March 7, 1980 The enclosed IE Information Notice No. 80-08, The States Company Sliding Link Electrical Terminal Block, is forwarded to you for information.
No written response is required.
If you desire additional information regarding this matter, please contact this office.
Sincerely,
Enclosures:
i~
IE Information Notice No. 80-08 with Attachment
- 2.
- List of Recently Issued IE Information Notices CONTACT:
S. D. Ebneter (215-337-5296) cc w/encls:
F. P. Librizzi, Gene*ral Manager - Electric Production E. N. Schwalje, Manager - Quality Assurance R. L. Mittl, General Manager - Licensing and Environment H. J. Midura, Manager - Salem Generating Station
/,
8 0031902 79
~
(
ENCLOSURE 1 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D. C.. 20555 SSINS: 6870 Accession No.:
7912190689 IE Information Notice No. 80-08 Date:
March 7, 1980 Page 1 of 1 THE STATES COMPANY SLIDING.. LINK ELECTRICAL TERMINAL BLOCK Description of Circumstances:
On July 19, *1979, the Consumers Power Company notified the Nuclear Regulatory Commission of a defect found in the sliding link electrical terminal block manufactured by the States Company, a subsidiary of Multi Amp Corp.
The defective terminal blocks were found at the Midland plant.
The connection between the two slotted bars on the terminal block is made by a U"-shaped sliding link and spacer located between the two bars.
The top of the LI-shaped link and the spacer are drilled and the bottom of the link is threaded to accept a 8-32 screw.
When the screw is tightened it binds the link, spacer and bar together to make electrical connection.
Looseningthe screw and sliding the link from between the bars breaks the connection.
The purpose of the link is to provide easy insertion of test instruments, etc. into the circuit:
The defect, which has been identified in 5% of the terminal blocks checked, occurs in the form of a crack between the threaded screwhole and the side of the LI-shaped link.
When the screw is tightened the crack widens and a poor or fntermittent electrical connection can result.
A defective link is impossible to cinch tightly in place aqd is* difficult to detect visua-lly. shows the States Company terminal block.
The defect, a crack in the bottom portion of the metal LI-shaped link, is displayed in the exploded view of the terminal block assembly.
These terminal blocks are widely used in the nuclear industry and niay be used as permanent installations in safety related systems.
The defective mechanical connection can cause an electrical circu.it malfunction.
This Information Notice is provided to inform licensees of a potenti'ally significant matter. It is expected that recipients will review the informa-tion for* applicability to their facilities.
No written response to this IE Information Notice is required.
However, the reporting. requirements as set forth in the regulations must be met.
If you require additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.
Attachment:
Grap.hie Display of Terminal Block
~.,,-
~*-.::-**
Information Notice No. 79-32 79-33 79-34 79-35 79-36 79-3T 80-01 80-02 80-03 80-04 80-05 80-06 80-07 ENCLOSURE 2 IE Information Notice No. 80-08 Date:
March 7, 1980 Page l of 1 RECENTLY ISSUED IE INFORMATION NOTICES Subject Separation of Electrical Cables for HPCI and ADS Date Issued to Issued 12/21/79 All Power Reactor Faci~
lities with an Operating
- License (OL) br Construction
- Permit (CP)
Improper Closure of Primary 12/21/79 All Power Reactor Faci-Containment Access Hatches lities with an OL or CP Inadequate Design of Safety-12/31/79 All Power Reactor Faci-Relat.ed Heat Exchangers lities with an OL or CP Control of Maintenance and Essential Equipment Computer Code Defect in Stress Analysis of Pipi~g Elbow*
Cracking in Low Presssure Turbine Discs Ftiel Handling Events 8X8R Water Rod Lower End Plug Wear Main Turbine Electro-hydraul ic Control System BWR Fuel Exposure in Excess of Limits Chloride Contamination of Safety Related Piping and Components Notification of Signif-icant Events Pump Fatigue Cracking 12/31/79 A 11 Power Reactor Faci-1 iti es with an OL or CP 12/31/79 All Power Reactor Faci-1 ities with an OL or CP 12/31/79 All Power Reactor faci-lities with an OL or CP 1/4/80 All Power Reactor Faci-lities with an OL or CP 1/25/80 All BWR Faci 1 iti es with an OLor CP 1/31/80 All Power Reactor Faci-litie~ with an OL or CP 2/4/80 All BWR Facilities with an OL or CP 2/8/80 All Power Reactor Faci-1 ities with an OL or CP and applicants for a CP 2/27/80 All Power Reactor Faci-lities with an OL and applicant for OL 2/29/80 All Power Reactor Faci-lities with an OL or CP