Docket No.:

50-311 Mr. R. L. Mittl, General Manager Licensing and Environment Energy Supply and Engineering Public Service Electric and Gas Company 80 Park Plaza, T17A Newark, New Jersey 07101

Dear Mr. Mittl:

SUBJECT:

ANNUNCIATOR ALARM VOLUME

<1-* *--

By letter, dated January 16, 1981, you proposed to reduce the audible alarm level for the overhead and console annunciators from 20dB above background noise to lOdB above background noise with the emergency ventilation fan in se,rvice.

The staff concurs in this action. The proposed audible i:'ilarm level above background is consi'S._tefit with current NRC recommendations on other NTOL plants.

If you have any further questions in this regard, please contact us*.

cc:* See next page.

DISTRIBUTION:

Docket File 50-311 LPDR PDR NSIC TERA RTedesco FMiraglia JKerri gan Sincerely, Robert L. Tedesco, Assistant Director for Licensing Division of Licensing r*..

~-1 NRC FORM 318 ll0/80J NRCM 0240 OFFICIAL RECORD COPY

"' USGPO: 1980-329-824

~/II Mr. R. L. Mittl, General

~anager cc: Richard Fryling, Jr., Esq.

Assistant General Counsel Public Service Electric & Gas Company 80 Park Plaza Newark, New Jersey 07101 Mark Wetterhahn, Esq.

Conner, Moore & Cober Suite l 050 1747 Pennsylvania Avenue, N. W.

Washington, D. C.

L0006 Mr. Leif J. Norrholm c/o U. S. Nuclear Regulatory Commission Drawer I Hancocks Bridge, New Jersey 08038 f'EB 9 1981