Responds to Ltr Requesting Approval of ASME Code Case N-523, Mechanical Clamping Devices for Class 2 & 3 Piping. Request Denied at This Time & Pse&G Should Request Relief from ASME Code as Described in GL 90-05
ML18101B172
Person / Time
Site: Salem, Hope Creek  
Issue date: 01/11/1996
From: Stolz J
NRC (Affiliation Not Assigned)
To: Eliason L
Public Service Enterprise Group
References
GL-90-05, GL-90-5, TAC-M93831, TAC-M93832, TAC-M93833, NUDOCS 9601180419
Download: ML18101B172 (4)


Text

Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit Public Service Electric & Gas Company Post Office Box 236 Hancocks Bridge, NJ 08038 January 1~1996

SUBJECT:

ASME CODE CASE N-523, HOPE CREEK GENERATING STATION AND SALEM GENERATING STATION, UNITS 1 AND 2 (TAC NOS. M93831, M93832 AND M93833)

Dear Mr. Eliason:

By letter dated October 10, 1995, Public Service Electric and Gas Company (PSE&G) requested approval for use of ASME Code Case N-523, "Mechanical Clamping Devices for Class 2 and 3 Piping".

We note in your letter that Code Case N-523 would be used to provide temporary repairs for moderate energy piping systems 6 inches and smaller and for high energy piping systems 2 inches and smaller. After reviewing the October 10, 1995 letter, we find that we cannot approve the requested use of ASME Code Case N-523 at this time.

The NRC has not, as yet, endorsed ASME Code Case N-523.

Until endorsement of ASME Code Case N-523, we request that you continue to use the guidance contained in Generic Letter (GL) 90-05, "Guidance for Performing Temporary Non-Code Repair of ASME Code Case 1, 2 and 3 Piping" which the NRC issued on June 15, 1990.

If, in the course of performing temporary non-code repairs, PSE&G chooses to use the provisions of ASME Code Case N-523, PSE&G should request specific relief from the ASME Code as described in GL 90-05.

~601~804i9 960111 PDR ADOCK 05000272 P

PDR Sincerely,

/S/

John F. Stolz, Director Project Directorate I-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation Docket Nos. 50-272/311/354 cc:

See next page DISTRIBUTION Docket File PUBLIC PDI-2 Reading SVarga/JZwolinski JStolz DJaffe/LOlshan

  • Previously Concurred MO'Brien OGC ACRS JStrosnider LNicholson, RGN-I OFFICE EMCB*

EMEB~

NAME JStrosnider RWessman I /11 /9(,

12/28/95 01/04/95

Ii

.,_~p..R REG(/

~c, *

(..,

UNITED STATES

' -iJ;e;¥"'011"

/..;

~

(')

<C 0

NUCLEAR REGULATORY COMMISSION Iii

~

~

~

WASHINGTON, D.C. 20555-0001 p;

~

~

~

~o

        • -ti.

Mr. Leon R. Eliason Chief Nuclear Officer & President-Nuclear Business Unit Public Service Electric & Gas Company Post Office Box 236 Hancocks Bridge, NJ 08038 January 11, 1996

SUBJECT:

ASME CODE CASE N-523, HOPE CREEK GENERATING STATION AND SALEM GENERATING STATION, UNITS 1 AND 2 {TAC NOS. M93831, M938l2 AND M93833)

Dear Mr.

Elia~on:

By letter dated October 10, 1995, Public Service Electric and Gas Company

{PSE&G) requested approval for use of ASME Code Case N-523, "Mechanical Clamping Devices for Class 2 and 3 Piping".

We note in your letter that Code Case N-523 would be used to provide temporary repairs for moderate energy piping systems 6 inches and smaller and for high energy piping systems 2 inches and smaller. After reviewing the October 10, 1995 letter, we find that we cannot approve the requested use of ASME Code Case N-523 at this time.

The NRC has not, as yet, endorsed ASME Code Case N-523.

Until endorsement of ASME Code Case N-523, we request that you continue to use the guidance contained in Generic Letter {GL) 90-05, "Guidance for Performing Temporary Non-Code Repair of ASME Code Case 1, 2 and 3 Piping" which the NRC issued on June 15, 1990.

If, in the course of performing temporary non-code repairs, PSE&G chooses to use the provisions of ASME Code Case N-523, PSE&G should request specific relief from the ASME Code as described in GL 90-05.

Docket Nos. 50-272/311/354 cc:

See next page Sincerely,

/.

~o~n F. Stolz, Director oject Directorate 1-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

(.-

Mr. Leon R. Eliason Public Service Electric & Gas Company cc:

Mark J. Wetterhahn, Esquire Winston & Strawn 1400 L Street NW Washington, DC 20005-3502 Richard Fryling, Jr., Esquire Law Department - Tower SE 80 Park Place Newark, NJ 07101 Mr. Clay Warren General Manager - Salem Operations Salem Generating Station P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. L. F. Storz Sr. V.P. - Nuclear Operations Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038 Mr. Charles S. Marschall, Senior Resident Inspector Salem Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ - 08625-0415 Maryland Office of People's Counsel 6 St. Paul Street, 21st Floor Suite 2102 Baltimore, Maryland 21202 Ms. R. A. Kankus Joint Owner Affairs PECO Energy Company 965 Chesterbrook Blvd., 63C-5 Wayne, PA 19087 Salem Nuclear Generating Station, Units 1 and 2, and Hope Creek Generating Station Richard Hartung Electric Service Evaluation Board of Regulatory Commissioners 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Lower Alloways Creek Township c/o Mary 0. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Mr. D. R. Powell, Manager Licensing and Regulation Nuclear Business Unit P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. David Wersan Assistant Consumer Advocate Office-of Consumer Advocate 1425 Strawberry Square Harrisburg, PA 17120 Ms. P. J. Curham MGR. Joint Generation Department Atlantic Electric Company P.O. Box 1500 6801 Black Horse Pike Pleasantville, NJ 08232 Carl D. Schaefer External Operations - Nuclear Delmarva Power & Light Company P.0. Box 231 Wilmington, DE 19899 Public Service Commission of Maryland Engineering Division Chief Engineer 6 St. Paul Centre Baltimore, MD 21202-6806

Mr. Leon R. Eliason Public Service Electric & Gas Company cc:

Hope Creek Resident Inspector U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, New Jersey 08038 Mr. M. E. Reddemann General Manager - Hope Creek Operations Hope Creek Generating Station P.O. Box 236 Hancocks Bridge, New Jersey 08038

  • Salem Nuclear Generating Station, Unit I and 2, and Hope Creek Generating Station Mr. E. C. Simpson Sr. V.P. - Nuclear Engineering Nuclear Department P.O. Box 236 Hancocks Bridge, New Jersey 08038