Notice of Violation from Insp on 970908-1019.Violation Noted:From 970909-16,valves 1FP186 & 1FP187 Were Closed, Isolating All Fire Protection Water to Units 1 & 2 Auxiliary & Containments
ML18106A166
Person / Time
Site: Salem  PSEG icon.png
Issue date: 11/18/1997
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML18106A165 List:
References
50-272-97-18, 50-311-97-18, NUDOCS 9711250206
Download: ML18106A166 (2)


Text

APPENDIX A NOTICE OF VIOLATION Public Service Electric and Gas Company Salem Nuclear Generating Station Docket Nos:50-272 50-311 License Nos:DPR-70 DPR-75 Units 1 and 2 During an NRC inspection conducted from September 8, 1997 through October 19, 1997, a violation of NRC requirements was identified. In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," NUREG-1600, the violation is listed below:

A.

License Conditions 2.C(5) (Unit 1) and 2.C(10) (Unit 2) require that the licensee implement and maintain in effect all provisions of the approved fire protection program as described in the Updated Final Safety Analysis Report (UFSAR).

UFSAR, Section 9.5.1.4.1, describes systems and components which are necessary for post-fire safe shutdown of Salem Units 1 and 2, including the auxiliary feedwater (AFW) pumps and other safety-related equipment. UFSAR Section

9. 5. 1. 7. 2, describes the water-based fire suppression systems which are utilized at Salem Units 1 and 2, and the components which they protect. For example, the AFW pumps are protected by two water sprinkler systems.

Procedure SC.FP-SV.FS-003(Q), "Fire Water Flowpath Verification," requires that the fire protection isolation valves to the Unit 1 and 2 auxiliary building and containments, 1FP186 and 1FP187, be in the open position.

Contrary to the above, from approximately September 9-1 6, 1997, valves 1FP186 and 1FP187 were closed, which isolated all fire protection water to the Salem Unit 1 and 2 auxiliary buildings and containments. This isolated water to the water-based suppression systems in those buildings, rendering the systems inoperable, and adversely affecting the licensee's ability to achieve and maintain safe shutdown in the event of a fire.

This is a Severity Level IV violation (Supplement 1 ).

Pursuant to the provisions of 10 CFR 2.201, Pubic Service Electric and Gas Company is hereby required to submit a written statement or explanation to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administrator, Region I, and a copy to the NRC Resident Inspector at the facility that is the subject of this Notice, within 30 days of the date of the letter transmitting this Notice of Violation (Notice). This reply should be clearly marked as a "Reply to a Notice of Violation" and sh~uld include for each violation: (1) the reason for the violation, or, if contested, the basis for disputing the violation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieved. Your 9711250206 971118 PDR ADOCK 05000272 Q

PDR

2 response may reference or include previous docketed correspondence, if the correspondence adequately addresses the required response. If an adequate reply is not received within the time specified in this Notice, an order or a Demand for Information may be issued as to why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to extending the response time.

Because your response will be placed in the NRC Public Document Room (PDR), to the extent possible, it should not include any personal privacy, proprietary, or safeguards information so that it can be placed in the PDR without redaction. If personal privacy or proprietary information is necessary to provide an acceptable response, then please provide a bracketed copy of your response that identifies the information that should be protected and a redacted copy of your response that deletes such information. If you request withholding of such material, you must specifically identify the portions of your response that you seek to have withheld and provide in detail the bases for your claim of withholding (e.g., explain why the disclosure of information will create an unwarranted invasion of personal privacy or provide the information required by 10 CFR 2. 790(b) to support a request for withholding confidential commercial or financial information). If safeguards information is necessary to provide an acceptable response, please provide the level of protection described in 10 CFR 73.21.

Dated at King of Prussia, Pennsylvania this 18th day of November, 1 997.