0PERATING DATA REPORT Docket No.50-272 Date:

~1~2--~2~-~8~8=--~~~~

Completed by Pell White Telephone: 935-6000 Extension: ~4~4~5~1~--~~~~-

Operating Status

1.

Unit Name Salem No. 1 Notes

2.

Reporting Period November 1988

3.

Licensed Thermal Power (MWt) 3411

4.

Nameplate Rating (Gross MWe) 1170

5.

Design Electrical Rating (Net MWe) 1115

6.

Maximum Dependable Capacity(Gross MWe)1149

7.

Maximum Dependable Capacity (Net MWe) 1106

8.

If Changes Occur in Capacity Ratings (items 3 through 7) since Last Report, Give Reason N/A

~~~~~~~-~~~~~-~~~-~~~~~~~~~-~

9.

Power Level to Which Restricted, if any (Net MWe)

N/A

~~~~~~~~~~~~

10. Reasons for Restrictions, if any N/A

~~--~~~~-~~-~~~~--~~~

This Month

11. Hours in Reporting Period 720
12. No. of Hrs. Reactor was Critical 720
13. Reactor Reserve Shutdown Hrs.

0

14. Hours Generator On-Line 7_2_0-~-
15. Unit Reserve Shutdown Hours 0
16. Gross Thermal Energy Generated ------

(MWH) 2459421. 6

17. Gross Elec. Energy Generated (MWH) 829390
18. Net Elec. Energy Generated (MWH) 796412
19. Unit Service Factor 100 2 0. Unit Availability Factor 100
21. Unit Capacity Factor (using MDC Net) 100
22. Unit Capacity Factor (using DER Net)
99. 2 2 3. Unit Forced Outage Rate 0

Year to Date 8040 6193. 1 0

6100. 1 0

20639712.4 6900910 6592010 75.9 75.9 74.1 73.5 3.4 Cumulative 100129 63888.2 0

61891. 9 0

192908721. 2 64095400 60988219

61. 8
61. 8 55.1 54.6 22.6
24. Shutdowns scheduled over next 6 months (type, date and duration of each)

Refueling outage scheduled for April 9, 1989 and lasting approximately 55 da s.

25. If shutdown at end of Report Period, Estimated Date of Startup:

N/A 8-1-7. R2

-*=.. =* *t *-, *t 90271 8:31 :l ::::o -

- l. ()C::j()(l(l27:L PDR ADU~~ ---*poc R

UNIT SHUTDOWN AND POWER REDUCTIONS REPORT MONTH NOVEMBER 1988 Docket No.50-272 Salem No.1 12-2-88 Completed by Art Orticelle Unit Name Date Telephone Extension 609-935-6000 No.

Date N/A 1

F: Forced S: Scheduled Type 1

Duration Hours Reason 2

Method of Shutting Down Reactor License Event Report 2 Reason A-Equipment Failure-explain B-Maintenance or Test C-Refueling D-Regulatory Restriction E-Operator Training & Licensing Exam F-Administrative G-Operational Error-explain H-Other-explain System Code 4 3 Method 1-Manual Component Code 5 2-Manual Scram.

3-Automatic Scram.

4-Continuation of Previous Outage 5-Load Reduction 9-0ther 44 51 Cause and Corrective Action to Prevent Recurrence 4 Exhibit G Instructions for Prepara-tion of Data Entry Sheets for Licensee Event Report (LER) File (NUREG 0161) 5 Exhibit 1 Salem as Source

880907063 870616056 871211120 880225078 880519094 880815186 PSE&G SALEM GENERATING STATION SAFETY RELATED WORK ORDER LOG SALEM UNIT 1 l

1 STATION AIR COMP. 28V. CONTROL BEZEL BREAKER FAILURE DESCRIPTION:

TRIPS/TROUBLESHOOT.

1 1XD5922 FAILURE DESCRIPTION:

12 REACTOR NOZZLE SUPPORT FAN HIGH TEMP ALARM IS IN.

1 llB DG FAILURE DESCRIPTION:

llB DG START AIR COMP RESET BUTTON/BROKEN/REWORK.

1 14 MS189 FAILURE DESCRIPTION:

LEAK THRU/REWORK F-8.

1 11 CONT AREA EMER A.C. FAN MTR FAILURE DESCRIPTION:

VIBRATING/REWORK.

1 lC 125V BTRY CHGR FAILURE DESCRIPTION:

EQUALIZING TIMER DEFECTIVE/REWORK.

e 1

WO NO 880823075 880824124 880901282 881003121 881102118 881122103 SALEM UNIT 1 UNIT EQUIPMENT IDENTIFICATION 1

12 EMERG. LTG. INVERTER DC INPUT VOLTAGE INDICATION FAILURE DESCRIPTION:

TROUBLESHOOT.

1 1CV18 FAILURE DESCRIPTION:

LETDOWN PRESS VLV/NOT CONTROLLING/TROUBLESHOOT.

1 11AF40 FAILURE DESCRIPTION:

VALVE FAILED TO CLOSE/REPAIR.

1 12SW158 12 RHR RM CLR VLV FAILURE DESCRIPTION:

FAILED OPEN/TROUBLESHOOT.

1 13 CONTROL AREA SPLY FAN FAILURE DESCRIPTION:

NO START INDICATION/REWORK.

1

  1. 12 BAT PUMP FAILURE DESCRIPTION:

FAILED MECHANICAL SEAL ON #12 BAT PUMP REPAIR/

REPLACE.

I I

'.. ' ~~OR PLANT MODIFICATIONS REPORT MONTH NOVEMBER 1988

  • OCR NO.

PRINCIPAL SYSTEM lSM-0194 Circulating Water lSM-0420 Radiation Monitoring

  • DCR - Design Change Request e

DOCKET NO.:

50-272 UNIT NAME:

Salem l DATE:

December 10, 1988 COMPLETED BY: P. White TE LE PHONE :

---=6,..;0_,,9.....,/'"""3,...,,3-=9,__.....,4'""'4'"""5'""5,----

DESCRIPTION This design change provided power for llA, 13A, and 12B Circulators from the Hope Creek 13KV substation.

This modification was to reduce the load on Salem Station power and auxiliary power transformers to improve the station voltage profile and reduce the level of fault current available.

This design change modified the wiring on the R19 monitors such that the automatic functions come from the alarm circuitry.

MA00R PLANT MODIFICATIONS DOCKET NO.:

50-272 REPORT MONTH NOVEMBER 1988 UNIT NAME:

Salem 1

  • DCR lSM-0194 lSM-0420 DATE:

COMPLETED BY:

TELEPHONE:

December 10, 1988 P. White 609/339-4455 SAFETY EVALUATION 10 CFR 50.59 This modification did not jeopardize the Hope Creek Station as their 13KV bus and 500-13KV transformers were originally designed for the load of two Hope Creek plants.

There was no change to any plant process or discharge or to the environmental impact of the plant.

No unreviewed safety or environmental questions are involved.

This design change was based on the results of a study performed by Radiation Protection.

There was no change to any plant process or discharge or to the environmental impact of the plant.

No unreviewed safety or environmental questions are involved.

DCR -

Design Change Request

.. u SALEM UNIT NO. 1 SALEM GENERATING STATION MONTHLY OPERATING

SUMMARY

UNIT NO. 1 NOVEMBER 1988 The Unit began the month operating at full power and continued to operate at essentially full power for the entire period.

REFUELING INFORMATION DOCKET NO.:

50-272 COMPLETED BY:

P. White UNIT NAME:

Salem 1 DATE:

TELEPHONE:

EXTENSION:

December 10, 1988 609/935-6000 4497 Month NOVEMBER 1988

1.

Refueling information has changed from last month:

YES NO X

2.

Scheduled date for next refueling:

April 15, 1989

3.

Scheduled date for restart following refueling: May 30, 1989

4.

A)

Will Technical Specification changes or other license amendments be required?

YES NO NOT DETERMINED TO DATE X

B)

Has the reload fuel design been reviewed by the Station Operating Review Committee?

YES NO X

If no, when is it scheduled?

February 1989

5.

Scheduled date(s) for submitting proposed licensing action:

February if required

6.

Important licensing considerations associated with refueling:

7.
8.
9.

NONE Number of Fuel Assemblies:

A)

Inc ore B)

In Spent Fuel Storage Present licensed spent fuel storage capacity:

Future spent fuel storage capacity:

Date of last refueling that can be discharged to spent fuel pool assuming the present licensed capacity:

8-l-7.R4 193 464 1170 1170 September 2001

AVERAGE DAILY UNIT POWER LEVEL Completed by Art Orticelle Docket No.

Unit Name Date Telephone Extension Month NOVEMBER 1988 Day Average Daily Power Level Day Average Daily (MWe-NET)

(MWe-NET) 1 1100 17 1109 2

1114 18 1098 3

1108 19 1036 4

1100 20 1122 5

1116 21 1086 6

1103 22 1109 7

1116 23 1095 8

1102 24 1102 9

1095 25 1102 10 1119 26 1105 11 1110 27 1092 12 1104 28 1127 13 1105 29 1093 14 1109 30 1121 15 1106 31 16 1109 P. 8.1-7 Rl 50*-272 Salem # 1 12-2-88 609-935-6000 4451 Power Level

PS~G Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Dear Sir:

MONTHLY OPERATING REPORT SALEM NO.

1 DOCKET NO. 50-272 Decem_ber 11, 1988 In compliance with Section 6.9.1.6, Reporting Requirements for the Salem Technical Specifications, the original copy of the monthly operating reports for the month of November 1988 are being sent to you.

RH:sl Average Daily Unit Power Level Operating Data Report Unit Shutdowns and Power Reductions Safety Related Maintenance Major Plant Modification Operating Summary Refueling Information Sincerely yours,