ML18102A718

From kanterella
Jump to navigation Jump to search
Forwards Update of ERDS Data Point Library
ML18102A718
Person / Time
Site: Salem 
Issue date: 01/02/1997
From: Dawn Powell
Public Service Enterprise Group
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LR-N96420, NUDOCS 9701070219
Download: ML18102A718 (13)


Text

OPS~G*

Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038-0236 Nuclear Business Unit

. " 1"' 0 () *19q7

.J/'.l'i

~ '* -*

LR-N96420 US Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

UPDATE OF EMERGENCY RESPONSE DATA SYSTEM (ERDS)

DATA POINT LIBRARY SALEM GENERATING STATION UNIT 2 DOCKET NO. 50-311 In accordance with 10CFR50 Appendix E Section VI.3.a, Public Service Electric and Gas (PSE&G) is notifying the NRC of changes to the Salem Unit 2 ERDS Data Point Library (DPL).

These changes affected the alarm/trip setpoints of ERDS data points U2R0044AS, U2R0046AS, U2R0046BS, U2R0046CS, and U2R0046DS.

The changes to the DPL are enclosed.

If you have any questions regarding this submittal, please contact us.

Enclosure 9701070219 970102 PDR ADOCK 05000311 p

PDR The pmn~r is in your hands.

Sincerely, David R. Powell Manager - Licensing and Regulation

\\

95-2168 REV. 6/94

..J !\\ i\\j 0 2 1997 Document Control Desk 2

LR-N96420 C

Mr. Hubert J. Miller, Administrator -

Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Mr. L. N. Olshan, Licensing Project Manager -

Salem U. S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Mail Stop 14E21 Rockville, MD 20852 Mr. c. Marschall (X24)

USNRC Senior Resident Inspector Mr. K. Tosch, Manager, IV Bureau of Nuclear Engineering 33 Arctic Parkway CN 415 Trenton, NJ 08625

Document Control Desk LR-N96420 3

  • J/~N 0 2 1997 BC Senior Vice President - Nuclear Engineering (N19)

Senior Vice President - Nuclear Operations (X04)

General Manager -

Salem Operations (S05)

Director -

QA/NSR (XOl)

Manager - Nuclear Safety Review (N38)

Manager - Joint Owners/Ext. Aff. Interface (N28)

Onsite Safety Review Engineer - Salem (X15)

Station Licensing Engineer -

Salem (X09)

E. Sellover P. Robinson Records Management (N21)

Microfilm Copy File Nos. 1.2.1, 5.25

DATA POINT LIBRARY REFERENCE FILE Date:

12/09/96 Reactor Unit:

SA2 Data Feeder:

SPDS NRC EROS Parameter:

CNTMNT RAD Point ID:

U2R0044AS Plant Spec Point Desc.:

R44A CNTMT POST LOCA RAD MON Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power-supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

RADIATION LEVEL IN CONTAINMENT A

R/HR LOG lEO 1E7 NA NA s

001 NA IN CONTAINMENT HI:lOO.O, HIHI:600.0 NA NA LOW Level Reference Leg:

NA Record No. 37 Page 1 of 2

  • DATA*POINT LIBRARY REFERENCE FILE CONT.

NRC EROS Parameter:

CNTMNT RAD Point ID:

U2R0044AS Plant Spec Point Desc.:

R44A CNTMT POST LOCA RAD MON Unique System Desc.:

PROVIDES INDICATION OF GENERAL RADIATION LEVEL INSIDE CONTAINMENT.

Record No. 37 Page 2 of 2

DATA POINT LIBRARY REFERENCE FILE Date:

12/09/96 Reactor Unit:

SA2 Data Feeder:

SPDS NRC EROS Parameter:

MAIN SL 2 Point ID:

U2R0046AS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46A Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

STM GEN2 STM LINE RAD LEVEL A

MR/HR NA 0.1 10,000 NA NA s

001 NA BLDG 04, EL. 100 HI:4.0, HIHI:7.0 NA NA LOW Level Reference Leg:

NA Record No. 38 Page 1 of 2

  • DATA' POINT LIBRARY REFERENCE FILE CONT.

NRC EROS Parameter:

MAIN SL 2 Point ID:

U2R0046AS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46A Unique System Desc.:

ENG. RANGE EQUIVALENT TO 0.1 TO 5000 uci/cc XE-133. PROVIDES INDICATION OF RADIOACTIVITY WITHIN MAIN STEAM LINE.

Record No. 38 Page 2 of 2

DATA POINT LIBRARY REFERENCE FILE Date:

12/09/96 Reactor unit:

SA2 Data Feeder:

SPDS NRC EROS Parameter:

MAIN SL 4 Point ID:

U2R0046BS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46B Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig states:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip set Points:

NI Detector Power Supply cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

STM GEN4 STM LINE RAD LEVEL A

MR/HR LOG SCALE 0.1 10,000 NA NA s

001 NA BLDG 04, EL. 100 HI:4.0, HIHI:7.0 NA NA LOW Level Reference Leg:

NA Record No. 39 Page 1 of 2

  • DATA POINT LIBRARY REFERENCE FILE CONT.

NRC EROS Parameter:

MAIN SL 4 Point ID:

U2R0046BS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46B Unique System Desc.:

ENG. RANGE EQUIVALENT TO 0.1 TO 5000 uCi/cc XE-133. PROVIDES INDICATION OF RADIOACTIVITY WITHIN MAIN STEAM LINE.

Record No. 39 Page 2 of 2

DATA POINT LIBRARY REFERENCE FILE Date:

12/09/96 Reactor Unit:

SA2 Data Feeder:

SPDS NRC EROS Parameter:

MAIN SL 1 Point ID:

U2R0046CS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46C Generic/Cond Desc.:

STM GENl STM LINE RAD LEVEL Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

A MR/HR LOG SCALE 0.1 10,000 NA NA s

001 NA BLDG 04, EL. 100 HI:4.0, HIHI:7.0 NA NA LOW Level Reference Leg:

NA Record No. 40 Page 1 of 2

  • DATA POINT LIBRARY REFERENCE FILE CONT.

NRC EROS Parameter:

MAIN SL 1 Point ID:

U2R0046CS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46C Unique System Desc.:

ENG. RANGE EQUIVALENT TO 0.1 TO 5000 uCi/cc XE-133. PROVIDES INDICATION OF RADIOACTIVITY WITHIN MAIN STEAM LINE.

Record No. 40 Page 2 of 2

DATA POINT LIBRARY REFERENCE FILE Date:

12/09/96 Reactor Unit:

SA2 Data Feeder:

SPDS NRC EROS Parameter:

MAIN SL 3 Point ID:

U2R0046DS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46D Generic/Cond Desc.:

An~log/Digital:

Engr Units/Dig States:

Engr units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power supply TUrn-on Power Level:

Instrument Failure Mode:

Temperature compensation For DP Transmitters:

STM GEN3 STM LINE RAD LEVEL A

MR/HR LOG SCALE 0.1 10,000 NA NA s

001 NA BLDG 04, EL. 100 HI:4.0, HIHI:7.0 NA NA LOW Level Reference Leg:

NA Record No. 41 Page 1 of 2

ii

  • DATA" POINT LIBRARY REFERENCE FILE CONT.

NRC EROS Parameter:

MAIN SL 3 Point ID:

U2R0046DS Plant Spec Point Desc.:

MAIN STEAM RAD MON R46D Unique System Desc.:

ENG. RANGE EQUIVALENT TO 0.1 TO 5000 uci/cc XE-133. PROVIDES INDICATION OF RADIOACTIVITY WITHIN MAIN STEAM LINE.

Record No. 41 Page 2 of 2