Public Service Electric and Gas Company Stanley LaBruna Public Service Electric and Gas Company P.O. Box 236: Hancocks Bridge, NJ 08038 609-339-4800 V:ce Pres:cent - Nuclear Operations NOV 1 4 1988 NLR-N88189 United states Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:
RESPONSE TO NRC BULLETIN 88-03 SALEM GENERATING STATION UNIT NO. 2 DOCKET NO. 50-311 Public Service Electric and Gas Company {PSE&G) has received the subject NRC Bulletin regarding potential inadequate latch engagement in GE HFA latching-type relays.
The information requested by this Bulletin as it relates to Salem Unit 2 is provided in the enclosure to this letter.
Should you have any questions with regard to this transmittal, please do not hesitate to contact us.
c Mr. J. c. Stone Licensing Project Manager Ms. K. Halvey Gibson,_ Acting senior Resident Inspector Sincerely, Mr. w. T. Russell, Administrator Region I Ms. J. Moon, Interim Chief
.New.Jersey Department of Environmental Division of Environmental Quality Bureau of Nuclear Engineering CN 415 Trenton, NJ 08625 8811220290 881114 PDR ADOCK 05000311 G
PNU Protection
.rc11
-'I I
STATE OF NEW JERSEY COUNTY OF SALEM
)
SS.
)
REF: RESPONSE TO NRC BULLETIN 88-03 Stanley LaBruna, being duly sworn-according to law deposes and says:
I am Vice President - Nuclear Operations of Public Service Electric and Gas Company, and as such, I find the matters set forth in our letter dated October 14, 1988
, concerning the Salem Generating Station, Unit No. 2, are true to the best of my knowledge, information and belief.
Subscribed and sworn t~ befo7e me thiJJ /.fwd-day of..;..~------"-'
~t../.
--~L 1988
~L'i:ofNew Jersey lARAINE Y. BEARD Notary Public of New Jeraey My Commission Expires May 1, 1991 My commission 'expires on --~~~~~~~~~~~~~--
I RESPONSE TO BULLETIN 88-03 SALEM GENERATING STATION UNIT NO. 2 DOCKET NO. 50-311 ENCLOSURE The purpose of this bulletin was to request licensees to perform inspections to ensure that all GE latching-type HFA relays installed in safety-related applications have adequate latch engagement and that those relays which fail to meet acceptance criteria be repaired or replaced.
The bulletin requested a letter of confirmation that the inspection had been completed and a summary of the number of relays inspected and any corrective actions taken.
This information is presented below as it relates to Salem Unit 2.
RESPONSE
The NRC Bulletin 88-03 GE HFA latching-type relay inspection for Salem Unit 2 was performed in October 1988 during the Fourth Refueling outage.
Documentation reviews and field examination revealed twenty-one (21) HFA latching-type relays, seven in each of the three emergency diesel generator control cabinets.
The relays all have *the Model No. 12HFA54Hl87H.
All of these relays were checked in accordance with a special test procedure (T-233) written to address those criteria noted in the Actions Requested portion of the NRC Bulletin 88-03.
The results of the examinations of all the relays were found to be satisfactory~ The Procedure T-233 data sheets are available onsite for inspection, if requested.
Until alternatively designed relays are made available which remedy the problem noted in NRC Bulletin 88-03, spare GE HFA latching-type relays of the model noted above have been ordered for replacement-in-kind applications, if replacement should be necessary in the future.
These spare relays will be inspected in accordance with the criteria of NRC Bulletin 88-03 upon receipt.