/03L-0:on 781007,during Cold Shutdown,Valve Pit Flooded While Draining Circulating Water Box D.Caused by Damage of Valve from Flooding
ML18113A595
Person / Time
Site: Surry 
Issue date: 10/31/1978
From: Raucom T
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
Shared Package
ML18113A593 List:
References
LER-78-035-03L, LER-78-35-3L, NUDOCS 7811060217
Download: ML18113A595 (2)


LER-1978-035, /03L-0:on 781007,during Cold Shutdown,Valve Pit Flooded While Draining Circulating Water Box D.Caused by Damage of Valve from Flooding
Event date:
Report date:
2811978035R03 - NRC Website

text

NRC FQRJ\\i366 (7-7~,*

U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT e CONTROL BLOCK:!

L _..___.__..,__.........,._....,_........ 10 (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) 1 o

GLJ l VI A I s Ip Is I 2 101 0 IO I - I O I O l O I O l O I O I O I O 101 41 11 11111 101 I 10 7

3 9

LICENSi:E CODE 14 15 LICENSE NUMBErl 25 26 LlCcNSc TYPE JO 57 CAT 58 CON'T

!IE]

7 a

~:~~~ L!:J©I o l s p I o I o I 2 I s I 1 101 11* o I o l 11 11 s 101 :y o I 3 I 11 1 I s I G) 60 61 DOCKET NUMBER 68 69 EVENT DATE 74 75 REPORT DATE 80 EVENT DESCRl?TION AND PROBABLE CONSEQUENCES (10)

I With the u..'1.it at cold shutdown, motoY operated valve NOV-SW-202B was found to be

[£TI]

inoperable in i_ts automatic mode, i.e. unable to shut automatically in response to

~

1a LOCA-p~~s-olackout event.

This condition is reportable in accordance with T S r

( ")

ITTIJ I *. o.o.~.o.

~ *

~22 valve was shut, therefore, the health and safety of the

~

!public

~

[Q]IJ 7

8 9

[£JI]

7 B

==

CAUSE

SUBCODE COMPONENT CODE COMP.

SUBCODE

!, i,~,

1C I~

~<.::) L.:_!\\:.V IV IA 11 IV 10 IP I~ ~@

l e-1

---..J 12 13 18 19 SEQUENTIAL OCCURRENCE REPORT REPORT NO.

CODE TYPE 10 /3 15 J I/I I 01 3J L!J 24 26 27 23 29 30 VALVE SU8CODE LU@

20 31 ACTION FUTu?:

5i-'"7D0WN Q

ATTACHMENT NPRD-4 TAKEN ACTIG:"11

"\\, :,_.:.:. -

\\:::,;..:OD HOURS ~ SUBMITTED FORM SUB.

PRIME C:OMP.

SUPPLIER REVISION NO.

LlU 32 COMPONENT MANUFACTURER 80 Li@I z;,?

i =*._3 ~ I 0 1 °1 °1 °1 -~@ ~@)

33 J4

==

36 37 40 41 42

~ IR 1 1 I 6 I 51@

CAUSE D::SCR!~::;~. :.~.;:; ::.'"?.::G,lVE ACTIONS@

43 44 47

!The motor *:':'e:-=.'.::2::,~c.:, da;naged by flooding of the valve pit by water pumped from

!Unit 2 conc.e.~er "D" Waterbox.

The flooded motor was replaced, thereby returning IJJI].

[!]}]

1the valve to a fully operable status.

QTI]

1 a

g 80 FACILITY STATUS

% ?CWER OTHER STATUS DJTI ~@ JOJO IO l@...___ ____

NA __

~

METHOD OF

~

DISCOVERY DISCOVERY DESCRIPTION ~

~~~[_O_p_e_r_a_t_o_r_o_b_s_e_r_v_a_t_i_*_o_n _________ _,

a g

10 12 11 44 ACTIVITY CONT::NT Q\\

RELEASED OF RELEAS:

AMOUNT OF ACTIVITY~

~

EJ@ W(§)l NA J

7 a

9 10 11 44 7

45 46 so NA

_LOCATION OF RELEASE @

45 so PERSONN::L EX?OSUR::5

~

NUMBER

{:;"::;,. TYP!:

DESCRIPTION

[iJl] 10 IO 10 J~@...___* ___

N_A ___________________ ___,

8 9

11 12 13 PERSONNEL INJURIES

~

NUMBER DESCRIPTION6 80 NA

~

[O 10 10 I@.

a 9

11

'-,2~-----------------------------------------'

8 0

7 LOSS OF OR DAMAGE TO FACILITY '4J' Tz'PE

DESCRIPTION

~

~

tJ@

1 a 91 ~o:---------~-----------------------------------8~0 NA PUBLICITY r;;,,.

1SSUEDC,;\\DESCRIPTION~

l'yjM-1) '1 0';.:' -..ff\\ ""11 NRC USE ONLY ITliJ ~ei._l ________

N=A:.:;__ ___

~_

.*. _... _i:_.i,,_.*.. _J-'":_.}_v_c,t...._____

II II I II II I II I~

7 8

9 10 68 69 80 ;

NAME OF ?REPARER __ T_._L_._B_a_u_c_o_m _________ _

PHONE: --.a.( 8_0_4_.:)_3_5_7_-_3_18_4 ___ _

0 [I.

1---- -.

..I-'.,--.,.-

I

  • * (AttacJ-im.ent~ Page 1.1)

Surry Power-Station, Unit 2 Docket No: 50-281 Report No: 78-035/0JL-0 Event Date: 10-7-78 Failed Motor Operator on Service Water Valve

1. Description of Event

During a cold shutdown period, the valve pit, containing HOV-SW-202B, was flooded while draining the circulating water box D.

The valve operator was 3~~rted by the flooding and the valve became inoperable in its automatic_-

i:!Ode.

The valve is required to shut automatically on "LOCA-plus-blackout"

£or c~rculating ~a~er conservation.

="e £ail::=-~ 2= the automatic function of the valve because of damage to the ~-:-'-=~,,~or :::o~""~ ----.~stitutes a condition that is reportable in accordance

,.;it::.

-=-.-;-,,,,...e_-::-, :':::-:::<:::..::::_cation 6.6.2.b.(2).

2.

Proo2-.=_2 -:::o:-.:s2::e:.:,==:c::S and Status of Redundant Systems:

-:::::,::':! -,--=2.,-=: ::C!DV-3W-202B incorporates an auto-close function as a means of conse=-:-'~g c::..::-=-~a=i__~g water during LOCA-plus-blackout ~onditions.

The valve was --....: ____ ::::e =2.uure was discovered and remained shut until the operator was -.-"'-:;--- -:-=-,-.

-:::.2 health and safety of the public were not affected.
3.

Cause

--"' s 2-.-e::1:::: occurred because a drain line _could not accept the volume of water-::~~ i:ron condenser 2-CN-SC-lB (D-Waterbox) to station drain to facili=.s_te 2 -,.::-;ntenance operatio_n.

The water filled the valve pit, containing the 1*1017-s:;-2023, thereby shorting out the motor.

4.

Immediace Cor=ective Action:

The valve pit was pumped out, and the motor tested for grounds caused by the water.

5.

Subsequent Corrective Action:

The motor was replaced and the valve was made operable in all respects.

6.

Actions Taken to Prevent Recurrence:

Personnel are instructed to control the pump discharge so as not to endanger adjacent equipment.

7.

Generic Implications:

None, the failure occurred due to water penetration of the electrical components.