ML18087A596

From kanterella
Jump to navigation Jump to search
Proposed Tech Spec 3.7.3 Re one-time Change to Permit Operation for Addl 24-h W/Component Cooling Water HX Rendered Inoperable
ML18087A596
Person / Time
Site: Salem 
Issue date: 11/22/1982
From:
Public Service Enterprise Group
To:
Shared Package
ML18087A595 List:
References
NUDOCS 8211300253
Download: ML18087A596 (1)


Text

PLANT SYSTEMS 3/4. 7. 3 COMPONENT COOLING WA/ER SYSTEM

  • LIMITING CONDITION FOR O~ERATION 3.7.3 At least two independent componerit cooling water loops shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3 and 4.

ACTION:

With only one component cooling water loop OPERABLE, restore at least two loops to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.*

SURVEILLANCE REQUIREMENTS 4.7.3 At least two component cooling water loops shall be demonstrated OPERABLE:

2.

At least once per 31 days by verifying that each valve (manual, power operated or a 11tomat i c) servicing safety related equipment that is hot locked, seal~d, or otherwise secured in position, is in its correct position.

  • The time for completion of repairs to the No. 22 Component Cooling Water Heat Exchanger shall be extended from 0700 hours0.0081 days <br />0.194 hours <br />0.00116 weeks <br />2.6635e-4 months <br /> on November 23, 1982 to 0700 hours0.0081 days <br />0.194 hours <br />0.00116 weeks <br />2.6635e-4 months <br /> on November 24, 1982.

If repairs are not completed by that time, the unit shall be placed in HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SALEM - UNIT 2 3/4 7-12