ML18102B462
| ML18102B462 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 07/24/1997 |
| From: | Olshan L NRC (Affiliation Not Assigned) |
| To: | Eliason L Public Service Enterprise Group |
| References | |
| TAC-M95691, TAC-M95692, NUDOCS 9707300205 | |
| Download: ML18102B462 (3) | |
Text
- ..
i--*
Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit Public S~rvice Electric & Gas Company Post Office Box 236 Hancocks Bridge, NJ 08038
.ly 24, 1997
SUBJECT:
CLARIFICATION OF LICENSING BASIS FOR CONTROL AREA AIR CONDITIONING SYSTEM, SALEM NUCLEAR GENERATING STATION, UNITS 1 AND 2 (TAC NOS. M95691 AND M95692)
Dear Mr. Eliason:
Your June 10, 1996, application for Amendment Nos. 190 and 173, which were issued on February 6, 1997, stated that the control room doses could be maintained within the limits of General Design Criterion 19 provided that operator action is taken to manually position a failed damper.
By letter dated June 30, 1997, you indicated that this statement is inaccurate since you have not prepared a separate dose assessment, which models a damper failure mitigated by operator action.
You further stated that this scenario goes
- beyond the NRC-approved licensing and design basis.
We have reviewed your June 30, 1997, letter and agree that a separate dose assessment modeling a damper failure mitigated by operator action is not required and goes beyond the NRC-approved licensing and design basis.
We appreciate your letter clarifying the statement made in your June 10, 1996, application for amendment.
Docket Nos. 50-272/311 cc:
See next page DISTRIBUTION Docket File PUBLIC PDI-2 Reading BBoger JStolz LOlshan MO' Brien OGC ACRS JLinville, RGN-I OFFICE
~PDI-2/PM NAME
~)LOlshan:rb DATE 1 /6 /97 OFFICIAL RECORD COPY DOCUMENT NAr1[: __ _S_l\\_95691. GEN __ ~
Sincerel/,
/s Leonard N. Olshan, Senior Project Manager Project Directorate I-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
(------ -9707300205 970724 i
PDR ADOCK 05000272 I
p PDR Dfvl I\\~
l UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 July 24, 1997 Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit Public Service Electric & Gas Company.
Post Office Box 236 Hancocks Bridge, NJ 08038
SUBJECT:
CLARIFICATION OF LICENSING BASIS FOR CONTROL AREA AIR CONDITIONING SYSTEM, SALEM NUCLEAR GENERATING STATION, UNITS 1 AND 2 (TAC NOS. M95691 AND M95692)
Dear Mr. Eliason:
Your June 10, 1996, application for Amendment Nos. 190 and 173, which were issued on February 6, 1997, stated that the control room doses could be maintained within the limits of General Design Criterion 19 provided that operator action is taken to manually position a failed damper.
By letter dated June 30, 1997, you indicated that this statement is inaccurate since you have not prepared a separate dose assessment, which models a damper failure mitigated by operator action.
You further stated that this scenario goes beyond the NRC-approved licensing and design basis.
We have reviewed your June 30, 1997, letter and agree that a separate dose assessment modeling a damper failure mitigated by operator action is not required and goes beyond the NRC-approved licensing and design basis.
We appreciate your letter clarifying the statement made in your June 10, 1996, application for amendment.
Docket Nos. 50-272/311 cc:
See next page Sincerely, dd~1 V'
t L f/./ ty!,..,
Leonard N. Olshan, Senior Project Manager Project Directorate 1-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
... Mr. Leon R. Eliason Ii> * ~'
Public Service Electric & Gas*
Company cc:
Mark J. Wetterhahn, Esquire Winston & Strawn 1400 L Street NW Washington, DC 20005-3502 Richard Fryling, Jr., Esquire Law Department - Tower 5E 80 Park Place Newark, NJ 07101 Mr. D. F. Garchow General Manager - Salem Operations Salem Generating Station P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Louis Storz Sr. Vice President - Nuclear Operations Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038 Mr. Charles S. Marschall, Senior Resident Inspector Salem Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Maryland Office of People's Counsel 6 St. Paul Street, 21st Floor Suite 2102 Baltimore, Maryland 21202 Ms. R. A. Kankus Joint Owner Affairs PECO Energy Company 965 Chesterbrook Blvd., 63C-5 Wayne, PA 19087 Mr. Elbert Simpson Salem Nucleariltenerating Station, Units 1 and 2 Richard Hartung Electric Service Evaluation Board of Regulatory Commissioners 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Lower Alloways Creek Township c/o Mary 0. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Mr. David R. Powell, Manager Licensing and Regulation Nuclear Business Unit P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. David Wersan Assistant Consumer Advocate Office of Consumer Advocate 1425 Strawberry Square Harrisburg, PA 17120 P. M. Goetz MGR. Joint Generation Atlantic Energy 6801 Black Horse Pike Egg Harbor Twp., NJ 08234-4130 Carl D. Schaefer External Operations - Nuclear Delmarva Power & Light Company P.O. Box 231 Wilmington, DE 19899 Public Service Commission of Maryland Engineering Division Chief Engineer 6 St. Paul Centre Baltimore, MD 21202-6806 Senior Vice President - Nuclear Engineering Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038