ML18092A750
| ML18092A750 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 01/21/1985 |
| From: | Public Service Enterprise Group |
| To: | |
| Shared Package | |
| ML18092A749 | List: |
| References | |
| M3Q-2, NUDOCS 8508290139 | |
| Download: ML18092A750 (80) | |
Text
I MAINTENANCE PROCEDURE All-1 ENCLOSURE 1 PROCEDURE APPROVAL COVER SHEET PROCEDURE NUMBER : __.
.;.;M3;;..Q~-.;;;2 _______ _
REVISION NUMBER:
8
--___;;~---
TITLE: REACTOR TRIP AND REACTOR TRIP BYPASS AIR CIRCUIT BREAKER SEMI-ANNUAL INSPECTION LUBRICATION AND TESTING REMARKS:
THIS PROCEDURE IS SAFE'rY RELATED.
ALL DOCUMENTATION SHALL BE MAINTAINED IN ACCORDANCE WITH ADMINISTRATIVE PROCEDURE (AP) 11 RECORD RETENTION PROGRAM.
TRIS PROCEDURE HAS BEEN REVIEWED.AND DETEBMINED TO BE IN COMPLIANCE WITH TECHNICAL SPECIFICATION REQUIREMENTS. '
UNIT #1 T.S. 4.3.1.1.1 UNIT #2 T.S. 4.3.1.1.
SUMMARY
OF REVISION: 1)
INCORPORATE APPLICABLE ITEMS ADDRESSED IN S-C-RlOO-NFD-081 REV. 9.
APPROVAL:
- 2)
INCORPORATE OTSC #1 AND 112.
q_ i.2."~
- 3)
SWAPPED STEPS !r.1;;¢::3 AND 9.12.4
- 4)
MOVED SHUNT TRIP TIMING (STEP 9. 11. 2) TO STEP 9.16 SUBMITTED/DATE:
ENGINEERING/DATE:
1 /-/ B-8:S-I I - I ?3-t;S NDE LEVEL III/DATE:
QAD/DATE:
MAINT. MGR./DATE:
SORC CHAIRMAN/NUMBER/DATE:
GEN. MGR. SALEM OPS./DATE:
A-11-1 Page 1 of 1
'/
I /-I B-i.:>>-
Rev *. o
I*
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 M3Q-2 SALEM GENERATING STATION MAINTENANCE DEPARTMENT MANUAL MAINTENANCE PROCEDURE M3Q-2 INDEX STEP TITLE PURPOSE APPLICABILITY/SCOPE REFERENCES ENCLOSURES RESPONSIBILITIES PRECAUTIONS.AND LIMITATIONS PREREQUISITES PROCEDURE 9.1 EQUIPMENT SETUP AND BREAKER CLOSURE TIMING 9.2 BREAKER U/V TRIP TIMING 9.3 BREAKER SHUNT TRIP TIMING 9.4 TRIP BAR AND U/V TRIP LEVER FORCE MEASUREMENT
.9~5 U/V TRIP ATTACHMENT CO.IL DROP OUT VOLTAGE TEST 9.6 INSPECTION AND ADJUSTMENT OF CONTACTS 9.7 BREAKER CLEANING AND INSPECTION 9.8 OPERATING MECHANISM CHECKs 9.9 CLOSING COIL INSPECTION AND REPLACEMENT 9.10 CONTROL RELAY INSPECTION 9~11 SHUNT TRIP INSPECTION 9.12 U/V TRIP ATTACHMENT 9.12.1 INSPECTION
- 9. 12.2 LUBRICATION Page l of 54 PAGE 3
3 3
3 4
4 4
5 10 10 12 13 14 16 17 20 23 24 25 28 30 31 33
- Rev. 8
INDEX (continued)
STEP.
9.12.3 COIL TEST 9.12.4 DROP OUT VOLTAGE TEST 9.13 U/V TRIP ATTACHMENT REPLACEMENT 9.14 MEASUREMENT OF TRIP BAR AND U/V TRIP LEVER FORCES
- 9. 15 BREAKER U /V TRIP TIMING 9.16 SHUNT TRIP TIMING 9.17 BREAKER CLOSURE T~ING 9.18 BREAKER MEGGER READINGS 9.19.RIGHT RAIL STOP LATCH INSPECTION 10.0 FINAL TESTING M3Q-2 Page 2 of 55 PAGE 36 37 38 44 46 47 48*
49 49 50 7
Rev. 8
1.0 TITLE SALEM GENERATING STATION MAINTENANCE DEPARTMENT MANUAL MAINTENANCE PROCEDURE M3Q-2 REACTOR TRIP AND REACTOR TRIP BYPASS AIR CIRCUIT BREAKER INSPECTION, LUBRICATION AND TESTING (Unit 1 T.S. 4.3.1.1.l and Unit 2 T.S. 4.3.1.1) 2.0 PURPOSE The purpose of this procedure is to guide personnel conducting semi-annual and refueling outage inspection, lubrication and testing of the Reactor Trip and Reactor Trip Bypass ACB's and replacement of selected components.
3.0 APPLICABILITY/SCOPE 4.0 3.1 APPLICABILITY.
This procedure is applicable to the Westinghouse Air Circuit Breakers (Model DB-50) used in the Salem Units Ul and #2 Reactor Trip and Reactor Trip Bypass applications.
3.2 SCOPE This procedure provides guidance for the periodic inspection and testing of the Under Voltage Trip Attachment (UVTA), Shunt Trip Attachment, Closing.Coil, Control Relay and Breaker Operating Mechanism.
Additionally, the periodic lubrication of.the UVTA and the force measurements of the Trip Bar and Under Voltage Trip.Lever are addressed.
REFERENCES 4.1 Westinghouse Technical Manual - Low Voltage Enclosed Switchgear (DB50 ACB), P.S.B.P. 301107, Issue U2.
4.2 West~nghouse Technical Manual - Replacement Instructions for Reactor Trip Switchgear Undervoltage Attachment, PSBP 127879, Issue U 4.
4.3 Public Service Field Directive S-C-RlOO-NFD-081-Rev. 9.
4.4 Westinghouse Letter NCD-ELEC-18 dated December 17, 1971.
4.5 Westinghouse EMS, WES2196 to NES380 dated March 4, 1984 and March 7, 1983.
4.6 Reactor Trip Breaker Controls wiring diagram, Public Service Drawing Number 203646 Rev. 7.
4.7 PSE&G Letters to NRC dated March 14, 1983 and April 28, 1983.
4.8 Public Service Safety Evaluation S-C-R-120-CSE-254.
4.9* Unit l Technical Specification 4.3.1.1.1 and Unit 2 Technical Specification 4.3.1.l.
M3Q-2 Page 3 of 55 Rev. 8
- 5. 0 ENCLOSURES.
5.1 - Cross Sectional Views of Type DB-50 Ci_rcui t Breaker.
S.2 Enclosure 2 - Breaker Serial Numbers and Positions 5.3 Enclosure~3 - Closing Solenoid - Construction Details 5.4 Enclosure 4 - Control Relay and Auxiliary Switch-Adjustment and Construction Details 5.5 Enclosure 5 - Shunt Trip Attachment - Location and Construction Details 5.6 Enclosure 6 - Undervoltage Trip Attachment - Construction and Lubrication Details 5.1 Enclosure 7 - Data Sheet
- 5~8 Enclosure 8 - Breaker "As Found"/"As Left" positions 5.9 Enclosure 9 - Repeated Verification of Undervoltage Trip Attachment Test 5.10 Enclosure 10 Overcurrent Trip Bracke~ Locations and Dust Cover Modification 5.11 1 - U/V arid Shunt Trip Coil Resistance vs Temperature Curves 5.12 Enclosure 12 - Trip Bar and UVTA Force Measurement Details.
6.0 RESPONSIBILITIES 6.1 It is the responsibility of the Maintenance Supervisor in charge of the test to ensure that notification is made to the Nuclear Regulatory Commission via the Senior Shift Supervisor whenever any data on Enclosure 7 is out of specification or an undervoltage trip device failure has occurred.
This notification must be made in one hour in accordanc~ with Reference 4.9. Prior to any corrective action being taken, Nuclear Plant Engineering must also be notified.
7.0 PRECAUTIONS AND LIMITATIONS M3Q-2 7.1 When working around electrical equipment. safety precautions and work habits specified in the Electric Production Department Safety Manual shall be observed by all personnel involved.
7.2 Except for use in cleaning of removed arc chutes, avoid the use of high pressure air. Dirt, grit or other substances can be driven into spaces between parts creating friction, which would not otherwise occur.
The maximum allowable air pressure is thirty (30)
- Page 4 of 55 Rev. 8
- 7. 3 If a** new or spare breaker is to be installed, inspect for the following:
- 1.
over current trip brackets shall be removed from trip bar.
If found installed, no action shall be taken without contacting Nuclear Engineering Department and Westinghouse Manager -
Operat1.ng Plant Projects.
(See Ref 4.3).
- 2.
Ensure the dust cover modifications, as specified in Design Change Packages 1EC1617 and 2EC1618, have been performed.
Refer to Enclosure 10 for Items l and 2.
- 3.
Ensure trip button cover pin modification has been performed in accordance with DR 84-3262 -
~crofilm 1367-0697.
7.4 In addition to the normal precautions taken when working around electrical equipment as specified in the Electric Production Department Safety manual, care must be taken to stand clear of the various mechanical mechanisms associated with these breakers.
7.5 Before any Maintenance work is performed, make certain that all control circuits are open and that the breaker is removed from the metal-clad unit.
7.6 Solvents shall only be of the type specified, and shall only be used;'
on the points specified, in this procedure
- 7.7 No modification or adjustment should be made to this equipment without first evaluating the impact of these actions on SAFETY.
Non-approved modifications or adjustments shall not be made.
7.8 Lubricant used in this procedure is flammable.
Ensure adequate ventilation and observe all necessary precautions and procedures.
Avoid prolonged exposure to skin.
Refer to Reference 4.3 for specific handling precautions.
8.0 PREREQUISITES M3Q-2 8.1 Properly calibrated digital multimeter, contact pyrometer, and calibrated megger will be required.
8.2 Calibration Data EQUIPMENT NOMENCLATURE.
(l) _____
(2) _____
(3) _____
(4) _____
EQUIPMENT SERIAL NUMBER CALIBRATION DATE Page 5 of 55 CALIBRATION DUE DATE Rev. 8
M3Q-2 8.3 The supervisor in charge of the test should enter U/V Trip Attachment Coil "reference" and previous drop out voltage values on Enclosure 7, step 9.12.3.d prior to starting the testing.
NOTE:
IF CIRCUIT BREAKER ?wjAINTENANCE IS BEING PERFORMED IN CONJUNCTION WITH MAINTENANCE PROCEDURE M3Q-3 DELETE STEPS 8. 4 AND 8. 5 AND PROCEED WITH STEP 9.0.
8.4 The semi-annual maintenance of the circuit breakers shall be performed in the following sequence:
8.4.1 A Reactor Trip ByPass Breaker 8.4.2 B Reactor Trip Bypass Breaker 8.4.3 A Reactor Trip Breaker 8.4.4 B Reactor Trip Breaker 8.5 Pre~Maintenance Notification Requirements:
8.5.1 Maintenance Supervisor circles the circuit breaker designation, enters the unit prefix, notifies I&C Department and proceeds to the indicated required step
- A Reactor Trip Bypass Breaker - Go to Step a B Reactor Trip Bypass Breaker -
Go to Step A Reactor Trip Breaker - Go to Step c B reactor Trip Breaker Go to Step d I&C Department Notification:
I&C Supervisor Date/Time Maintenance Supervisor Date/Time
- a.
A Reactor Trip Bypass Breaker (1)
Obtain permission of the Senior Shift/Shift Supervisor to remove the breaker from cubicle.
Senior Shift/Shift Supervisor Date Page 6 of 55 b
Rev. 8
M3Q-2 (2)
(3)
If the breaker has a cycle counter installed, record the number of cycles on the counter prior to testing on Enclosure 7
- Enter the breaker serial number on Enclosure 8 and proceed to Step 9.0 to commence actual maintenance.
- b.
B Reactor Trip Bypass Breaker (1)
Obtain permission of the Senior Shift/Shift to remove the breaker from cubicle.
Senior Shift/Shift Supervisor Date (2)
If the breaker has a cycle coutlter installed, record the number of cycles on the counter prior to test~ng on Enclosure 7.
(3)
Enter the breaker serial number on Enclosure 8 and proceed to Step 9.0 to commence actual maintenance.
- c.
A Reactor Trip Breaker (l) Notify the Senior I&C Supervisor that the I&C Department must* set up to perform SSPS trip test of A Reactor Trip Breaker due to maintenance.
(2)
Obtain confirmation from the Senior I&C Supervisor/
Cognizant I&C Supervisor that required testing set up is complete.
I&C Senior/Supervisor Date Time.
(3)
Inform the Senior Shift Supervisor/Shift Supervisor of requirement to remove the A Reactor Trip Breaker and to install the B Reactor Trip Bypass in the A Trip position.
(4)
Obtain permission of the Senior Shift Supervisor/
Shift Supervisor and assist Operations Department in the actual circuit breaker transfer.
Senior Supervisor/Supervisor Date T:ime Page 7 of SS Rev. 8
M3Q-2 (5)
SUPERVISOR WITNESS INSPECTION HOLD POINT After the circuit breaker transfer verify with the cognizant I&C Supervisor and the Shift Supervisor that testing has been completed on the A
Reactor Trip Breaker* position and the system has been returned to normal.
Shift Supervisor Date Time I&C Supervisor.
Date Time Quality Assurance Date Time (6) If the breaker has a cycle counter installed, record the number of cycles on the counter prior tq testing on Enclosure 7.
(7)
Enter the serial number of the circuit breaker just removed on Enclosure 8.
- d.
B Reactor Trip Breaker (1)
Notify the Senior I&C Supervisor that the I&C Department must set up to perform SSPS trip test of B Reactor Trip Breaker due to maintenance.
(2)
Obtain confirmation from the Senior I&C Supervisor/
Cognizant I&C Supervisor that required testing set_up is complete.
I&C Senior/Supervisor*
Date Time (3)
Inform the Senior Shift Superiiisor/Shift Supervisor of requirement to remove the B Reactor Trip Breaker and to install the A Reactor Trip Bypass in the B Trip position.
(4)
Obtain permission of the. Senior Shift Supervisor/
Shift Supervisor and assist Operations Department in the actual circuit breaker transfer.
Senior Supervisor/Supervisor Date Time Page 8 of SS (SW)
Rev. 8
M3Q-2 (5)
SUPERVISOR WITNESS INSPECTION.HOLD POINT After the circuit breaker transfer verify with the cognizant I&C Supervisor and the Shift Supervisor that testing has been completed on the B
Reactor Trip Breaker position and the system has been returned to normal.
Shift Supervisor Date Time I&:C Supervisor Date Time Quality Assurance Date Time (6)
If the breaker has a cycle c9unter installed, record the number of cycles on the counter prior to testing on Enclosure 7.
(7)
Enter the serial number of the circuit breaker just removed on Enclosure 8
(IHP)
Rev. 8
9.0 PROCEDURE NOTE:
ENCLOSURE 8 WILL BE USED TO RECORD ANY CHANGE IN BREAKER POSITION FROM THE NORMAL POSITION INDICATED ON ENCLOSURE 2, WHEN ALL MAINTENANCE WORK IS COMPLETED.
9.1 EQUIPMENT SETUP AND BREAKER -CLOSURE TIMING 9.1.1 Connect a 43t2VDC source through a 2 pole test switch (43VDC Test Switch) to control st.abs 1111 and H12.
This.
will be the supply voltage to the UV trip attachment.
9.1.2 Connect a 125VDC test source to control stabs #1 and #8 and con~ect a momentary push button between control stabs Hl and #2.
This will be the supply voltage for the control relay and the closing coil.
9.1.3 Connect visicorder channels for the following traces:
- a.
Three channels for the three (3) main breaker contacts.
Jumper all three (3) line side stabs together, and connect one channel per phase on the load side.
9.1. l 9.1.2 9.1.3.a.
- b.
One channel across the load side of the 43VDC test switch. -----
I
.j M3Q-2
- c.
One channel -on breaker control stabs #2 and HS for breaker closure voltage (125VDC).
9.1. 4.BREAKER CLOSURE TIMING ~
~ u)
SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Energize 43VDC power supply, then close 43VDC test switch.
Verify the voltage is 43 t 2VDC, adjust power supply if necessary.
- b.
Energize 125VDC power supply. *
- c.
Start visicorder.
- d.
Close the 125VDC test switch, depress the test.push button and release.
Note that the breaker closes.
- e.
Stop visicorder.
- f.
Open 125VDC. test switch.
- g.
Open 43VDC test switch.
Note that the breaker trips.
Page 10 of 55 9.1.3.b 9.1.3.c (SW)
(IHP) 9.1.4.a 9.1.4.b 9.1.4.c 9.1.4.d 9.1.4.e 9.1.4.f 9.1.4.g Rev. 8
.I
- 1
- h.
De-energize 43VDC and 12SVDC power supplies.
- i.
Remove visicorder trace and identify same.
Record closing time on Enclo~ure 7.
NOTE:
RECORD THE FOLLOWING INFORMATION ON EACH TRACE:
- 1.
Breaker serial number (S/N) and position
- 2.
Visicorder Speed (10 IN/SEC.)
- 3.
Timing Frequency (60 Hz)
- 4.
Indicate paper direction S.
Timing Line period (0.01 SEC.)
- 6.
Procedure number M3Q-2
- 7.
Date
- 8. Electrician/Test Engineer Signature
- 9.
Opening Time or Closing Time
- 10.
"QA Record - Retain in Accordance with APll"
- j. Repeat steps a through i.two (2) more times. Verify that there were no failures.
Page 11 of SS 9.1.4.h 9.1.4.i 9.1.4.j Rev. 8 *
' 9. 2 BREAKER UV TRIP TIMING
~ 'v
~
M3Q-2 SUPERVISOR WITNESS INSPECTION HOLD POINT 9.2.l Raise and lower the trip bar by hand to assure it does not bind; i.e., it should feel like a free weight.
9.2.2 Energize 43VDC power supply 9.2.3 Close 43VDC test switch 9.2.4 Manually close the breaker 9.2.5 Start_visicorder 9.2.6 Open the 43VDC test switch.
Note that the breaker trips.
9.2.7 Stop visicorder 9.2.8 De-energize 43VDC power supply.
9.2.9 Remove visicorder trace and identify same.
See step 9.1.4.i for required information.
Record trip time on Enclosure 7.
9.2.10 Repeat steps 9.2.2 through 9.2.9 two (2) more times.
Verify that there were no failures
- Page 12 of 55 (SW)
(IHP) 9.2.l 9.2.2 9.2.3 9.2.4 9.2.5 9.2.6 9.2.7 9.2.8 9.2.9
-~
Rev. 8
9.3 BREAKER SHUNT TRIP TIMING M3Q-2 SUPERVISOR WITNESS INSPECTION HOLD POINT 9.3.l Re~ove 125VDC power supply from breaker control stabs #1 and
- 8 and reconnect to control stabs #3 and #7.
9.3.2 Disconnect visicorder from stabs #2 and #8 and reconnect to 113 and 117.
9.3.3 Energize 125VDC and 43VDC power supplies.
9.3.4 Close 43VDC test switch.
9.3.5 Manually close the breaker.
9.3.6 Start visicorder.
9.3.7 Close 125VDC test switch.
Note that the breaker trips.
9.3.8 Stop visicorder and open 125VDC test switch.
9.3.9 Remove visicorder trace and identify same.
See step 9.1.4.1 for required information.
Record trip time on Enclosure 7.
9.3.10 Repeat steps 9.3.5 through 9.3.9 two (2) more times.
Verify that there were no failures.
9.3.11 De-energize 125VDC and 43VDC power supplies.
Page 13 of 55 (SW)
(IHP) 9.3.l 9.3.2 9.3.3 9.3.4 9.3.5 9.3.6 9.3.*7 9.3.8 9.3.9 9.3.10 9.3.11.
Rev. 8
9.4 TRIP BAR AND U/V TRIP LEVER FORCE MEASUREMENT NOTE:
THE FAILURE OF AN UNDERVOLTAGE TRIP ATTACHMENT MUST BE REPORTED TO THE NUCLEAR REGULATORY COMMISSION.
IF AN UNDERVOLTAGE TRIP ATTACHMENT FAILS A TEST, NOTIFY THE SENIOR SHIFT SUPERVISOR IMMEDIATELY.
DO NOT CONTINUE WITH THE PROCEDURE UNTIL FURTHER DIRECTION IS OBTAINED FROM THE NUCLEAR ENGINEERING DEPARTMENT.
9.4.1 Enter calibration data on all equipment required for measurements:
EQUIPMENT NOMENCLATURE WEIGHT STAND WEIGHT SET WEIGHT SET EQUIPMENT SERIAL NUMBER
- 9. 4. 2 TRIP BAR FORCE MEASUREMENT SUPERVISOR WITNESS INSPECTION HOLD POINT CALIBRATioN DATE CALIBRATION DUE DATE
- a.
Energize the 43VDC power suppiy and close the 43VDC test switch to energize the UV trip attachment.
- b.
Manually close the breaker.
- c.
Add weights in 10 gram increments via pulley arrangement shown on Enclosure 12, Figure 1, until the breaker trips.
- d.
Record total weight (weights and weight stand) added to
-the bar, on Enclosure 7.
- e.
Repeat steps (b), (c) and (d) two more times.
Verify* that there were no failures.
(SW)
(IHP)
M3Q-2 9.4.3 UVTA FORCE MEASUREMENT SUPERVISOR WITNESS INSPECTION HOLD POINT a.~ Load the trip bar with 460 grams of weight as shown on 2.
- b.
Energize the UVTA and manually close the breaker.
- c.
Attempt to trip the breaker by de-energizing the UVTA:
- d. If the breaker fails to trip at or below 460 grams, notify the Senior Shift Supervisor.
Do not.. continue with the procedure until further direction is obtained from Nuclear Engineering Department:
- e. If breaker tripped:
- 1.
Increase weight on trip bar in 60 gram increments and repeat steps (b) and (c) until the breaker fails to trip.
- -2.
Record, on Enclosure 7, the total amount of weight (weights and weightstand) on the.trip bar when the breaker fails to trip.
- f. *** Remove 60 grams from.the trip bar; Repeat steps (H), (c),
- (d), and (e), two more times.
Verify there were no failures.
Page 15 of 55 (SW)
(IHP)
Rev. 8
9.5 M3Q-2 U/V TRIP ATTACHMENT COIL DROP OUT VOLTAGE TEST SUPERVISOR WITNESS INSPECTION HOLD POINT 9.5.1 Close 43VDC test switch.
9.5.2 Adjust voltage to approximately 43VDC.
9.5.3 Manually close the breaker.
9.5.4 Slowly turn the variable potentiometer to decrease the voltage.
(Approximately 15 sec/volt when approaching the drop out voltage). Monitor the voltage and record on the voltage at which the breaker trips open (Undervoltage Trip Attachment Coil drop' out voltage).
9.5.5 Repeat steps 9.5.2 through 9.5.4 two (2) more times. Verify that there-were no failures.
9.5.6 De-energize the test equipment and remove all test equipment.
Page 16 of 55 I
(SW)
(IHP) 9.5.1 9.5.2 9.5.3 9.5.4
~
- 9. 5. 6_
Rev. 8°
9.6 INSPECTION AND ADJUSTMENT OF CONTACTS M3Q-2 SUPERVISOR WITNESS INSPECTiON HOLD POINT 9.6.l ARCING CONTACTS
- a.
Remove arc chutes, dust cover control relay cover and three (3) auxiliary switch covers.
- b.
Inspect the Arcing Contacts for rough or high spots.
If necessary to dress the contacts, dress with a file or aluminum oxide paper. If replacement is not required, proceed to step 9.6.2. If replacment is required, continue with step 9.6.1.c.
- c. If replacement of the arcing contact is required proceed as follows:
(1)
Open the breaker.
(2)
Remove the Stationary Arcing Contacts.
(3)
Remove the Moving Arcing Contacts.
(4)
Install new Moving Arc Contacts.
(S)
Install new Stationary Arcing Contacts.
9.6.2 MAIN CONTACTS Visually inspect the mating surf aces of the movable and stationary contacts for any evidence of pitting or corrosion.
NOTE:
IF THE MA.IN CONTACTS SHOW EVIDENCE OF PI'ITING OR* BURNING CONTACT WESTINGHOUSE NUCLEAR SERVICE DIVISION AND PUBLIC SERVICE NUCLEAR ENGINEERING DEPARTMENT FOR FURTHER EVALUATION.
(HIP) 9.6.1.a 9.6.1.c.,(l) 9.6.1.c. (2) 9.6.1.c.(3) 9.6.1.c.(4) 9.6.1.c. (S) 9.6.2 Rev. 8
9.6.3 M3Q-2 CONTACT ADJUSTMENT The DB-50 Arcing Contacts should touch first on closing, open last on opening.
Contact pressure on the main contacts is maintained by adjusting gap "G" to be.050 -.*093 inches.
(See Enclosure #1).
- a.
Energize the undervoltage trip coil with 43 t2 VDC by connecting 43 VDC source to control stabs #11 and #12.
- b.
Slowly close the breaker, verify that arcing contacts close before main contacts.
- c. Measure the "As Found" gap "G" using the "go-no-go" gauge which has a.050" feeler gauge on one end and a
.093" gauge on the other. *Indicate satisfactory or unsatisfactory on Enclosure 7 for "As Found" condition.
If adjustment of contact gap is not necessary, open the breaker and proceed to Step 9.7. If adjustment is necessary, proceed with Step 9.6.3.d.
- d.
Perform contact adjustment as follows:
NOTE:
TO INCREASE THE GAP TURN INSULATING LINK COUNTERCLOCKWISE.
TO DECREASE THE GAP TURN INSULATING LINK CLOCK-WISE.
1/2 TURN CHANGES THE GAP BY APPROXIMATELY.010 TO.015 INCHES.
CAUTION!
DO-NOT OVERADJUST AS THIS WILL CAUSE THE CONTACT SPRINGS TO COMPRESS TO THE SOLID POSITION AND THUS INCREASE THE CLOSING EFFORT.
CHECK FOR OVER ADJUSTMENT BY PRYING THE STATIONARY ARC TIPS OPEN TO AT LEAST 1/16 INCH GAP.
IF CORRECT G GAP CANNOT BE OBTAINED BY THE ADJUSTMENT STATED, CONTACT WESTINGHOUSE ELECTRIC NUCLEAR SERVICES DIVISION AND PUBLIC SERVICE NUCLEAR ENGINEERING DEPARTMENT.
Page 18 of 55 Rev. 8
M3Q-2 Adjust the contact gap by opening the breaker and removing the crossbar, then screwing the insulating link in or out on the stud.
Be sure to tighten the lock nuts after each adjustment.
Measure gap "G" as described above and record "As Left" contact gap on Enclosure 7.
9.6.4 Inspect the auxiliary switches as follows:
- a.
Manually operate breaker and check contact engagement in the breaker "CLOSED" and "OPEN" positions.
- b.
Inspect contacts for burning and pitting.
- c.
Check mounting bolts.
9.6.5 Inspect the secondary disconnecting devices for abnonnal wear and overheating.
- a. Devices may be cleaned using specified solvent.
- b.
If discoloration, due to overheating or abnormal wear is observed, notify t~e Electrical Supervisor.
Page 19 of 5.5 9.6.3.d 9.6.4 9.6.5 Rev. 8
9.7 M3Q-2 BREAKER CLEANING AND INSPECTION 9.7.1 Breaker Inspection prior to cleaning
- SUPERVISOR WITNESS INSPECTION HOLD POINT CAUTION:
THE INTENT OF THE TIGHTNESS VERIFICATION IS TO. ENSURE THE CONNECTIONS ARE NOT LOOSE.
DO NOT FORCE OR OVERTIGHTEN THE FASTENERS.
- a.
Check all nuts, washers*, bolts, cotter pins and terminal connections for tightness.* Notify Supervisor of deficient conditions.
- b.
Check pole bases for cracks and cleanliness.
- c.
Check insulating links for cracks and cleanliness.
Check for tightness of adjustment locknut.
- d.
Check crossbar for looseness by moving main contacts laterally (refer to Enclosure 6). *
- e.
Check all tru arc rings are on the pins properly. If replacements are required, assemble with flat side of ring to the outside.
- f.
Visually check the physical condition of the cell interlock and verify proper operation of the interlock as follows:
- 1.
With the breaker out of the cubicle at the test location, verify there is a minimum clearance of 1/4" between the cell interlock tab and the breaker trip bar.
This will allow for a rise of the cell interlock arm position of approximately 1/8" when the breaker is inserted into the cubicle.
Adjust the cell interlock tab as necessary to obtain the required clearance. Manipulate the cell interlock tab in a sideways motion.
Verify that movement is not excessive and does not reduce the clearance between the cell interlock tab and the breaker trip bar to less than 1/4" (excessive sideways movement of the cell interlock could cause this clearance to be reduced)
- Page 20 of 55 (SW')
(IHP) 9.7.1.a 9.7.1.b 9.7.1.. c
. 9.7.1.e 9.7.1.f(l)
Rev. 8*
MJQ-2
- 2.
With the breaker out of the cubicle, test the cell interlock mechanism by closing the breaker, operating the cell interlock mechanism-and verifying that the breaker trips *
- 3. Verify that the cell interlock arm, tab, and stop pin are undistorted.
- g.
Verify inertia latch operates freely by moving with a finger.
(Located to the left side of breaker mechanism housing).
- h.
Inspect all wiring and wiring insulation to make sure no damage has resulted during operation.
- i. Inspect for the presence of dust, dirt and other types of foreign substances or contaminants,*including moisture and rust. Look for loose, damaged, broken or distorted parts. Check for signs of excessive heating, burning or arcing.
Examine the breaker for signs of rubbing; wearing, or stress.
- j. Inspect arc chutes for heavy erosion or broken plates.
Damaged chutes should be replaced.
9.7.2 BREAKER CLEANING
- a.
Clean and check the tightness of the control circuit stabs.
- b.
Thoroughly clean the equipment.
Cleaning should consist of wiping with paper towels or lint-free cloths to remove dust and dirt. In some cases, brushing with a medium bristle or stiff brush may be necessary.
Do not use a wire brush.
Brushing may be supplemented by vacuuming.
If sticky or gummy substances are present, a mild solvent such as Stoddards Solvent may be used.
The preferred method is to apply the solvent by dampening a paper towel
- and wiping the affected area.
In confined areas or in cleaning small parts, apply the solvent sparingly using a small brush.
Do not apply the solvent to coils, wires or other electrically insulated partso Page 21 of 55 9.7.l.f(2) 9.7.1.f(3) 9.7.1.g 9.7.1.h 9.7.1.i
. 9.7.l.j 9.7.2.a 9.7.2.b Rev. 8.
M3Q-2 9.7.3 BREAKER INSPECTION AFTER CLEANING SUPERVISOR.WITNESS INSPECTION HOLD POINT
- a.
Inspect for the presence of dust, dirt and other types of foreign substances or contaminants, including moisture and rust. Look for loose, damaged, broken or distorted parts.
Check for signs of excessive heating, burning or arcing.
Examine 'the breaker for signs of rubbing, wearing or stress.
- b.
Check that all retaining rings are securely in place on all visible shafts and pins as follows:
Moving Contact Hinge Pins Stationary Arcing Contact Hinge Pins Crossbar Operating Mechanism Auxiliary Switch Linkage Pantograph 6
2 8
3 6
Positioning and Interlock Lever 2 TOTAL 33 2-Per Pole 2-Per Pole One Each End 5 Left Side 3 Right Side 3 Top 3 Bottom
- c.
Raise and lower the trip bar by hand to assure it does not bind; i.e., it should feel like a free weight.
- d.
Inspect the positioning stop bracket and support rails for signs of mechanical damage and corrosion.
- e.
Check breaker support wheels for free movement.
Page 22 of 55 (SW)
(IHP) 9.7.3.a 9.7.3.b 9.7.3.c 9.7.3.d 9.7.3.e Rev. 8
.9
- 8. OPERATING MECHANISM CHECKS SUPERVISOR WITNESS INSPECTION HOLD POINT The operating mechanism (See Enclosure 1) is non-adjustable and consists of a series of non-ferrous links designed to secure low closing and tripping forces.
- 1.
Check for signs of sluggishness and friction by raising the trip bar and slowly rotating the manual operating handle in the "close" direction.
The linkage should follow the handle without sticking. Verify that all parts maintain proper alignment and move freely.
- 2. Restrain the UVTA. Reset Lever in the "Reset" position using a piece of string or wire. (Requires two persons)
- 3. Without latching the breaker, manually operate the moving contact assembly in both the "closed" and "open" direction.
Verify the linkage is properly aligned and moves freely.
4*
Manually close and latch the breaker.
Slowly release the UVTA Reset Lever to trip the breaker. Verify the moving contact assembly returns to the full open (reset) alignment.
- 5. Inspect the breaker linkage for excessive wear, cracks or signs of stress. Notify the Electrical Supervisor immediately of any discrepa~cies noted.
- 6.
Verify the restraining string or wire is removed.
(IHP) 9.8.3 9.8.4 9.8.5 9.8.6 Rev. 8
M3Q-2 9.9 CLOSING COIL INSPECTION AND REPLACEMENT SUPERVISOR WITNESS INSPECTION HOLD POINT 9.9.1 The closing coil (See Enclosure 3), is non-adjustable.
It is designed for intermittent duty only.
Inspect connections, and check for loose bolts. If it is not necessary to replace the coil, proceed to Step 9.10. If it is necessary to replace the coil proceed with Step 9.9.2.
9.9.2 To remove/replace the coil:
- a. Trip breaker.
- b.
Disconnect closing coil leads from control circuit wiring.
One coil wire (large black) is on -the top left terminal of the Control Relay.
The other coil wire (large black) is on the bottom 4 pole auxiliary switch located on the third:
(3rd) bottom terminal from the left.
- c.
Remove the bolts (9), washers (12), relay release arm (8),
bolts (10), washers (11), and plate (2).
- d.
Drop closing coil (7) with brass tube (5).
- e.
Check new coil for continuity prior to installation.
- f.
Replace closing coil.
Be sure to replace brass tube (S) so that the stationary core (4) and moving core (3) are aligned in the tube.
- g.
Reinstall plate (2), washers (11), bolts (10), relay release arm (8), washers (12), and bolts (9).
- h.
Reconnect closing coil leads.
One coil wire (large black) is on the top left terminal of the control relay.
The other coil wire (large black) is on the bottom 4 pole auxiliary switch located on the third (3rd) bottom terminal from the left.
NOTE THE UVTA MUST BE RESTRAINED IN ITS NORMAL ENERGIZED POSITION TO OPERATE THE BREAKER MANUALLY.
- i. Manually rotate operating handle in "close" direction with trip lever down to verify solenoid operates smoothly without binding.
(SW)
(IHP) 9.9.1 9.9.2.a.
9.9.2.b.
9.9.2.c.
9.9.2.d.
9.9.2.e.
9.9.2.f.
9.9.2.g.
9.9.2.ha 9.9.2.1:
Page 24 of 55 Rev. 8
9.10 CONTROL RELAY INSPECTION M3Q-2 SUPERVISOR WITNESS INSPECTION HOLD POINT The control relay (See Enclosure 4) mounts directly under the auxiliary switch. It i's a single-coil, mechanically-tripped device with the coil suitable for continuous energization.
The operation sequence is outlined in Reference 4.6.
The contacts should normally last the life of the breaker, but are replaceable if found necessary.
9.10.l Inspect contacts for visible sign of stress or arcing.
9.10.2 Check the relay trip assembly.for correct operation of the relay and the relay release arm as.follows:
- a.
Disconnect the closing coil leads from the control circuit wiring.
One coil wire (large black). is on the top left terminal of the control relay.
The other coil wire (large black) is on the bottom 4 pole auxiliary switch located on the third (3rd) bottom terminal from the left.
(See Reference 6)
- b.
Block the undervoltage trip attachment by applying 43 +/-2 VDC to the coil as follows:
(1)
Connect variable DC power supply to a two pole test switch assuring the power supply is de-energized and the variable potentiometer is turned to the lowest position.
(2)
Connect a voltmeter to the line side of the 43V test switch.
(3)
Connect the load side of the 43VDC test switch to breaker control stabs #11 and #12.
(4)
With the 43VDC test switch in the open position, energize the power supply.
Adjust the voltage to 43 +/- 2VDC.
(S)
Close the 43VDC test switch and recheck the power supply. If voltage drops below 43 f 2VDC, readjust to proper level.
(IHP) 9.10.l 9.10.2..a.
9.10.2.b(l) 9.10.2.b(2) 9.10.2.b(3) 9
- 10
- 2
- b ( 4)
- 9. 10. 2. b (5:
Rev. 8
M3Q-2 _
L
- c.
(1)
Connect 125VDC to stabs Ill and 118 *per step 9.1. 2 (2)
Energize th~ relay operating ("X") coil by depressing the monentary push button.
(3)
Ensure that the coil is energized and the "x" contacts are closed.
9.10.2.c(l) 9.10.2.c(2) 9.10.2.c(3)
NOTE CHECK THAT THE RELAY RELEASE ARM DOES NOT RUB ON EITHER SIDE OF THE RELAY TRIP ASSEMBLY LEVER APERATURE.
THE RELEASE ARM MAY BE BENT TO SUIT.
- d.
Slowly close the.breaker manually.* The relay release arm should operate the relay trip assembly and the relay trip assembly should open the relay contacts just before the breaker latches. This position can best be determined by watching the pawl in the breaker operating mechanism, which should. snap in place just after the relay contacts open. If operation is satisfactory, proceed to Step 9.10.2.f.
- e.
If this operation sequence is not satisfactory, Westinghouse Electric Nuclear Services Division will be contacted to perform adjustment.
- f.
When the breaker is latched, de-energizing and then energizing the relay operating coil, with the 125VDC Supply switch, should not cause the relay contacts to move toward the closed position.
Trip breaker by. de-energizing the 43VDC power supply.
CAUTION!
ENSURE BREAKER TRIPS BEFORE PROCEEDING.
- g.
De-energize the temporary 125VDC supply to the control relay.
- h.
Reconnect closing coil leads to the control circuit wiring.
One coil wire (large black) is on the top left terminal of the control relay.
The other coil wire (large black) is on the bottom 4 pole auxiliary switch located on the. third (3rd) bottom terminal from the left.
Check electric closing of breaker by re-energizing 43VDC power supply and the 125VDC control relay power supply.
Page 26 of 55 9.10.2.d.
9.10.2.e..
9.10.2.f.
9.10.2.g.
9.10. 2. h.
Rev. 8
- i.,Close breaker electrically via push button in 125VDC circuit.
Verify breaker closes electrically.
- j. After proving that the breaker can be.closed electrically, de-energize the 125VDC and 43VDC power supplies.
Page 27 of 55 9.10. 2. i.
9.10.2.j.
Rev. 8
9.11 SHUNT TRIP INSPECTION AND TIMING M3Q-2 The shunt trip mounts on top of the p*lat'form immediately to the right of the operating mechanism.
(See Enclosure 5).
It is non-adjustable and is intended for intermittent duty only.
The shunt trip circuit must always be opened by an auxiliary switch contact.
9.11.l SHUNT TRIP INSPECTION SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Energize the undervoltage-trip attachment coil via the test switch that was installed in Step 9.10.2.b.
- b. With the breaker in the open position, manua_lly push the moving core against the stationary core and rotate the breaker handle to the closed position. The breaker should be trip free.
- c.
The trip lever of the shunt trip should have from l/32"
(.032) to 1/8" (0.125) inch clearance to the trip bar.
Measure and record clearance on Enclosure 7.
CAUTION!
THE INTENT OF TIGHTNESS VERIFICATION IS TO ENSURE THE CONNECTION IS NOT LOOSE.
DO NOT FORCE OR OVER.TIGHTEN ANY FASTENERS.
- d.
Visually. examine contacts (on the auxiliary contact blocks) for evidence of arcing.
Visually examine the wiring for fraying and check all terminals for tightness.
- e.. Inspect the auxiliary contact block connecting linkage.
Ensure all snap rings are installed and linkage is not bent or deformed in any way.
Operate the breaker manual handle back and forth.
Observe the linkage for smooth
operation.
- f.
Check for loose bolts*.
- g.
Check for faulty coil as follows:
(1)
Ensure that the coil has reached ambient temperature.
Using contact pyrometer, measure the temperature of the shunt trip attachment frame (see Enclosure S).
Record temperature on Enclosure 7.
(2)
Manually close the breaker
- Page 28 of 55 (SW)
(IBP) 9.11.1.a.
9.11.l.b.
9.11.1.d.
9.11.1.e.
9.11.l.f.
Rev. 8
M3Q-2 (3)
Measure resistance between control stabs #3 and #7.
Record on Enclosure 7.and verify resistance is satisfactory.
9.11.2 SHUNT COIL TEST.
SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Connect 125VDC power supply to control stabs #3 and #7 (shunt trip coil).
- b.
Adjust the 125VDC POWER SUPPLY to 70+/-1 VDC.
- c. Manually close the breaker.
- d.
Close 125VDC test switch {Actual voltage is 70VDC).
Note that the breaker trips. If the breaker does not trip, the SHUNT TRIP ATTACHMENT must be replaced.
9.11.3 De-energize the 125VDC and 43VDC power supplies.
Page 29 of 55
. (SW)
(IHP) 9.11.2.a.
9.11.2.b 9.11 *. 2.c 9.11.2.d 9.11.3 Rev. 8
9.12 UNDERVOLTAGE TRIP ATTACHMENT M3Q-2 The undervoltage the shunt trip.
breaker when the normal.
trip mounts on top.of the platform, to the right of (See Enclosure 1). Its function is to trip the voltage falls to between 30 and 60 percent of The moving core is normally held magnetically against the stationary core to hold the Micarta rod and consequently the reset lever, in the reset position *
. When the coil voltage is reduced sufficiently, the reset lever spring*
overcomes the magnetic attraction of the cores (See Enclosure 6) and rotates the reset lever clockwise.
As the reset lever rotates, it carries with it the latch pin which rotates relative to the latch until the latch is released.
When the latch releases, the trip spring rotates the trip lever counterclockwise.to trip the breaker.
The latch is reset by the cross bar moving the adjustable reset lever as the breaker*opens. shows the cross bar in the open position of the breaker.
CAUTION!
THE SELF-LOCKING SCREW (REFER TO ENCLOSURE 116) IN THE MOVING CORE IS SET AT THE FACTORY AND SHALL NOT BE ADJUSTED IN THE FIELD.
THE UNDERVOLTAGE TRIP ATTACHMENT COIL VOLTAGE DROP OUT ADJUSTMENT IS MADE AT THE FACTORY.
THIS ADJUSTMENT SCREW IS NOT TO BE TAMPERED WITH IN THE FIELD.
DO NOT ATTEMPT TO MAKE ANY FIELD ADJUSTMENTS ON TRIS SCREW.
CAUTION!
THE FAILURE OF AN UNDERVOLTAGE TRIP ATTACHMENT MUST BE REPORTED TO THE NUCLEAR REGULATORY COMMISSION.
IF AN UNDERVOLTAGE TRIP ATTACHMENT FAILS, DURING ANY SINGLE TEST, NOTIFY THE SENIOR SHIFT SUPERVISOR IMMEDIATELY.
DO NOT PROCEED WITH THE PROCEDURE UNTIL FURTHER DIRECTION IS OBTAINED FROM THE NUCLEAR ENGINEERING DEPARTMENT.
NOTE:
THE UNDERVOLTAGE TRIP ATTACHMENT SHALL BE REPLACED DURING EACH REFUELING OUTAGE.
IF THE U/V TRIP ~TTACHMENT-IS TO BE REPLACED, PROCEED TO* STEP 9.13.
Page 30 of SS Rev. 8
M3Q-2 NOTE:
IF THE UNDERVOLTAGE ~RIP ATTACHMENT ON THE.RF.ACTOR TRIP OR REACTOR TRIP BYPASS BREAKERS FAILS AT ANY 'TIME DURING THIS PROCEDURE, IT MUST BE REPLACED.
9.12.l UNDERVOLTAGE TRIP ATTACHMENT INSPECTION SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Perform a visual inspection of the undervoltage trip attachment.
Check for loose 111Dunti~g bolts.
- b.
Inspect the three (3) points identified as A, B and C on Enclosure 6 to verify that they are sealed and have not been disturbed.
- c.
Attach a restraining device (such as string) on the reset lever.
Hold the reset lever in the reset position (where it would normally be when coil is energized).
- d.
Close the.breaker.
- e.
Slowly retease the reset lever. Verify it trips the
- breaker before the reset lever comes to rest.
- f.
While releasing the reset lever, watch for unhesitant, smooth positive snap action of the undervoltage attachment and breaker trip.
- g.
Verify that the temporary restraint is removed.
- h.
Check for faulty coil as follows:
(1)
Ensure that the coil has reached ambient temperature.
Using_contact pyrometer, measure the temperature of the-U/V trip attachment frame (See Enclosure 6).
Record temperature on Enclosure 7.
(2)
Measure resistance between terminals 1111 and 1112.
Record on Enclosure 7 and verify resistance is satisfactory.
Page 31 of 55 (SW)
(IBP) 9.12. l.a.
9.12. l. b.
9~12.1.c.
9.12.l.d..
9.12. l. f.
9.12.l.g.
- 9. 12.1. h (1) 9.12. Lh(2.
Rev. 8'
- i. Inspect undervoltage trip attachment for accumulations of dust and debris.
- j. If cleaning is required, it should consist of wiping with paper towels or lint free cloths to remove dust and dirt.
In some cases, brushing with.a medium or stiff bristle brush may be necessary.
Do not use a wire brush.
Brushing may be supplemented by vacuuming.
- k.
If sticky or gummy substances are present, a mild solvent may be used.
Do not apply the solvent to coils, wires or other electrically insulated parts.
Page 32 of SS 9.12.1.i 9.12.1.j 9.12.1.k Rev. 8
M3Q-2 9.12.2 UNDERVOLTAGE TRIP ATTACHMENT LUBRICATION NOTE:
INTERVALS BETWEEN LUBRICATION OF THE UNDERVOLTAGE TRIP ATTACHMENT SHOULD NOT EXCEED TWO HUNDRED BREAKER OPERATION CYCLES WHEN BREAKER OPENED AND THEN CLOSED EQUALS ONE CYCLE.
NOTE:
LUBRICATE THE UNDERVOLTAGE TRIP ATTACHMENT WITH 53701GW REV. C LUBRICANT.
THIS
. LUBRICANT IS COMPOSED OF A fINELY GROUND AND PURIFIED NATUBAL ORE OF MOLYBDENUM DISULFIDE AND ISOPROPYL ALCOHOL.
IT IS PREPARED BY MIXING 5 PARTS BY WEIGHT OF TRIS LUBRICA'IING GRADE MOLYBDENUM DISULFIDE WITH 3 PARTS BY WEIGHT OF COMMERCIAL GRADE ISO-PROPYL ALCOHOL.
A LUBRICATION KIT*,
CONTAINING LUBRICANT AND HANDLING ACCESSORIES SHOULD BE USED.
MIXING BY VOLUMF; IS NOT RECOMMENDED.
THE INTENT OF THIS LUBRICA'IING MIXTURE IS 'IO PROVIDE A FLUID SYSTEM TO CARRY SOLID LUBRICAN'I TO THE CLOSELY FI'ITED PARTS.
A PROPER MIXTURE WILL LEAVE A S!fOO'IB UNIFORM COATING ON THE SURFACE OF A PART.
IF THE MIXTURE DOES NOT CONTAIN ENOUGH ALCOHOL, THE LUBRICANT DOES NOT FLOW WELL AND PRODUCES A LUMPY COATING.
WHEN NOT IN USE, THE MIXTURE SHOULD BE KEPT IN A SEALED CONTAINER TO PREVENT EVAPORATION OF THE ALCOHOL.
IF SUFFICIENT ALCOHOL HAS EVAPORATED TO MAKE THE LUBRICANT VISCOUS OR PASTELIKE, A NEW BATCH SHOULD BE PREPARED.
TRE MIXTURE SETTLES RAPIDLY AND SHOULD BE MIXED WELL BEFORE AND DURING EACH USE.
- Folio fl ------
Page 33 of 55 Rev. 8
M3Q-2 a
- LUBRICATION PRECAUTIONS CAUTION!
LUBRICANT IS FLAMMABLE.
ENSURE ADEQUATE VENTILATION.
OBSERVE ALL NECESSARY PRECAUTIONS AND PROCEDURES.
AVOID PROLONGED EXPOSURE TO THE SKIN.
- 1.
The lubrication mixture must be kept thoroughly mixed prior to and throughout the procedure by vigorously shaking the container occa~ionally.
- 2.
Place a cloth beneath the UVTA while applying lubricant to collect over-shoot and run-off lubricant.
- 3. Additional precautions on handling of the lubricant are provided in the instruction sheet accompanying the lubrication kit.
- b.
LUBRICATION TECHNIQUES
- 1. The lubricant is to be applied using the container and dispensing tube provided with the lubrication kit. Lubricant handling and application techniques are further described in the instruction sheet accompanying the ld.t.
- 2.
The lubrication may be performed without removing the UVTA from its mounting.
However, special care is required to reach all lubrication points_ by varying the direction of the application bottle dispensing tube.
- 3.
Dispense drops of lubricant at designated points by placing tip of dispensing tube at the appropriate location and gently raising the container.
- 4. Apply lubricant liberally at all points, and manually exercise the mechanism during and following lubricant application. This manual exercising is accomplished by. first blocking the breaker partially towards the closed position (so that the UVTA reset lever is released).
Exercise the device by manipulating the reset lever
- Page 34 of 55 Rev. 8'
M3Q-2 9.12.3 UNDERVOLTAGE TRIP ATTACHMENT COIL TEST
.?
.).
SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
With the undervoltage attachment remaining de-energized, operate the breaker by means of the manual lever, and confirm that the breaker trips "free" (open) on closing motion.
- b.
Connect a variable DC power supply to a 2 pole test switch assuring the power supply is de-energized and the variable potentiometer is turned to ~he lowest position.
- c.
Connect a voltmeter to the line side of the 43VDC test switch.
- d.
Connect the load side of the 43VDC test switch to breaker control stabs #11 and #12.
- e. With the 43VDC test switch in the open position energize the power supply. Adjust the voltage to 43 t 2VDC.
- f.
Close the test switch and recheck the power supply. If voltage drops below 43 t 2 VDC, readjust to proper level.
Verify undervoltage coil latches the trip mechanism by moving the breaker toward the closed position with the manual lever.
The undervoltage trip attachment lever will stop following the connection arm with the breaker approximately 1/3 to 1/2 travel toward the closed position.
- g.
Manually close the breaker.
Measure gap between undervoltage trip lever and breaker trip bar and record on Enclosure 7.
. h.
Open the 43VDC test switch.
Verify that the undervoltage relay drops out and trips the breaker.
- i. SUPERVISOR WITNESS INSPECTION HOLD POINT Reclose the 43 VDC test switch.
Reclose the breaker.
Wait a minimum of thirty (30) minutes; then open the 43 VDC test switch.
Verify that the breaker trips.
Perform this step ten (10) times and record on. (Maintenance)
'v 1-""
~
..... l" J
\\_.,...
- . *,I Page 36 of 55 (SW)
(HIP) 9.12.3.a.
9.12.3.b.
9.12.3.c.
9.12.3.d.
- 9.12.3.e.,
9.12.3.f.
9.12.3.g
- 9.12.3.h.
(SW)
(IHP) 9.12.3.i.
Rev. 8
. :Co}..-
9.12.4 U/V TRIP ATTACHMENT COIL DROP OUT VOLTAGE TEST ~\\.C.L NOTE:
REPLACE THE UVTA AFTER LUBRICATION, IF.
THE DROPOUT VOLTAGE IS GREATER THAN 60% OR LESS THAN 30% OF THE RATED UVTA COIL VOLTAGE OR THE DROPOUT VOLTAGE DIFFERS BY MORE THAN +/- 5 VOLTS FROM THE "REFERENCE" VOLTAGE.
SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Close 43VDC test switch.
- b.
Adjust voltage to approximately 43VDC.
- c. Manually close the breaker.
- d.
Slowly turn the variable.potentiometer to decrease the voltage.
(Approximately 15 sec/volt when approaching the d~op out voltage). Monitor the voltage and record on Enclosure 7 the voltage at which the breaker trips open.
- e.
Repeat Steps 9.12.4.b through 9.12.4.d two (2) more times. Verify there were no failures.
- f.
De-energize the test equipment.
Page 37 of 55 I
(SW)
(!HP) 9.12.4.a 9.12.4.b 9.12.4.c 9.12.4.d 9.12.4.e 9.12.4 *. f
. Rev. 8
\\_
9.13 UNDERVOLTAGE TRIP ATTACHMENT REPLACEMENT NOTE:
SUPERVISOR WITNESS IF THE UNDERVOLTAGE TRIP ATTACHMENT IS NOT TO BE REPLACED, PROCEED DIRECTLY TO SECTION 9.14.
NOTE:
IF THE UNDERVOLTAGE TRIP ATTACHMENT ON THE REACTOR TRIP OR REACTOR TRIP BYPASS BREAKER FAILS AT ANY TIME DURING THIS PROCEDURE IT MUST BE REPLACED.
IF SO, THE FOLLOWING PROCEDURE WILL BE USED, AFTER ALL REQUIRED NOTIFICATIONS ARE GIVEN AND DIRECTION HAS BEEN OBTAINED FROM THE NUCLEAR ENGINEERING DEPARTMENT.
!2!!_:
REFER TO CAUTIONS UNDER SECTION 9.12 BEFORE PROCEEDING.
INSPECTION HOLD POINT
- 9.13.1 Verify that an undervoltage trip attachment, meeting Quality Control requirements is available.
9.13.2 *confirm that the breaker is in the tripped position.
9.l3.3 Remove the arc chutes from the center and right side (as viewed from outside) poles if not already removed.
9.13.4 Separate the undervoltage coil leads at the in-line c"C:>Iinection beneath the platform.
9.13.S Remove the two mounting screws, and take away the original undervoltage attachment.
9.13.6 Install the new undervoltage attachment in place, making certain that the "trip lever" does not bind with, and is beneath, the breaker "trip bar." Bolt in place with the original mounting hardware.
Run the coil lead via the same grommet and routing as t.he original coil, and reconnect to* leads beneath the platform.
Either polarity is satisfactory.
(IBP) 9.13.l 9.13.2 9.13.3 9.13.4 9.13.5 9.13. 6 Rev. 8
M3Q-2 9.13.7 Check coil resistance as follows:
- a.
Ensure that the coil has reached ambient temperature.
Using contact pyrometer,-measure the temperature of the U/V Trip Attachment frame (See Enclosure 6).
Record temperature on Enclosure 7.
- b.
Measure resistance between terminals #11 and #12.
Record on Enclosure 7 and verify resistance is satisfactory.*
9.13.8.The undervoltage attachment will be shipped with reset adjustment all "out" (i.e. minimum space between the fixed and*moveable reset arms), and therefore should remain in the TRIPPED condition with the breaker fully open.
However, a false RESET usually bccurs during the installation and mounting process.
Therefore, the itlitial step is to cycle the undervoltage attachment by manually moving the
'breaker toward the closed position to allow the undervoltage attachment to trip.
NOTE:
FOR FINITE OBSERVATION OF UNDERVOLTAGE OPERATION, BREAKER OPERATION IS OBTAINED BY MANUALLY PUSHING THE CENTER "M>VING ARCING CONTACT" IN A SLOW BUT CONTINUOUS MOTION.
PUSHING ON ONE OF THE SIDE CONTACTS IS NOT ACCEPTABLE, AS THERE MAY BE SOME UNDESIRABLE COCKING OF THE MOVING ASSEMBLY, AND OPERATION BY THE "LEVER.
HANDLE" IS NOT ACCEPTABLE BECAUSE THE RAPID MOVEMENT AND OVER TRAVEL SHOCK DO NOT PROVIDE A CRITICAL CHECK.
9.13.9 With the undervoltage attachment de-energized, and the breaker toward the closed position, confirm that the undervoltage attachment is in the TRIPPED condition as indicated by zero clearance between the trip lever and trip bar.
(The trip lever will actually be suspending the trip bar about 1/4 inch).
9.13.10 Confirm that the "reset lever" pivot/lock screw is sufficiently loose. to permit movement between the fixed and moveable "reset arms;" and loosen the locknut on the "reset lever"- adjust screw.
Page 39 of 55
- 9. 13. 7 9.13.8 9.13.9 9.13.10 Rev. 8
M3Q-2 9.13.11 With the moving main contacts in their full open position slowly increase the "reset lever adjustment" by turning the screw clockwise until RESET occurs.
On initial adjustment, as much as 10 to 20 turns of the screw may be required.
RESET action will be indicated by an audible click, slight dropping of the trip lever and trip bar, and raising of the trip latch.
9.13.12 After RESET action has occurred in Step 9.13.11, turn the "reset adjust screw" ~
additional ~* Then relock the adjust screw and the pivot/lock screw.
9.13.13 Move the breaker toward the closed position until a TRIP occurs as denoted by a readily audible click, dropping of the latch, and kick-out of the trip lever.
9~13.14 Allow the moving assembly to move slowlf toward the open position and confirm that RESET occurs just.!!. the moving assembly comes ~
..!!!.! (See Step 9.13.11).
9.13.15 Repeat Steps 9.13.13 and 9.13.14 a* sufficient number of times to be assured that TRIP action (on closing motion) and RESET action (just as the moving assembly comes to rest on opening motion) are correct. If, however, there are any malfunctions or questionable.actions, re-adjust the "reset lever" and repeat Steps 9.13.10 through 9.13.15.
Page 40 of 55 9.13.11 9.13.12 9.13.13 9.13.14 9.13.15 Rev. 8.
9.13.16 U/V TRIP ATTACHMENT MANUAL TEST SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Ensure the three (3) points identified as A, B and C on are sealed with a glyptal type paint or sealing wax in a manner to reveal any future movement of these points.
- b. Attach a restraining device (such as string) on the reset lever. Rold the reset lever in the reset position (where it would normally be when coil is energized).
- c.
Close the breaker.
(SW)
(IHP) 9.13.16.a 9.13.16. b 9.13.16.c
- d.
Slowly release the reset lever until it trips the breaker *...,....,..,......,..,,,_.,....
9.13.16.d M3Q-2
- e.
While releasing the reset lever, watch for unhesitant, smooth positive snap action of the undervoltage attachment and breaker trip.
- f.
Verify that the temporary restraint is removed.
9.13~17 UNDERVOLTAGE TRrP ATTACHMENT COIL TEST SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
With the undervoltage attachment remaining de-energized, operate the breaker by means of the manual lever, and confirm that the breaker trips "free" (open) on closing motion.
- b.
Connect a variable DC power supply to a two pole test switch assuring the power supply is de-energized and the variable potentiometer is turned to the lowest position.
- c.
Connect a voltmeter to the line side of the 43VDC test switch *
- d.
Connect th~ load side of the 43VDC test switch to brea~er connect stabs Ulland #12.
- e. With the 43VDC test switch in the open position, energize the power supply.
Adjust the volt~ge to 43 t 2 VDC.
Page 41 of 55 9.13.16. e 9.13.16. f (SW)
(Im?)
9.13.17.a 9.13.17.b 9.13.17.c 9.13.17.d 9.13.li.e Rev. 8
- f.
Close the 43VDC test switch and recheck the power supply.
If voltage drops below 43 t 2 volts, readjust to proper level.
Verify undervoltage coil latches the trip mechanism by moving the breaker toward the closed position with the manual lever.
The undervoltage trip attachment lever will stop following the connecting arm with the
_breaker approximately 1/3 to 1/2 travel toward the closed position.
- g.
Manually close the breaker. Measure gap between undervoltage trip lever and the breaker trip bar and record on Enclosure 7.
- h.
Open the 43VDC test switch. Verify that the undervoltage relay drops out and trips the breaker.
- i.
SUPERVISOR WITNESS INSPECTION HOLD POINT Reclose the 43VDC test switch.
Reclose the breaker.
Wait a minimum of thirty (30).minutes, then open the 43VDC test switch.
Verify that the breaker trips. Perform this step ten (10) times and record on Enclosure 9. (Replacement) 9.13.18 REPLACEMENT U/V TRIP ATTACHMENT LUBRICATION SUPERVISOR WITNESS INSPECTION HOLD POINT Lubricate the U/V trip attachment as described in step 9.12.3.
9.13.19 U/V TRIP ATTACHMENT COIL DROP OUT VOLTAGE TEST SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Close 43VDC test switch.
- b.
Adjust voltage to approximately 43VDC.
- c.
Manually close the breaker.
- d.
Slowly turn the var-iable potentiometer to decrease the voltage.
(Approximately 15 sec/volt when approaching the drop out voltage).
Monitor the voltage and record on the voltage at which the breaker trips open.
Page 42 of 55
- 9. 13
- 17. f 9.13.17. g 9.13.17.h (SW).
(IBP) 9.13.17.i (SW)
(IBP) 9.13.18 (SW)
(IHP) 9.13.19. a 9.13.19. b
- 9. 13. 19. c 9.13.19.d Rev. 8
- e.
Repeat Steps 9.13.19.b through 9.13.19.d two (2) more times.
The average of the three recorded drop out voltages becomes the "reference" drop out voltage for this U/V trip attachment.*
- f.
De-energize the test equipment.
Page 43 of SS 9.13.19.e
- 9. 13. 19. f Rev. 8
9.14 TRIP BAR AND U/V TRIP LEVER FORCE MEASUREMENT NOTE:
M3Q-2 9.14.1 THE FAILURE OF AN UNDER.VOLTAGE TRIP ATTACHMENT MUST BE REPORTED TO THE NUCLEAR REGULATORY COMMISSION.
IF AN UNDERVOLTAGE TRIP ATTACHMENT
- FAILS A TEST, NOTIFY THE SENIOR SHIFT SUPERVISOR IMMEDIATELY.
DO NOT CONTINUE WITH THE PROCEDURE UNTIL FUIUlTER DIRECTION IS OBTAINED FROM THE NUCLEAR ENGINEERING DEPARTMENT.
Enter calibration data on all equipment required for measurements:
EQUIPMENT NOMENCLATURE WEIGHT STAND WEIGHT STAND WEIGHT STAND EQUIPMENT 0
CALIBRAT~ON SERIAL NUMBER DATE CALIBRATION DUE DATE 9.14.2 TRIP BAR FORCE MEASUREMENT SUPERVISOR WITNESS INSPECTION HOLD POINT a.-
Energize the 43VDC power supply, and close the 43VDC test switch to energize the UV trip attachment.
- b.
Manually close the breaker.
- c.
Add weights in 10 gram increments via pulley arrangement shown on Enclosure 12, Figure 1, until the breaker trips.
- d.
Record total weight (weights and weight stand) added to
- the bar, on Enclosure 7.
- e.
Repeat steps (b), (c) and (d) two more times.
Verify that there were no failures.
9.14.3 UVTA FORCE MEASUREMENT
\\ \\_,
- I
- ~*.
/,.
/
SUPERVISOR WITNESS
-INSPECTION HOLD POINT
- a.
Load the trip bar with 460 grams of weight as shown on Enclosure 12.
- b.
Energize the UVTA and manually close the breaker.
(IHP)
(SW)
(IHP)
Rev. 8
- c.
Attempt to trip the breaker by de-energizing the UVTA.
- d.
If the breaker fails to trip,at or below 460 grams, notify the Senior Shift Supervisor.
Do not continue with the procedure until further direction is obtained from Nuclear Engineering Department.
- e.
If breaker tripped:
- 1.
Increase weight on trip bar in 60 gram increments and repeat steps (b) and (c) until the breaker fails to trip.
- 2.
Record, on Enclosure 7, the total amount of weight (weights and weight stand) on the trip bar when the breaker fails to trip.
- f.
Remove 60 grams from the trip bar.
(c), (d), and (e), two more times.
no failures
- Page 4S of SS Repeat steps (b),
Verify there were Rev. 8
\\*
9.15 BREAKER U/V TRIP TIMING 9.15.l Connect visicorder channels for the following traces.
- a.
Three channels for the three (3) main breaker contacts.
Jumper the three (3) line side stabs together and connect one channel per phase on the load side.
- b.
One channel across the load side of the 43VDC test switch.
9.15. l.a n~t'o ~)
9.15.2 BREAKER TRIP TIMING
\\(..L.8--..,...15""',-1-.-b-M3Q-2 SUPERVISOR WITNESS INSPECTION HOLD POINT
- a.
Verify ready light is lit.
- b. Verify breaker to be tested is open.
- c. Verify undervoltage coil is de-energized.
- d.
Energize 43VDC power supply.
- e. Close 43VDC test switch.
£.
Manually close breaker.
- g. -Start visicorder
- h.
Open 43VDC test switch.
Note that the breaker trips.
- i.
Stop visicorder.
- j. De-energize 43VDC power supply.
- k.
Remove visicorder trace and identify same.
See Step 9.1. 4. i for required information.-
Record trip time on Enclosure 7.
- l. Repeat Steps d through k two (2) more times.
Verify there were no failures.
Page 46 of 55 (SW)
(IBP)
- 9. 15. 2. a
- 9. 15. 2. c 9.15.2. e 9.15.2.f 9.15. 2.g 9.15. 2.h 9.15.2.i 9.15. 2. j 9.15. 2. k 9.15.2.l Rev. 8
9.16 BREAKER SHUNT TRIP TIMING
. tc(J)
.. q;~
M3Q-2 SUPERVISOR WITNESS INSPECTION HOLD POINT 9.16.l Connect 125VDC power supply to control stabs #3 and #7.
9.16.2 Connect visicorder to stabs #3 and #7.
9.16.3 Energize 125VDC and 43VDC power supplies.
9.16.4 Close 43VDC test switch.
9.16.5 Manually close the breaker.
9.16.6 Start visicorder.
9.16.7 Close 125VDC test switch.
Note that the breaker t.rips.
9.16.8 Stop visicorder and open 125VDC test switch.
9.16.9 Remove visicorder trace and identify same.
See step 9.1.4.i for required information.
Record trip time on Enclosure 7.
9.16.10 Repeat steps 9.16.5 through 9.16.9 two (2) more times.
- verify that there were no failures.
9.16.11 De-energize 125VDC and 43VDC power supplies.
Page 47 of 55 (SW)
(IEP)
- 9. 16. 1 9.16.2 9.16. 3 9.16. 4 9.16. 5 9.16. 7 9.16.8 9.16.. 9 9.16.10" 9.16.11 Rev. 8 I
9.17 BREAKER CLOSURE TIMING SUPERVISOR WITNESS INSPECTION ROLD POINT 9.17.l Disconnect visicorder leads from the 43VDC test switch.
9.17.2 Connect visicorder leads to 125VDC source and adjust visicorder. Disconnect from the 125VDC source and connect visicorder to breaker control stabs #2 and #8.
9.17.3 Connect 125VDC source to stabs #1 and #8.
9.17.4 Energize 43VDC and 125VDC power s~pplies. Close the 43VDC test switch.
9.17.5 Start visicorder.
9.17.6 Close 125VDC test switch, depress the test pushbutton and release.
Note that breaker closes.
\\J 9.17.7 Stop visicorder.
9.17.8 Open 125VDC test switch.
9.17.9 Open 43VDC test switch.
Note that breaker trips.
9.17.10 De-e~ergize 43VDC and 125VDC power supplies.
9.17.11 Remove visicorder trace and identify same.
See Step*9.l.4.i for required information.
Record closing time on.
9.17.12 Repeat Steps 9.17.4 through 9.17.ll two (2) more times.
Verify there were no failures.
9.17.13 De-energiz~ and remove all test equipment.
9.18 BREAKER MEGGER READINGS M3Q-2 SUPERVISOR WITNESS INSPECTION ROLD POINT 9.18.l Reinstall the arc chutes, dust cover, control relay cover and 3 aux control switch covers.
Be sure that the upper block cover is installed properly. It has a full top cover lip whereas the other two cover lips are notched for wiring purposes.
Page 48 of 55 (SW)
(IHP) 9.17.1 9.17.2 9.17.3 9.17.4 9.17.S 9.17.6 9.17.7*.
9.17.9 9.17.10 9.17.ll I 9.17.12 9.17.13 (SW)
(IHP)
- 9. 18. 1 Rev. 8
9.18.2 Close breaker and megger at 500 volts, phase to phase, and phase to ground.(Breaker Chassis), using a calibrated megger.
R~cord readings on Enclosure 7
- 9.19 RIGHT RAIL STOP LATCH INSPECTION M3Q-2 SUPERVISOR WITNESS INSPECTION HOLD POINT Perform a visual inspection of the right rail stop latch, on the breaker cubicle, to verify that the latch was not damaged during breaker removal and reinstallation.
(IHP) 9.19 Rev. 8
- 10. 0 FINAL TESTING M3Q-2 NOTE:
IF CIRCUIT BREAKER MAINTENANCE IS BEING PERFORMED DURING AN OUTAGE, THE FOLLOWING STEPS MAY BE DELETED:
10.l.3.a*, b, c and 10.1.4.a, b, c.
10.l Maintenance Supervisor circles the circuit breaker designation, enters the unit prefix and proceeds to the indicated step.
A REACTOR TRIP BYPASS BREAKER -
Go to Step 10.1.1 B RF.ACTOR TRIP BYPASS BREAKER - Go to Step 10.1.2 A REACTOR TRIP BREAKER -
Go to Step 10.1.3 B RF.ACTOR TRIP BREAKER -
Go to Step 10.l.4 10.1.1 A REACTOR TRIP BYPASS BBEAKER
- a. Notify the Seni"or Shift Supervisor/Shift Supervisor that maintenance has been completed and obtain permission to reinstall the breaker into its cubicle, rack the breaker into the fully racked in position and test the cell interlock.
Senior Shift Supervisor/Shift Supervisor Date
- b.
SUPERVISOR WITNESS INSPECTION HOLD POINT With the breaker in the fully racked in position, verify that there is adequate clearance between the cell int-erlock tab and the breaker trip bar (l/16"
- min).
Manipulate the cell interlock tab with a sideways motion and verify that adequate clearance remains between the cell interlock tab and the breaker trip bar.
- c.
SUPERVISOR. WITNESS INSPECTION HOLD POINT Manually close the breaker.* Operate the cell -interlock mechanism and visuaily verify that the breaker trips b_efore the cell interlock pin clears the highest point of the positioning stop bracket.*
Page "50 of 55 (SW)
(IBP)
- 10. l. lb (SW)
(IBP) 10.l.lc Rev. 8
- d.
SUPERVISOR WITNESS INSPECTION HOLD POINT Rack the breaker out and inform the*Senior Shift Supervisor/Shift'Supervisor that final testing has been completed.
10.1.2 B REACTOR TRIP BYPASS BREAKER
- a.
Notify the Senior Shift Supervisor/Shift Supervisor that maintenance has been completed and obtain permission to reinstall the breaker into its cubicle, rack the breaker into the fully racked in position and test the cell interlock.
Senior Shift Supervisor/Shift Supervisor Date
- b.
SUPERVISOR WITNESS INSPECTION BOLD POINT With the breaker in the fully racked in position, verify that there is adequate clearance between the* cell interlock tab and the breaker trip bar (1/16" min).
Manipulate the cell interlock tab with a sideways motion and verify that adequate clearance remains between the cell interlock tab and the breaker trip bar.
- c.
SUPERVISOR WITNESS INSPECTION HOLD POINT Manually close the breaker.
Operate the cell interlock mechanism and visually verify that the breaker trips before the cell interlock _pin clears the highest point of the positioning stop bracket.
- d.
SUPERVISOR WITNESS INSPECTION HOLD POINT Rack the breaker out and inform the Senior Shift Supervisor/Shift Supervisor that f~al testing had been completed.
10.1.3 A REACTOR TRIP BREAKER
- a. Notify the Senior I&C Supervisor that the I&C Department must set up to perform SSPS trip test of A Reactor Trip Breaker due to completion of maintenance and reinstallation.
Page 51 of 55 (SW)
(IHP)
- 10. l. ld (SW)
(IBP) 10.1. 2b (SW)
(IBP) 10.l.2c (SW)
(IHP) 10.1. 2d 10.1. 3a Rev. 8
- b.
Obtain confirmation from the Senior I&C Supervisor/
cognizant I&C Supervisor that required testing set up is complete
- I&C Senior/Supervisor Date Time
- c.
Inform the Senior Shift Supervisor/Shift Supervisor of the requirement to remove the breaker presently installed in the A Reactor Trip position. to reinstall the original A Reactor Trip Breaker and the original B Reactor Trip Bypass Breaker in their correct
_c_u_b_i_c-les. and to rack in the A Reactor Trip Breaker and test the cell interlock *.
- d.
Obtain permission of the Senior Shift Supervisor/Shift Supervisor and assist Operations Department in the actual circuit breaker transfer.
Senior Shift/Shift Supervisor Date Time
- e.
SUPERVISOR WITNESS INSPECTION HOLD POINT With the breaker in the fully racked in position. verify that there is adequate clearance between the cell interlock tab and the breaker trip bar (1/16" min).
Manipulate the cell interlock with a sideways motion and verify that adequate clearance remains between the cell interlock tab and the breaker trip bar.
- f.
SUPERVISOR WITNESS INSPECTION HOLD POINT Manually close the breaker.
Operate the cell interlock mechanism and visually verify that the breaker trips before the cell interlock pin clears the highest point of the positioning stop bracket.
- g.
Inform the cognizant I&C Superiisor that the circuit breaker is ready for the SSPS Trip test.
Page 52 of 55 (SWl (IBP)
- 10. l.3e (SW)
(IBP) 10.l.3f 10.l.3g Rev. 8
- h.
SUPERVISOR WITNESS INSPECTION HOLD POINT After the SSPS Trip test, verify with the cognizant I&C Supervisor and the Shift Supervisor that testing has been completed on the A Reactor Trip Breaker and the system has been returned to normal.
Shift Supervisor Date Time I&C Supervisor Date Time Quality Assurance Date Time
. i. Enter the serial numbers of the circuit breakers "As Left" on.
10.1.4 B REACTOR TRIP BREAKER
- a. Notify the Senior I&C Supervisor that the I&C Department must set up to perform SSPS Trip test of B Reactor Trip Breaker due to completion of maintenance and reinstallation *
- b.
Obtain confirmation from the Senior I&C Supervisor/
cognizant I&C Supervisor that required testing set up is complete.
I&C Senior/Supervisor Date Time
- c.
Inform the Senior Shift Supervisor/Shift Supervisor of the requirement to remove the breaker presently installed in the B Reactor Trip position, to reinstall the original B Reactor Trip breaker and the original A Reactor Trip Bypass breaker in their correct
- --**cubicles, and to rack in the B Reactor Trip Breaker arid test the cell interlock.
- d.
Obtain permission of the Senior Shift Supervisor/Shift
Supervisor and assist the Operations Department in the actual circuit breaker transfer.
Senior Shift/Shift Supervisor Date Time Page 53 of 55 (SW)
(IHP) i I I
i
\\
l0.l.3i
- 10. l.4a 10.1. 4c Rev. 8
- e.
SUPERVISOR WITNESS INSPECTION HOLD POINT With the breaker in the fully racked in position, verify that there is adequate clearance between the cell
-interlock tab and the breaker trip bar (1/16" min).
Manipulate the cell interlock tab with a sideways motion and verify that adequate clearance remains between the cell interlock tab and the breaker trip bar.
- f.
SUPERVISOR WITNESS INSPECTION HOLD POINT Manually close the breaker.* Operate the cell interlock mechanism and visually verify that the breaker trips before the cell interlock pin clears the highest point of the positioning stop bracket.
- g.
Inform the cognizant I&C Supervisor that the circuit breaker is ready for the SSPS Trip test.
- h.
SUPERVISOR WITNESS INSPECTION HOLD POINT After the SSPS Trip Test, verify with the cognizant I&C Supervisor and the Shift Supervisor that testing has been completed on the B Reactor Trip Breaker and the system has been returned to normal.
Shift Supervisor Date Time I&C Supervisor Date Time Quality Assurance Date Time
- i. Enter the serial numbers of the circuit breakers "As Left" on Enclosure 8.
(IHP) 10.l.4e (SW)
(IHP)
- 10. l.4f l0. l.4g (SW).
(IBP).
10.1. 4i Rev. 8
11.0 CLOSEOUT AND FINAL REVIEW M3Q-2 11.1 Procedure completed:
Satisfactory
---~Unsatisfactory Record final cycle counter reading. on Enclosure 7.
11.2 Remarks: __ ~----------~~--------------~
11.3 Test performed by:
Signature Date 11.4 Reviewed by:
Maintenance Supervisor Date Quality Assurance-Date 11.5 A copy of Enclosure 7 has been forwarded to the Senior Staff Engineer - Maintenance.
Maintenance Supervisor Date Page 55 of 55
. o Rev. 8.
MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE l CROSS SECTIQNAL VIEW OF TYPE DB-50 CIRCUIT BREAKER QB-!O C1RCU1T BREAKER
!IQQ AMPJBJI, §00 Vo!.T! A*C UNDERVOLTAGE
.TRIP ATTACH-MENT M3Q-2 BREAKER SHOWN IN CLOSED POSITION Enclosure l Page l of 2
. ~
S":'\\C
- lO'i'
\\P.P9' COIL.
iE~MINAI..
lee Revo 8
ce-50 gtRCU1T eee:AKER SHUNT TRIP ATTACHMENT WITH U.V.
ATTACHMENT REMOVED I
1.1_ow~ con.
":"~MINA1..
Jc.
BREAKER SHOWN IN CLOSED POSITION M3Q-2 Page 2 of 2
~
I LC'NE.=I S':"..!:
, lOT
\\ 1.P.P!A C:Oll.
i!=IMtN~L.
3oe ReVe 8
M3Q-2 MAINTENANCE PROCEDUBE M3Q-2 ENCLOSUBE 2 BREAKER SERIAL NUMBERS AND POSITIONS A TRIP 02YN201-l B TRIP 02YN20l-2 A TRIP 124Y7268B B TRIP 224Y7268B UNIT In UNIT ~2 Page 1 of 1
.A BY-PASS 324Y7269B B BY~ASS 424Y7269B A_B_'l_-P_A_s_s __
l*
324Y7268B B BY-PASS 424Y7268B Rev. " I
M3Q-2 MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE 3 CLOSING SOLENIOD -
CONSTRUCTION DETAILS
- -*--*::J
'.. J
~ 0
~--L.
1' ('f f!'iff
~--==ii
-QQ I
I "'
I i ["'4V*.. '.Pl"~**~,v.x-..:.""' !
,
- 1
- :.. *;~ : :
I
~
' 11*
I:
~ ; i
\\' i: *
- I~
- . '. I: :
- 1
- --'~-
'.11.
~'
I I
'f ti~*'
- ~~
1 j
"'*-'=:"¥"
. : ~IL
- -~.:.;;~
t !
n
' I I i k* i
~
\\3 *'
Page 1 of 1 I I I I 1 I
- 1 l..:..
- : Ii:
i.* '
j':.
~
I
~:====~~:.:'!~... =
Rev. 8 I
MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE 4 CONTROL RELAY - ADJUSTMENT AND CONSTRUCTION DETAILS I ----- ? ?IN.~N '""'"'"i t\\y I ;"'(\\
i_il
~C..i.-f"'\\
\\:..,
~-1 L-soLENOlD
~~AGN ET FRp._ME.
- ___...i,.;;;...__._
i I
~---i LE. \\JER,_ _ _..-*-""'\\
I I
RELAY RELEASE ARM I
I w CLOSING SOLENOID MOVING CORE
- Rl!!..AY lllOL.0~
STO? SURF.I.CE REL.EASE L.E'IER COVER.*
159 l\\IOVING CONT.'-*'",53 A.P 163
/
STATIONARY CONT. 1...=> :so-'
l'l.P. 18, AOJUST~EN'r I
'61
.).RC
- ~*.. ~~ ~~~ ~-0: :Ni.'f M3Q-2 Page 1 of 2 Rev. 8
M3Q-2 AUXILIJ\\RY SWITCH -
CONSTRUCTION DET~ILS Page 2 of 2 5.. A,T S 1..EVEA CON TAC T---i~°"
F1lllGEfll COlllTACT-__._,;...;.,....
AO TOA CASE
_Rev. B
M3Q-2 I
- I 0 lj I ii
- )
~ I ij ii 11 ii I'
MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE 5 SHUNT TRIP ATTACHMENT -
LOCATION AND CONSTRUCTION DETAILS LgC.HION
.o SUT*ONAA'I' CORE Page l of l 0
C01;..
300 OETAI LS Rev. 8
- M3Q-2 MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE 6 UNDERVOLTAGE TRIP ATTACHMENT -
CONSTRUCTION AND LUBRICATION DETAILS Tr:(IP BRACKET ENLARGED VIEW 'Pit
~~&14G PTI AL.L. SURFACES LATCH GUIDE PIN PT 2 ALL SUAFACU ATCH ENLARGED VIEW '9'
~--- SEE ~
VUJiJ I B.
- VERIFY SEALANT I~TACT AT POINTS A,a,c
SEE ENI.ABGED VIEW I A.'
- !.'f(*
Page 1 of 1
- Rev.. 8
MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE 7
.EAKER ~ERIAL NUMBER _____ _
DATA SHEET DATE. _______________ ___
WORK ORDER NUMBER CAUTION!
~----------~
(..I M3Q-2 ANY DATA FOUND OUT OF SPECIFICATIONS MUST BE REPORTED TO THE NUCLEAR REGULATORY COMMISSION VIA THE SENIOR SHIFT SUPERVISOR.
IF DATA IS OUT OF SPECIFIED RANGE, SUSPEND THE CONTINUANCE OF THE PROCEDURE.
DO NOT TAKE CORRECTIVE ACTION AND IMMEDIATELY NOTIFY. THE SENIOR SHIFT SUPERVISOR TO REPORT TO THE NUCLEAR REGULATORY COMMISSION THAT A REACTOR TRIP CIRCUIT BREAKER HAS BEEN FOUND TO BE OUT OF SPECIFICATION.
8.6 CYCLE COUNTER READING:
AS FOUND : ______
CYCLES 9.1.4.i Breaker Closure Timing:
9.2.9 9.3.9 9.4.2.d 9.4.3.e 9.5.4 1st 2nd 3rd I
Maximum Acceptable Value:
200 msec. (12 cycles at 60 hz)
Breaker U/V Trip Timing:
1st 2nd*
3rd I
Maximum Acceptable Value:
100 msec. (6 cycles at 60 hz)
Breaker Shunt Trip Timing:
I 1st 2nd 3rd
~--
Maximum Acceptable Value:
100 msec. (6 cycles at 60 hz)
Trip Bar Force Measurement:
'"?
~/
1st gm. 2nd gm. 3rd gm.
Maximum Acceptable Force is 885 gm. for all trials.
U/V Trip Lever Force Measurement:
, *./. i~.. -s~*/_~_...,:C
~ _:____.--
1 s t ____ __,gm 2nd _______,gm 3rd _____
"""'gm Minimum acceptable force is equal to or greater than 460 gms.
U/V Trip Attachment Coil Drop Out Voltage:
1st VDC 2nd VDC 3rd VDC Acceptable Range:
14.4 to 28.8 Volts D.C.
Page 1 of 5 Rev. 8
BREAKER SERIAL NUMBER ______ _
M3Q-2 9.6.3 Arcing Contacts Adjustment
- c.
As Found Arc Contact Gap r/JA ___ 0B_ 0C __ _
- d.
As Left Arc Contact Gap r/JA ___ r/JB ___ I/JC __ _
9.11.1.c Shunt Trip Bar Clearance:
inch Acceptable Tolerance:
1/32" (.032) to 1/8" (.125) inch 9.11.1.g Shunt Trip Frame Temperature:
°F Shunt Trip Coil DC Resistance:
Ohms Acceptable Value 55 Ohms to 67 Ohms at 75°F.
Ref er to Enclosure 11 for acceptable resistance if temperature is other than 75°F.
OF 9.12.1.h U/V Trip Coil Frame Temperature: ------
U/V Trip Coil DC Resistance:
Ohms Acceptable Value 230 Ohms to 260 Ohms at 75°F. Refer to 1 for acceptable resistance if temperature is other than 75°F
- Page 2 of 5 Rev. 8
BREAKER SERIAL NUMBER _____ _
- 1t M3Q-2 9.12.3.g. U/V Trip Bar Clearance: _______ inch Acceptable Clearance 1/32 (.032) to 1/8 (0.125) inch.*
9.12.4.d U/V Trip Attachment Coil Drop Out Voltage:
\\
9.13. 7 1st VDC 2nd VDC 3rd voe Acceptance Criteria:
- 1)
Voltage is 14.4 to 28.8 VDC.
- 2)
Voltage is within +/-5 volts of
- voe.
(Reference drop out voltage to be entered by supervisor)
- 3)
Voltage has not trended downward, over 2 successive test intervals, by 2 or more volts.
DATE VOLTAGE DATE VOLTAGE (Previous test data to be entered by supervisor)
Replacement U/V Trip Coil Frame Temperature:
°F Replace~ent U/V Trip Coil DC Resistance:
Ohms Acceptable Value:
230 Ohms to 260 Ohms at 75°F.
Refer to Enclosure 11 for acceptable resistance if temperature is other than 75°F.
9.13.17.g Replacement U/V Trip Bar Clearance:
inch Acceptable Clearance 1/32 (.032) to 1/8 (.125) inch.
9.13.19.d Replacement U/V Trip Attachment C.oil Drop Out Voltage:
1st VDC 2nd VDC 3rd VDC Acceptable Range:
14.4 to 28.8 Volts D.C.
The average value is the "reference 11 drop out voltage for this U/V trip attachment.
9.14.1.d Trip Bar Force Measurement:
1st gm.
2nd gm.
3rd gm.
Maximum Acceptable Force is 885 gm. for all trials.
Page 3 of 5 Rev. 8
BREAKER SERIAL NUMBER:..------
DATE:-..------------~
WORK ORDER NUMBER._ ________ _
M3Q-2 9.14.2.d U/V Trip Lever Force Measurement:
- ..lst ______ gm 2nd _____ gm 3rd _____ gm.
Minimum Acceptable Force is equal to or greater than 460 gm.
9.15.2.k Breaker U/V Trip Timing:
9.16.9 9.17.11 9.18.2 1st ____ 2nd _____ 3rd _____ _
Maximum Acceptable Value:
100 msec.
(6 cycles at 60 hz)
Breaker Shunt Trip Timing:
1st ____ _ 2nd ----
3rd._ ___ _
Maximum Acceptable Value:. 100 msec (6 cycles at 60 hz)
Breaker Closure Timing:
l.st ____ 2nd._ ___ 3rd:_ ___ _
Maximum Acceptable Tolerance: 200 msec. (12 cycles at 60 hz)
Breaker Megger Readings:
0 1 - 0 2 ---- 01-03 __ _
0 2 - 0 3 ---
fJ 1 -
Gnd ----
rJ 2 -
Gnd ----
fJ 3 - Gnd ---
Minimum Acceptable Value is equal to or greater than 2 megohms Page 4 of 5 Rev. 8
_ u.1 Cycle Counter Reading:
As Left:
cycles Data Reviewed:
Acceptable Unacceptable
~~~~
~~~~
_Remarks=------------------~--~~
Maintenance Supervisor Any data found out of specification shall have a Deficiency Report written against it and will be dispositioned by the Nuclear Engineering Department.
The Circuit Breaker will not be acceptable for service until all Deficiency Reports have been satisfactorily co!!pleted..
All Deficiency Reports properly completed:
Maintenance Supervisor Date Quality Assurance Date BREAKER SERIAL NUMBER.
M3Q-2 Deficiency Report Numbers:
Quality Assurance Page 5 of 5 Dat.e Rev. 8
MJQ-2
[
I I I I MAINTENANCE PROCECURE MJQ-2 ENCLOSURE 8 BREAKER "AS FOUND" / "AS LEFT" POSITION A TRIP BREAKER POSITION "AS FOUND" CONDITION UNIT #1 A BY-PASS B TRIP B BY-PASS UNIT lt2 A TRIP l
[
A 3Y-PASS l
l B TRIP I
B BY-PASS REVIEWED BY:
Maintenance Supervisor Date Quality Assurance Date Page l of 2 I
Rev. 8
A TRIP B TRIP
[
A TRIP B TRIP REVIEWED BY:
M3Q-2 BREAKER POSITION "AS LEFT" CONDITION UNIT #1
[
I UNIT ~2
[
A BY-PASS l B BY-PASS A BY-PASS B BY-PASS Maintenance Supervisor Date Quality Assurance Date Page 2 of 2 Rev. 8
.'.1AINTENANCE ?ROCEDuRE ~JQ-2 ENCLOSURE 9 REPEATED.VERIFICATION OF UNDERVOLTAGE TRIP ATTACHMENT TEST DATE:
TEST '2 DAT!::
Electric an TEST U OATl!:1 Electrician T!S1' lt4 Electri.CiAn TEST U DATE:
Electrici41\\
DATZ:
Electrician DATE:
Electri.c1an T!ST >>8 DATE:
E:lectri.cian 1'!ST >>9 DATE:
E:lectr1cian TEST no DATE:
Electrician FOLLOWING PROCEDURE STEP* 9.12.3.i CAUT:ON A THIRT.C ( 3 0) MINTJ't'!: WAIT IS i:IEQUIUD BE'IWEEH EACH TtST.
Maintenance Supervuor Maintenance Supervisor Maintenance Supen'isor M.aintenance Supervise:
Maintenance Supervisor Maintenance Supervisor Maintenance Supervisor MaintenAnce Supervisor
~aintenance Supervisor Page 1 of 2 TIME:
TIME; TIM!!1
. Til'IE:
1'!$:
TIME:
7!~:
Inspection Hold Point Inapecti.on Hold Point Inspection Hold Point
!nspection Hold Point Inspection Hold Point
- nspect1on Hold ?01nt
!~spect~on Hold ?oint
!nspect1on Hold ?01nt Rev. 8
DATE:
Electrician T!S'l' 112 DAT!!:
Electric Un TEST llJ OAT!!&
Electrician TEST 114 CATE:
Electrician TEST 115 DATE:
Electrician TEST ~6 DATE:
Electrician DATE:
Electrician TEST li8 DATE:
E:lectri.cian DATE:
Electrician TEST lilO DATE:
E:lectrician M3Q-2 FOLLOWING PROCEDURE STEP 9.~3.17.i CAUTION II. THIM"! (30) MINUTE WAIT IS REQUIIWl BETWEEN EACH TEST.
M.llinten.ance Supervisor Maintenance Supervisor l1aintenance Supervisor Maintenance Supervisor Maintenance Supervisor l1aintenance Supervisor
~aintenance Supervisor
~aintenance Supervisor Page 2 of 2 TIME:
TIME:
TIME:
TIME:
TIME:
TIME:
TIME:
TI:'IE:
TIME:
Inspection Hold Point Inspection Hold Point Inspection Hold Point Inspection Hold Point Inspection Hold Point Inspection Hold Point
!nspection Hold Point rnspectLon Hold ?oint InspectLon Hold ?oint Rev. 8
MJQ-2 MAINTENANCE PROCEDURE MJQ-2 ENCLOSURE 10 OVERCURRENT TRIP BRACKET LOCATIONS AND DUST COVER MODIFICATIONS OVERCURRENT TRIP DUST COVER~
EXISTING HOLE
\\"-..NUT INEW)
- LOCK WASHER (NEW) 0 Page 1 of 1 Rev. 8
/
i I
I
zi..sl I
ZM z.so s l4i i.:J c.J
~
1---
tqo
~
- !]
~
d
!J>
Q
<:j M3Q-2 MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE 11 U/V AND SHUNT TRIP COIL RESISTANCE VS TEMPERATURE CURVES 1 Page l of 2
'\\.
--'. '\\\\.
.~
~' --
~ \\ -
1-
- ~ \\ (
\\""-
~"' ~
~~. "- -~ -,,, ~
i I
=<.1:1 :
. co~i ~ -
\\eo'r.c.~:.;:.*
~1: Z.S 0~
Rev. 8
I 'i
~
~
~
~
- fl,
~
~~
.J -
0
~
- M3Q-2 I I.
i I
~=~
I i
I
.SS !
\\\\
I
~
I
<?
- ~
5S
\\ :<.. *""""
I",.
'7= \\,,I~"::~ ~ -
- ~.:,
- . ~ \\' \\ ~ ~
1-
)~
"t.i:,.
"":..I..
- ** ~-z. -, -
. c =~ 7 :- : \\ 00 '%, ~..;:;..:c. -:-~ ~,"'.
d-i"" 1 Page 2 of 2 Rev. 8
~
f J,
- ::.:,\\.... ~~~.~:*-:~-~ r
~:
J'
- . \\,_ -.,.
MAINTENANCE PROCEDURE M3Q-2 ENCLOSURE 12 TRIP BAR & tNTA FORCE MEASUREMENT DETAILS
-""'.-, ----1 Brf:!4 R~r
- (0
~
- ~
,:rtJmtt I
i
/
- -<) iA1~
I ///
oA/l
,,/
~'
AcW Wfil.*fi,t" I *re ":." )..C ""t:
fr*f N1.-1..f!.
-r:::----- 2 Page 1 of 2 IR1P AA B
- JI "001r10/U~L -...iivHT
~DDEI) ttiRE f& Cl'ErK T~1PP1NG foACE
~-*
Re*
,(: -
NOTE: PRESS HARD YOU ARE MAKING FIVE (5) COPIES f**: :-~.. ~~-~'-,.
'.-:i '
A"DMINISTRATIVE PROCEDURE 3 CHANGE TYPE:
ON-THE-SPOT CHANGE
~
D
~
PERMANENT (GREENJ
- TEMPORARY (ORANGE!
~~o'< ~f\\~ QJ\\.o).
\\~~~, \\.-\\~ ~ee..~') i\\,r C..\\ct...;,; \\'}<~~
PROCEDURE TITLE(,.~\\ - \\\\1\\NM-.\\ ~\\C~-+\\~'1' '\\,~\\.'f"i..._"\\,...__ ~~ \\~l t.'IU&
- EXPIR.ES:
ALL ON-THE-SPOT CHANGES TO BE CONSIDERED FOR APPLICABILITY TO BOTH UNITS.
lR1 UNIT I PROCEDURE NO.
W 3 ()l REV. NO.
.f' CHANGE NO.
IZI uN1T z PROCEDURE No.
m 3 G - ~
REV. NO.
?
CHANGE NO.
PROPOSED CHANGE:
/
J c_~~ "-'je.
NC lo SU r'E!_
~
P~Jc. I of' I Vtv;t ON~
\\.Jt.J 1T Tw 0
Ll II I
n 7,-,f o~ '/"1 a.o l-
"ii Tll. If' 0 ~ y,J ~ I 'J -I 118 Tr;f o ~y,.; ~o I - 3 "11 11 By Pn-s s 3-.s 4 '17 :J. '</ t3 rt8 fiyphSS L/- d..L/Y 7d..i:, <; 13
'8" Tll.IP --
o~'(N a I CJ - '3 1}9 IJyf¥tSS -.3 a..,q Y 7Q.. & J> £3 c~ u f3 'ff'IJSS - '-/ ;J. '/ '/ 7 ~ '1 i' 13 REASON FOR CHANGE:
To c.orrc.c. T r'1e..
S-e.IZ.11'- L No\\
13 '/ f Pr~S. fo.-5 '-+, O~-S "--Ii'\\ """"'2 \\:
ACTION TAKEN FOR OTHER UNIT:
AUTHORIZATION:
- suPERVISOR IN CHARGE DUTY SENIOR SHIFT SUPERVISOR OR SHIFT SUPERVISOR DISTRIBUTION TO FIELD COPIES COMPLETED (IF APPLICABLE)
RESPONSIBLE SUPERVISOR
- SIGNATURE ALSO VERIFIES THAT APPLICABILITY TO BOTH UNITS HAS BEEN CONSIDERED.
ACCEPTABLE:
POST CHANGE-REVIEW/APPROVAL YES NO DD D*D DD
- _I __ I DEPARTMENT HEAD QUALITY ASSURANCE
'SORC (CHAIRMANJ MEETING NO.
GENERAL MANAGER* SALEM O!°ERATIONS RETURN COMPLETED OR REJECTED FORM TO DEPARTMENT REQUE!?TING CHANGE.
FOLLOW-UP TO REJECTED ON-THE-SPOT CHANGE ACTION TAKEN:
PERFORMED BY:
SIGNATURE RETURN TO DEPARTMENT HEAD FOR ROUTING THROUGH POST CHANGE-REVIEW/APPROVAL. CYCLE.
AP.3 FORM AP.J-1 DATE DATE DATE
- JATE DATE DATE
"'-/
i REV. 1Z
__ I),.,
/. f NOTE; PRESS HARO YOU ARE llllAl<ING F'IVE (!)COPIES ADMINISTRATIVE PROCEDURE 3 CHANGE TYPI!::
~UNITI
~
UNITZ PROCEDURE NO. --""'m""'"..
3~Q-_-_...q,,
...... _______ REV. NO. __ 9 __ CHANGE No._3 PROCEDURE NO. --""'cn~...:13o&...;Q-.._-_.o.-
...... _______ Rl:V. NO. __.8
____ CHANGE N0. _ _.3.___
PROP'OSl:D CHANGE:
ST'-Q 9.,,3 (C)
~~
J Ge l.H-C-.
c.. /,PrM) c.
tJ..'-
1~ r.s~ rt""-
1t4J f""A1 r~/,
f/,,~ ~ f~ fo
~e1t-o :
x; /! ttJ;-ul 1-meAJ *r of Co,.J I"-t is AJof AJCc...ess1ta.y 1 afe11J
'the. bc-eA>k.e,.
IJe.Lc. ~e. f-hc.
LA~ i- ("~I-0 t-I-Ac.
StAI """'-C.. : ~NO To.l~ 9.7 pro cee.c/.
REASON P'09' CH.ANGIE:
'/OIJ coulJ ~L.f +o V<tL.'/ /j,f°Lln.Jf
- c. ~~'-L~ j 1-h e..
A-'-' K Sw 1 e~
'4;1.JQ d,..) c::. iJN AJ<l '-k ACTION TAKEN l"OR OTHER UNIT:
-3+vs '* 1.. 'I ~ '~*'* s f), ~ sec.o,.,ullf.ILy
- AUTHORIZATION:
Z.=tl-K DISTRIBUTION TO FllELD COP'llES COMPLETED (IP Al'PLlCA*LE) s::i 9 ti:~.t._. ~
"*SPGN~"YISO"
ACCEPTABLE:
POST CHANGE-REVIEW/APPROVAL
~-~
~~~
L...!::...J L-1 VI'//~---
[1J {;? l rrl\\dllfll'-._*_q__,.~-*
...,*..,.~..,*011:-+"b'""_.,T,M,...~~~T"""'=\\ ~~l:=AD=-----
1 ?1 /II r ____
-~_
- _Q_U_"_.... _*_T_v=_,,._s_\\_-u'ii._bii'i'=
. ~ L-J"=""
-~: ~-
~..:. !,"."
\\S 5 o~i-
!IORC ICKAl"MA*I MC.TING NO.
- r-1 __
~9 GICNICR~~
- SAL.SM OP'l:RATIONS RICTU"N COMP'L.&Tl:O OR RW:Jl:CTIJ:O FORM TO Ol:P'A,.TMll:NT "CQUICSTING CH ANGii:.
FOLLOW-UP' TO REJECTED ON*THE*SPOT CHANGE ACTION TAKEN:
PERl"ORMl:D *Y:
SIGNATU"C "l:TU"N TO Oll:PA"TM*NT Hl:AD P'CI" "OUTING TM"OUGH P'OST CHANG**tt*V**WIA.. ftOYAL. cvci.*.
OATE OATll:
OATI:
OAT*
ltSV. I&
NOTE. F"RESS HARO YOU ARE MAKING FIVE (5) COF"IES CHANGE TYF"E:
ADMINISTRATIVE PROCEDURE 3 ll'ERMANENT {GREEN I D *TEMll'ORARY ON*THE*SPOT CHANGE AL.I.. ON*THE*SPOT CHANGES TO BE CONSIDERED FOR AF"F"L.ICABIL.ITY TO BOTH UNITS.
~UNITI
~
UNITZ PAOCEDUAENO.~--~rn~~.3~c-.~
...... -__.':l,,,.... ____________ ~
PAOCEDURENO. __......;tn-...,._3,..._C?,_._* __ cJ-
______________ ~
AEV. NO.
REV. NO.
PROPOSED CHANGE:
C:.h'\\N3 e, eloJJa~..;re_
vAJ. r o"" e.
~'-"~
~.
pt+j <:.
t.JAJ,T Tl4Jc CHANGE NO.
£ CHANGE NO.
Qr' "A" T1!1P
- OQ.YAJ ~o,... J "a** nil'.. o ;;.y1i1 ~o I - 3 13"/p~S -
3-~4'°'/ ~t.'1 B
'f:J.. Tr*f.~
o~y~.J.1'1-1 "IJ **.
Tri~ - o~y,..; ~ a<;-3
'"If,, Stp1t-.SS..
.3~'1t7~'-"<t a
'I- ;l"I'/ ~b
~ a
. '*s.. i1ptt-SS -
£/.~'# '17~ '-~ B REASON FO" CHANGE:
- i:-a v~,.. TE.
LtJ Tes I
,j e1t.1 it L Nos f°.j' ;t;o~.l oA.J tJN." tr o..ve 'llfltJ fqJo.
1tiJ ACTION TAl<EN FOA OTHER UNIT:
ORANG!!:
~
~
AUTHORIZATION:
Z.-=(1 =trs=
T SUllE"VISO" DATE 0" SHll"T SUllC"V~O"
, ** ~l. Lb..
DISTRIBUTION TO Flll:LD COPIES COM~LETED (IF A~~LIC:ABLE)
- '*s1GNATUl'IE ALSO v11:R11"1cs THAT A"'"-IC:A*11..1Tv TO *OTH UNITS HAS *CCN c:0Ns1011:R11:0.
ACCEPTABLE:
POST CHANGE-REVIEW/ APPROVAL
'fl!:S NO
...f-so~c:. IC:H Al RM AN}
... :.. 0¥..ht!:::.Ji RETURN COM.. l..ETEC OR Rl!:JECTEC FORM TO 01!:.. ARTMl!:NT Rl!:QUl!:STING CHANG!!:.
FOL.l..OW*UP TO REJECTED ON*Tlo-lE*SPOT CHANGE ACTION TAKEN:
PERFORPo!tED BY:
SIGNATU"C "ll:TU"N TO CC"'A"TMll:NT HCAO l"O" ROUTING TH.. OUGH ll'OST C:HANGll:*"ll:VICW/Allll"OVAI.. CYC:l.I:*
l'Oltll~t
£ '"/7-P~
ClATE
-~J; zlx' )-
~or+e: _
~r~1<&s ClATI!:
CATE ltCV. U.
0 I
NOTE: PRESS HARO YOU ARE MAKING FIVE(!) COPIES CHANGE TYPE:
ADMINISTRATIVE PROCEDURE 3 ON*THE*SPOT CHANGE
[2(f l"ERMANENT (GREEN*, D *TEMl"ORARY ORANGE PROCEDURE TITLE AL.I.. ON-THE-SPOT CHANGES TO BE CONSIDERED FOR APPLICABILITY TO BOTH UNITS.
~UNITI PROCEDURE NO.
!1:1. 3 G)- ~
REV. NO.
~
CHANGE NO. '
0 UNITZ.
PROCEDURE NO.
m3~-~
REV. NO.
~
CHANGE NO.
PROPOSED CHANGE:
ACTION TAKEN FOR OTHER UNIT:
s ""'e:
AUTHORIZATION:
OR SHll'"T SUl"ERVISOR DISTRIBUTION TO FIELD COPIES COMPLE;:TED (IF APPLICABLE)
SI~
RESPONSIBLE SUPERVISOR
- °*SIGNATURE ALSO VERIFIES THAT APl"LICAlllLITY TO BOTH UNITS HAS BEEN CONSIDERED.
ACCEPTABLE:
YE!I NO RETURN COMPLETED OR REJECTED FORM TO DEPARTMENT REQUESTING CHANGE.
FOL.L.OW*UP TO REJECTED ON-THE-SPOT CHANGE ACTION TAKEN:
PERFORMED BY:
SIGNATURE RETURN TO DEl"ARTMENT HEAD l'"OR ROUTING THROUGH POST CHANGE-REVIEW/APPROVAL CYCLE.-
-i.-1.1-Rr 4
DATE a 137><~
J DATE DATE
- JATE DATE REV. t;