Discusses Evaluation of 801031 Fire Test Rept, Cable Tray Fire Test - 3M Fire Barrier Sys. Sys Exhibits Equivalent or Better Characteristics than Kaowool & Can Provide Acceptable Fire Barrier for Cable Trays & Cables
ML18085B074
Person / Time
Site: Salem  PSEG icon.png
Issue date: 03/18/1981
From: Tedesco R
Office of Nuclear Reactor Regulation
To: Mittl R
Public Service Enterprise Group
References
NUDOCS 8103240604
Download: ML18085B074 (4)


Text

i.

'*~.,,__ -i'.

  • ~.

.. *.~-

ar-I.-

MAR 18 1981 Docket Nos.:

50-311/272 Mr. R. L. Mittl, General Manager Licensing and Environment Energy Supply and Engineering


e*

DISTRIBUTION:

Docket File 50-311/272 PDR LPDR NSIC TERA Public Service Electric andGas Company 80 Park Plaza, Tl7A LB#3 Files RTedesco DRoss SVarga TNovak JKerri gan FMiraglia GHarrison RFerguson VBenaroya VNoonan Newark, New Jersey 07101

Dear Mr. Mittl:

SUBJECT:

SALEM CABLE TRAY FIRE BARRIER EVALUATION; DOCKET NOS. 50-311/272 To satisfy the cable tray fire protection requirements of Section III.G of the Appendix R to 10 CFR Part 50, you have proposed to utilize the 3M fire barrier system.

The fire test for this material/system has been documented in a report provided by you, 11Cable Tray Fire Test - 3M Fire Barrier System 11, dated October 31, 1980.

The fire test was based oh the ASTM E-119 fire test method.

The 3M material tested was compared to Kaowool as a baseline reference, which has been previously approved by us.

We have evaluated your fire test report and conclude that it demonstrates that the 3M fire barrier system exhibits equivalent or better characteris-tics than Kaowool, and therefore can provide an acceptable fire barrier for cable trays and cables. Based on our evaluation, we conclude that the use of the 3M fire barrier system meets the requirements of Appendix R to 10 CFR Part 50 and is acceptable.

cc: See next page.

Sincerely, Ofllihat itgned by Robert ~ Tedeaoo Robert L. Tedesco, Assistant Director for Licensing Division of Licensing OFFICE~

DL: LB#3 SURNAME~ "jP.**K******tj:!/""." :~..

.. ~~~~-~--.

DATE~ *.Jfi&.~J......... ).

P..1j_q._,...... R~T... ~.!:i~9.......................................................................................

... ~l.~!.~1.,............................ ********************* *****************.......................

NRC FORM 318 110/SOJ*NRCM 0240 OFFICIAL RECORD COPY ii USGPO: 1980-329-824

e

,e UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555.

MAR 18 1981 Docket Nos.:

50-311/272 Mr~ R. L. Mittl, General Manager Licensing and Envi~onment

  • Energy Supply and Engineering Public Service.Electric and Gas Company 80 Park Plaza, T17A Newark, New Jersey 07101

Dear Mr. Mittl:

SUBJECT:

SALEM CABLE TRAY FIRE BARRIER EVALUATION; DOCKET NOS. 50-311/272 To satisfy the cable tray fire protection requirements of Section III.G of the Appendix R to 10 CFR Part* 50, you have proposed to utilize the 3M fire barrier system.

The fire test for this material/system has been documented in a report provided by you, 11 Cable Tray Fire Test-3M Fire.

Barrier System 11

, dated October 31, 1980.

The fire test was bas.ed on the ASTM E-119 fire test method.

The 3M material tested was compared to Kaowool as a baseline reference, which has been previously approved by us.

We have evaluated your fire test report arid conclude that it dem6nstrates that the 3M fire barrier system exhibits equivalent or better characteris-tics than Kaowool, and therefore can provide an acceptable fire barrier for cable trays* and cables. Based on our evalua~ion, we conclude that the use of the 3M fire barrier system meets the requirements of Appendix R to 10 CFR Part 50 and is acceptable.

cc:

See next page.

Sincerely, Q~JJ>t~~~;

Robert L. Tedesco, Assistant Dire~tor for Licensing Division of Lic~nsing

Mr. R. L. Mittl, General Manager cc: Richard Fryling, Jr., Esq.

  • Assistant Gen~ral Counsel Public Service Electric & Gas Company 80 Park Plaza Newark, New Jersey 07101 Mark Wetterhahn, Esq.

Conner, ~core & Caber Suite 1050 *.

1747 Per.nsylvania Avenue, N. W.

Washington, D. C.

~0006 Mr. Leif J. Norrholm c/o U. S. Nuclear Regulatory Commission Drawer I Hancocks Bridge,. New Jersey 08038

'I

  • .4