
+0.04 8
14 56 so AV6
-0.02 12 14 56 57 AV6
+0.13 7
14 56 58 AV6
-0.02 13 14 56 71 AVS
-0.02 13 14 56 71 AV2
-0.11 10 14 56 81 AV1
-0.02 12 14 56 81 AV2
+0.02 11 14 56 81 AV3
-0.04 8
14 56 82 AV6
-0.02 8
14 56 82 AV2
+0.02 11 14 57 44 AV2
-0.09 12 Page 38 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (AVB WEAR)
SG Row Column Location Inch
%TW 14 57 46 AV6
+0.08 13 14 57 46 AV3
+0.02 10 14 57 46 AV2
-0.19 15 14 57 61 AV6
+0.11 15 14 57 70 AV6
-0.30 11 14 57 70 AVS
-0.07 12 14 57 70 AV2
-0.07 11 14 57 72 AV6
-0.02 12 14 57 79 AV3
-0.02 11 14 57 79 AV2
+0.07 11 14 58 47 AVS
-0.02 12 14 58 so AV1
+0.06 11 14 58 52 AV6
+0.04 13 14 58 54 AV1
-0.06 12 14 58 57 AV6
+0.08 15 14 58 61 AV1
+0.04 10 14 58 63 AV2
-0.07 11 14 58 64 AV1
-0.07 11 14 58 64 AV6
-0.02 13 14 58 64 AV2
-0.13 11 14 58 65 AV6
-0.02 13 14 58 70 AV1
+0.02 10 14 58 72 AV1
-0.04 7
14 58 74 AV2
-0.13 11 14 58 74 AV1
-0.13 12 14 58 76 AV2
+0.12 14 14 59 55 AV6
+0.08 20 14 59 55 AV2
+0.40 16 14 59 55 AV1
-0.35 12 14 59 57 AV1
-0.52 12 14 59 59 AV3
-0.09 12 14 59 60 AV1
+0.13 11 14 59 63 AV6
+0.11 12 14 59 64 AV1
-0.04 13 Page 39 of 39 LR-N18-0054 1R25 SERVICE INDUCED INDICATIONS (TSP WEAR)
SG Row Column Location
%TW 11 8
41 01H 6
11 47 24 03C 6
12 44 22 07C 4
12 53 33 03C 5
13 16 119 02C 6
13 20 5
02C 6
13 30 11 03C 10 13 53 85 01C 13 14 13 94 04H 5
14 17 119 02C 4
14 18 5
01C 5
14 18 5
02C 11 14 18 6
02C 6
14 26 116 02C 9
14 31 113 02C 10 14 33 111 02C 10 14 59 56 03C 8
Page 1 of 1 LR-N 18-0054 1R25 SERVICE INDUCED INDICATIONS (FBP WEAR)
SG Row Column Location 0/oTW 11 53 34 FBC 9
13 55 83 FBH 6
14 20 118 FBC 7
Page 1 of 1 LR-N 18-0054 SG 13 13 13 13 13 13 1 R25 SERVICE INDUCED INDICATIONS (FOREIGN OBJECT WEAR)
Axial Circumferential Row Column Location Length Extent (inches)
(Degrees) 2 91 03C -0.72 0.26 75 15 117 FBH +0.55 0.19 55 16 118 FBH +0.71 0.27 60 17 117 FBH +0.57 0.38 60 24 89 05C -0.78 0.23 55 55 53 TSC +0.19 0.29 60 Page 1 of 1 0/oTW 98 11 11 23 16 24