UNITED STATES NUCLEAR REGULATORY COMMISSION REGION I 631 PARK AVENUE KING OF PRUSSIA, PENNSYLVANIA 19406 October 24, 1980 Public Service Electric and Gas Company ATTN:
Mr. F. W. Schneider Vice President - Production 80 Park Plaza - 15A Newark, New Jersey 07101 Gentlemen:
The enclosed Supplement No. 3 to IE Bulletin 79-018, "Environmental Qualifica-tion of Class lE Equipment," is forwarded to you for action. This supplement clarifies two issues raised by Supplement No. 2.
These are (1) the submittal of qualification information for equipment resulting from TM! Action Plan requirements and (2) the qualification of equipment which is required to achieve a cold shutdown condition.
This action is a result of industry feedback to NRC regarding interpretation of Supplement No. 2.
The information presented is applicable to your submittal regarding environmental qualification of Class lE equipment which is required by November 1, 1980.
If you desire additional information regarding this matter, please contact this office.
Sincerely,
~~-~r~
Director
Enclosures:
- 1.
Supplement No. 3 to IE Bulletin No. 79-018
- 2.
List of Recently Issued IE Bulletins CONTACT:
S. D. Ebneter (215-337-5283) cc w/encls:
F. P. Librizzi, General Manager - Electric Pr~duc:
E. N. Schwalje, Manager - Quality Assurance R. L. Mittl, General Manager - Licensing and Environment H. J. Midura, Manager - Salem Generating Station R. A. Uderitz, General Manager - Fuel Supply Department (80 11 0 1 0 320 Q
UNITED STATES
~SINS No.:
6820 7\\ccessi.on No.:
8008220248 IEB Sup #3 to 79-018 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT.
WASHINGTON, D.C.
20555 October 24, 1980 IE Bulletin No. 79-016 Supplement No. 3:
ENVIRONMENTAL QUALIFICATION OF CLASS IE EQUIPMENT Description of Circumstances:
Two issues were raised by Supplement No. 2 which require clarification. These are:
(1) the dates required for submittal of qualification information for TMI related equipment, and (2) whether the equipment required to achieve a Cold Shutdown condition must be environmentally qualified if the licensing basis for the plant was a Hot Safe Shutdown condition.
(1) Supplement No. 2 (Q. l, Q.5) addressed the minimum cold shutdown require-ments.
The staff position on this issue is that the licensee must identify and environmentally qualify the equipment needed to complete one method (path) of achieving and maintaining a cold shutdown condition.
The equipment of other paths must be reviewed to assure that its failure will not aggravate or contribute to the accident (ref.
Q.5 Supp. No. 2).
Due to an inconsistency between Supplement No. 1 and Supplement No. 2, the staff positic;m on this issue was unclear.
Therefore, the following will apply:
- a.
The qualification information for equipment needed to achieve and maintain a Hot Safe Shutdown condition must be submitted not later than November 1, 1980.
- b.
The qua.lification information for equipment required to achieve and maintain a Cold Shutdown condition (ref. Q.1 and Q.5 of Supplement No. 2) must be submitted not later than February 1, 1981.
(2)
IEB 79-018 required a 90 day response which was due in mid-April 1980.
Supplement 1 (Feb. 1980) informed licensees that equipment which was 11planned11 to be installed as a result of lessons learned need not be addressed in that response.
Some of this equipment has since been installed.
Supplement No. 2 (Q.5, Q.21) identified that the staff posi-tion was that equipment which is installed should be treated in a manner similar to all other safety-related electrical equipment and be addressed in the November 1, 1980 submittal.
This position represents no change in staff position regarding the scope of the review.
However, since the staff position on this issue was unclear the following will apply:
- a.
Qualification information for installed TMI Action Plan equipment must be submitted by February 1, 1981.
- b.
Qualification information for future TMI Action Plan equipment (ref.
NUREG-0737, when issued); which requires NRC pre-implementation review, must be submitted with the pre-implementation review data.
lEB 79-018 Sup #3 October.24, 1980 Page 2 of 2
- c.
Qualification information for TMI Action Plan equipment.currently
- under NRC review should be submitted as soon as possible.
- d.
Qualification information for TMI Action Plan equipment not yet installed which does not require pre-implementation review should be submitted to NRC for review by the implementation date.
The above items l and 2 represent no change in staff position regarding the scope of the 79-0lB Supplement 2 review.
IE Bulletin No. 79-018 was issued under a blanket GAO clearance (8180225 (R0072), clearance expired July 31, 1980) specifically for identified generic problems.
Supplement No. 3 to Bulletin 79-018 is for information, hence no GAO clearance is required.
IE Bulletin No. 79-0lB Supplement No. 2 October 24, 1980 RECENTLY ISSUED IE BULLETINS Bulletin Subject No.
Supplement 3 Environmental Oualifica-to 79-0lB tion of Class lE Equipment 80-22 Automation Industries, Model 200-520-008 80-21 Revision 1 to 79-26 Revision 1 to 80-19 80-20 80-19 80-18 Supplement 3 to 80-17 Supplement 2 to 80-17 (Not Used)
Boron Loss from BWR Control Blades Failures of Mercury-Wetted Matrix Relays in Reactor Protective Systems of Operating Nuclear Power Plants Designed by Combustion Engineering Failures of West_inghouse Type N-2 Spring Return to Neutral Control Switches Failures of Mercury-Wetted Matrix Relays in Reactor Protective Systems of Operating Nuclear Power Pl ants Designed by Comb us ti on Engineering Maintenance of Adequate Minimum Flow Thru Centrifugal Charging Pumps Following Secondary Side High Energy Line Rupture Failure of Control Rods to Insert During a Scram at a BWR Failure of Control Rods to Insert During a Scram at a BWR Date Issued 9/30/80 9/12/80 8/29/80 8/15/80 7/31/80 7 /31/80 7 /24/80 8/22/80 7/22/80 Issued To All holders of a power reactor OL or CP All holders of a radiography license All holders of a BWR power reactor OL All holders of a power reactor OL or CP All holders of a power reactor OL or CP All holders of a power reactor OL or CP All holders of a PWR power reactor OL or CP All holders of a BWR power reactor OL or CP All holders of a BWR power reactor OL