Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit Public Service Electric and Gas Company Post Office Box 236.

Hancocks Bridge, NJ 08038 SUBJECT!

CHAN~ES TO TECHNICAL SPECIFICATION BASES 3/4.8.3, SALEM NUCLEAR GENERATING STATION, UNITS 1 AND 2 (TAC NOS. M94418 AND M94419)

Dear Mr. Eliason:

By letter dated November 28, 1995, you submitted a proposed change to the Technical.Spe~ification (TS) Bases, Section 3/4.8.3, for Salem Nuclear

.Generattng*station, Units'l and 2.

The*chan~e wai made as part of Revision 14 to the Updated Final Safety Affalysis R~port (UFSAR)~ dated December 28, 1995, that removed the containment penetration overcurrent protective device Tables 8.3-4A and 8.3-4B from the UFSAR.

This information is now controlled by Engineering Calculations ES-13.0lO(Q). for Unit 1 and ES-13.005(Q) for Unit 2.

We understand that a 50.59 evaluation will be conducted prior to making any changes to these calculations. This is similar to the process used when these tables were in the UFSAR~ Reference to these Engineering Calculations has been added to the UFSAR.

The staff has reviewed your proposed change to TS Bases Section 3/4.8.3 and finds it acceptable to control the information concerning the containment penetration overcurrent protective devices in the Engineered Calculations instead of the UFSAR.

Therefore, the proposed change to TS Bases 3/4.8.3 is acceptable.

Enclosed is a copy of the revised Bases page B 3/4 8-2 for each unit.

Docket Nos. 50-272/50-311

Enclosure:

As stated cc w/encl:

See next page DISTRIBUTION:

Docket File PUBLIC PDI-2 Reading SVarga JStolz MO'Brien(2)

LOlshan OGC ACRS Sincerely,

/SI Leonard L. Olshan, Project Manager Project Directorate I-2

  • Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation LNicholson, RGN-I JCalvo GHi 11 (2)
  • ~

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555--0001 Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit Public Service Electric and Gas Company Post Office Box 236 Hancocks Bridge, NJ 08038 March 14, 1996

SUBJECT:

CHANGES TO TECHNICAL SPECIFICATION BASES 3/4.8.3, SALEM NUCLEAR GENERATING STATION, UNITS 1 AND 2 (TAC NOS. M94418 AND M94419)

Dear Mr. Eliason:

By letter dated November 28, 1995, you submitted a proposed change to the Technical Specification (TS) Bases, Section 3/4.8.3, for Salem Nuclear Generating Station, Units 1 and 2.

The change was made as part of Revision 14 to the Updated Final Safety Analysis Report (UFSAR), dated December 28, 1995, that removed the containment penetration overcurrent protective device Tables 8.3-4A and 8.3-4B from the UFSAR.

This information is now controlled by Engineering Calculations ES-13.0lO(Q) for Unit 1 and ES-13.005(Q) for Unit 2.

We understand that a 50.59 evaluation will be conducted prior to making any changes to these calculations. This is similar to the process used when these tables were in the UFSAR.

Reference to these Engineering Calculations has been added to the UFSAR.

The staff has reviewed your proposed change to TS Bases Section 3/4~8.3 and finds it acceptable to control the information concerning the containment penetration overcurrent protective devices in the Engineered Calculations instead of the UFSAR.

Therefore, the proposed change to TS Bases 3/4.8.3 is acceptable.

Enclosed is a copy of the revised Bases page B 3/4 8-2 for each unit.

Docket Nos. 50-272/50-311

Enclosure:

As stated cc w/encl:

See next page Sincerely,

~~9~

Leonard L.

Olshan~ Project Manager Project Directorate 1-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Mr.. Leon R. Eliason e Public Service Electric & Gas Company cc:

Mark J. Wetterhahn, Esquire Winston & Strawn 1400 L Street NW Washington, DC 20005-3502 Richard Fryling, Jr., Esquire Law Department - Tower 5E 80 Park Place Newark, NJ 07101 Mr. Clay Warren General Manager - Salem Operations Salem Generating Station P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Louis Storz Sr. Vice President - Nuclear Operations Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038 Mr. Charles S. Marschall, Senior Resident Inspector Salem Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Maryland Office of People's Counsel 6 St. Paul Street, 21st Floor Suite 2102 Baltimore, Maryland 21202 Ms. R. A. Kankus Joint Owner Affairs PECO Energy Company 965 Chesterbrook Blvd., 63C-5 Wayne, PA 19087 Mr. Elbert Simpson Salem Nucle~enerating Station, Units 1 and 2 Richard Hartung Electric Service Evaluation Board of Regulatory Commissioners 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Lower Alloways Creek Township c/o Mary 0. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Mr. Frank X. Thomson, Jr., Manager Licensing and Regulation Nuclear Department P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. David Wersan Assistant Consumer Advocate Office of Consumer Advocate 1425 Strawberry Square Harrisburg, PA 17120 Ms. P. J. Curham MGR. Joint Generation Department Atlantic Electric Company P.O. Box 1500 6801 Black Horse Pike Pleasantville, NJ 08232 Carl D. Schaefer External Operations - Nuclear Delmarva Power & Light Company P.O. Box 231 Wilmington, DE 19899 Public Service Commission of Maryland Engineering Division Chief Engineer 6 St. Paul Centre Baltimore, MD 21202-6806 Senior Vice President - Nuclear Engineering Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038

3/4.8 ELECTRICAL POWER SYSTEMS BASES (Continued) case circuit breakers and lower voltage circuit breakers are grouped into representative samples which are then tested on a rotating basis to ensure that all breakers are tested.

If a wide variety exists within any manufacturer's brand of molded case or lower voltage circuit breakers, it is necessary to further divide that manufacturer's breakers into groups and treat each group as a separate type of breaker for surveillance purposes.

Containment penetration conductor overcurrent protective device information is provided in the UFSAR.

SALEM -

UNIT 1 B 3/4 8-2 Revised by NRC Letter dated March 14. 199*

ELECTRICAL POWER SYSTEMS BASES (Continued) case circuit breakers and lower voltage circuit breakers are grouped into representative samples which are then tested on a rotating basis to ensure that all breakers are tested.

If a wide variety exists within any manufacturer's brand of molded case or lower voltage circuit breakers, it is necessary to further divide that manufacturer's breakers into groups and treat each group as a separate type of breaker for surveillance purposes.

Containment penetration conductor overcurrent protective device information is provided in the UFSAR.

SALEM -

UNIT 2 B 3/4 8-2 Revised by NRC Letter dated March 14, 1996