ML18092A371

From kanterella
Jump to navigation Jump to search

Forwards SER Re Valve Operability Demonstration Info for 10-inch Vacuum Relief Isolation Valves,Based on Review of 791108,21,810731,820218 & 830607 Submittals.License Change Request Should Be Submitted within 45 Days.W/O Encl
ML18092A371
Person / Time
Site: Salem  
Issue date: 10/30/1984
From: Varga S
Office of Nuclear Reactor Regulation
To: Uderitz R
Public Service Enterprise Group
References
TAC-51881, TAC-51882, NUDOCS 8411150145
Download: ML18092A371 (1)


Text

October 30, 1984

  • Docket Nos. 50-272 and 50-311 Mr. Richard A. Uderitz, Vice President -

Nuclear Public Service Electric and Gas Company Post Office Box 236 Hancocks Bridge, New Jersey 08038

Dear Mr. Uderitz:

DISTRIBUTION Docket Fi le LPDR ORB#l Rdg DFischer OELD EJordan ACRS 10 RWright NRC PDR Gray File CParrish DEisenhut JPartl ow JNGrace RFerguson

SUBJECT:

SER FOR SALEM 1 AND 2 ON CONTAINMENT ISOLATION DEPENDABILITY BY DEMONSTRATION OF CONTAINMENT PURGE AND VENT VALVE OPERABILITY (TAC NOS. 51881 AND 51882)

We have completed our review of your submittals providing valve operability demonstration information for the 10-inch pressure vacuum relief isolation valves for Salem Unit 1 and Unit 2 dated November 8, 1979, November 21, 1979, July 31, 1981, February 18, 1982, and June 7, 1983.

The staff finds the information submitted demonstrated the ability of the Masoneilan International 10-inch valves, when these valves are blocked by mechanical means to an opening angle of 60° or less, to close against the buildup of containment pressure in the event of a DBA/LOCA.

Our Safety Evaluation Report is enclosed.

In order to complete our effort on this issue, appropriate Technical Specifications should be issued to reflect the limitation of opening angle for the 10-inch valves.

You should submit a license change request to accomplish this task within 45 days from receipt of this letter.

Enclosure:

As stated cc w/enclosure:

See next page ORM@L Dm-clier;ps 10/~1/84

/s/SAVarga Steven A. Varga, Chief Operating Reactors Branch #1 Division of Licensing