Text
.ti ti MONTH May 1979 e
AVERAGE DAILY UNIT POWER LEVEL IXJCKET NO.
50-272 UN IT Salem #1 DATE June 11, 1979 COMPLETED BY L. K. Miller TELEPHONE 609-365-7000 X507 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL 1
2 3
4 5
6 7
8 9
10 11 12 13 14 15 16 Pg.
2 of 16 8.1-7.PJ.
(MWe-NET) 0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
(MWE-NET) 17 0
18 0
19 0
- 20.
0 21 0
22 0
23 0
24 0
25 0
26 0
27 0
28 0
29 0
30 0
31 0
7 9 061 5 0 15'3' '.
- i. Unit. Naire:
S~lem # 1
- Notes:
- 2.
Reportinq Period: ___
. _Ma:_.._y_l_97_9~~-----
3.. Licel'sed 'llle:aral Power Ufit) :
3338 4.*
Na!Ieplate Ratinq {Gzcss Kfe) :
1135
~
- s.
Cesign Electrical Rat.inq (Net.!<fie) : __
1_09_0 ___ _
- 6.. MaxjJmJm. Dependable Capacity (Gross. Kfe) :
1124
- 7.
MaxilmJm* Dependable Capacity {Net MNe) :
1079 50-272 DCCKET NJ.: _________
CATE :
June 11, 1979
~
BY: L. K. Miller
'lEt.EE'lDNE: 609-365-7000 X507
- a. If Changes Cccllr ill Capacity Ratings {Itens Nul!Cer* 3 'nirou;h 7) Since Last Repo:c:t, Give Reason:
- NONE
- --"":" ' ****NONE
- 9.
Power* Level To Which' Restticted, If Aey {Net MNe) :. ---------------------
10:... Reasons Far Restrictions,. u* Arri: -------NO~~-------------------
ll. EQur.; In Reporting Period l2. Nllni:eJ:'. Of Hours Psactor Was Critical l3. Reactor P.eserve Shutdcwn 5:)urs l4. !lours Generator On-Lina
~ --*~~
- 15. Unit P.eserve Shlll:down l:Toi.ti:s*
- 16.
Gzcss 'lbemal Energy Generated(MolH) l7.
Gress. Electrical Energy Genera.ted(MWH) l8. Net Electrical Energy Generated{mH) l9.. unit Service Factor
- 20. unit Availahiljty Factcr 2l. unit Capacity Factcr {Usinq MOC Net) 22:..
Unit Capaci:ey Factor {Usinq DER Net)
- 23. unit Forced outage Rate
'!bis Mcnth' 744 '*.*.*
0 0
0
.o 0
0 (4' 414) 0 0
0
.o 0
Year to Date 3,623 2,184.5 22.7 2,161.3 0
6,482,491 2,181,770 2,081,907 59.7 59.7 53.3 52.7 3.0
- 24.
Shutdoms Scheduled over Next 6 Months {Type, Date, arid Duration of Each) :
NONE Ctmllative 16,824 9,841.4 22.7 9,459.3 0
27,467,227 9,154,580 8,668,887 56.2 56.2 47.8 47.3 31.3
- 25. If Shut Down At Endo£ Rep:lrt Period~ Estimated oate o~ Startup: ____
J_u_l __ y ___ 2_1 __,_1_97_9 ________ _
- 26. units In Test Status (Prior to Catlnercial Cperation) :.
8-l-7.R2 Pg. 3 of 16 Forecast 9/10/76 11/01/76 12/20/76 Achieved 12/11/76 12/25/76 6/30/77
- 00.
DATE 79-189 4/3/79 1
F: Forced S:
Scheduled Page 4 Of 16 B-1-7.Rl.
TYP~
5 2
UNIT smn:roms l\\ND PCl'IBR IlEOOCTIONS REPORT MJlffll May 1979 METIDD OF OORATIOO RF.ASON2 s11l1ri!tr.
(llXIRS) ram REACroR 744 c
1 Reason:
A-B:Jui?lEl'lt Faiiure(Explain)
B-Maintenance or Test C-Refueling LICENSE EVEN!'
REPoRT I D-RegUlatm:y Restriction E--Operator Training & License Examinatibn F-ildministrative
~ational Error(Explain) j SYSTEM WIPOOENl' CODE4 CODE~
RC FUELXX M:?thod:
1-Manual 2-Manual Scram.
l-Aut:anatic Scram.
4-other (Explain)
A.
IDad Reduction DOCKET NO. :
50-272
~~~~~~~~~-
- UN IT !NAME:
Salem #1 DATE:
June 11, 1979.
COMPLETED BY:.L. K. Miller TELEPHONE: 609-365-7000 X507 CAUSE 1\\ND CORROCTIVE ACTION 'IO PREVENT REOJRRmCE Annual Refueling outage 4
Exhibit G - Instructions for Preparation of Data Entry Sheets for Licensee Event Report (LER) File (NlJREI}-0161) 5 Exhibit 1-Sarre Souroa II-Other (Ellplain)
B.
Continuation of Previous outage.
MAJOR PLANT MODIFICA~~S REPORT MONTH May i979
- DCR NO.
PRINCIPLE SYSTEM lED-0246 Pressurizer Spray lED-0312 Auxiliary Feed lED-0319 Fire Protection lE:C-0415 Transformer Instruments lE~-0416 Spent Fuel Cooling lEC-0450 Waste Liquid lEC-0471 Control Air TGA lOD-0044 Circulating Water
- DESIGN CHANGE REQUEST 8-l-7_~Rl DOCKET NO.:
50-272 UNIT 9-m:
Salem #1 DATE:
June 11, 1979 COMPLETED BY:
L. K. Miller TELEPHONE: ( 6 09) 365-7000 SUBJECT Replace positioners for PSl and PS3 Modify controls to allow restarting from Control Room X507 Construct equipment dike around 11, 12 and 13 Chillers Change watt transducer from Phase 2/N to Phase 2/3 Install tie-in for future heat exchanger Add Auxiliary Relay in Control Circuit of 1WL12 Replace 1CA129 with pipe nipple Install sample valves on upper motor bearing reservoirs Page 5 of 16
DOCKET NO.:
50-272
-~*-*
- r.t~JOR PLANT MODIFICATa1S UNIT-.ME:
Salem #1 REPORT MONTH May 191'1J DATE:
June 11, 1979
- DCR NO.
lED-0246 lED-0312 lED-0319 lEC-0415 lEC-0416 lEC-0450 lEC-0471 lOD-0044 COMPLETED BY:
L. K. Miller TELEPHONE: ( 6 09) 365-7000 X507 10CFRS0.59.
SAFETY EVALUATION The functional '.operation of the Pressurizer Spray Control Loop remains unchanged.
Instruments are to be replaced to improve system reliability.
The basic system design function remains unchanged.
The design change permits greater operator flexibility.
Design change is not safety related and will not affect safe operation of plant.
Safety related **equipment is not affected.
This change will improve watt transducer accuracy.
This design change does not affect any presently performed safety analysis nor does it create any new safety hazards.
The basis of the Tech. Specs. are not affected.
This design change is not safety related and does not, in any way, affect any safety related systems or the safe shutdown of the unit.
The subject design change request is non-safety related and does not impair any safety related system function or reliability function.
The changes involved are non-nuclear and seismic class 3.
This change affects a system which is not safety related.
Incorporation of this change will not affect a safety related system.
Page 6 of 16
DOCKET NO.:
50-272
~~~~
....... ~~~~~~~~~1
SUMMARY
OF SAFETY RELATED ~*NTENANCE UNIT N.: ___
s_a_l_em...;....;ti;..;n~------i
~
DEPARTMENT Performance REPORT MONTH May 1979 WORK ORDER EQUIPMENT NO.
900271 Instrument, N41 Power Range Drawer.
900276 Instrument, N43 Power Range Drawer.
900281 Instrument, N31 Power Range Drawer.
900284 Instrument, lROllA
~00288 Instrument, N42 Power ;:Range Drawer.
DATE :
June 11, 1979
~~~~~__;~~~~~~~--
L. K. Miller
~~~~~~~~~~~~~--
TELEPHONE: ___
6_0 _9 -_3_6_5_-_7 o_o_o __ x_5_0_7 ____ ~
FAILURE DESCRIPTION CORRECTIVE ACTION Out of spec.
Calibrated.
Input amps NM301, NM302 Recal. NM301, 302, 307, 1QM431B, Out of Spec.
1QM203A.
Detector voltage bistable Reset loss of Det. Voltage setpoint out of spec.
bistable.
Calibration check.
Check completed.
Out of Spec.
Calibrated.
900293
.Instrument, N32
- - Out of Spec *.
Clean, tightened connection, Source Range Drawer calibrated.
900294 Instrument, Spare Channel for backup.
Installed.
Source Range Det.
900484 Instrument, 1R012B Erratic Alarm.
Replaced relay, functionally checked.
900487 Instrument, 1R002.
Out of calibration.
Calibrated.
900494 Instruments, iROllA Initiate channel alarms.
Performed channel function 1R012B,
- 1R012A tests.
902654 Instrument, N32 Counts increased high.
Reverted to installed detector.
Source Range Drawer 902659 Instrument, N31 Check, Counts increased 10 Calibrated recorder.
Source Range Drawer. to 150.
902804 Valve Operator, Stroke valve.
Stroked valve.
10PR018.
Page 7 of 16
DOCKET NO.:
50-272
SUMMARY
OF SAFETY RELATED ~NTENANCE DEPARTMENT Performance UNIT N.:
DATE:
Salem Ill June 11, 1979 REPORT MONTH May 19 79 COMPLETED BY:
L. K. Miller TELEPHONE:
609-365-7000 X507 WORK ORDER EQUIPMENT FAILURE DESCRIPTION CORRECTIVE ACTION NO.
902805 Valve Operators, Stroke Valves.
Stroked valves.
12GB004, 14GB004.
902809 Valve, 10SS107.
Stroke valve.
Stroked valve.
902811 Valve, 10SS049.
Stroke Valve.
Stroked valve.
903001 Valve Operator, Position Indication erratic Replaced bezel lamps.
903010 Instrument, N32.
Indication erratic.
Cleaned connectors.
Source Range Drawer.
903024 Instrument, N32 Reads higher than N31.
Replaced detector, repaired Source Range Drawer.
connector.
903348 Instrument, lTIC-High inlet temperature.
Cleaned contacts, calibrated 0627A.
switch.
903359 Instruments, Out of Spec. Flow.
Calibrated.
1FA3165Z-02, 1FA3540Z-01,
... 1F.A3165Z-03, 1FA3540Z-02.
903362 Valve, llAFOll Will not open past halfway.
Adjusted controller, adjusted limit switch.
903368 Instrument, Output 2 failed.
Replaced, calibrated.
1PC0514A/B.
903370 Instrument, 1PL9493. Gauge failed.
Zero adjusted needle.
Q03376 Valve Operator, Will not open.
. Adjusted limit switch
- 11MS018.
903385 Valve Operator, No open indication.
Adjusted limit switch.
10CH030.
Page 8 of 16
DOCKET NO.:
50-272
SUMMARY
OF SAFETY RELATED ~NTENANCE UN IT N~
- _ __.s=a..... 1...
e...
m_...#1..__ ______ _
DEP ARTMEN.T Performance DATE: __ J_un_e __ l_l_, __
1_97_9 ______ ~---
~
REPORT MONTH~M~a~y.......,19~7~9--~~~-
COMl?LETED BY:
L. K. Miller TELEPHONE:
609-365-7000 X507 WORK ORDER EQUIPMENT FAILURE DESCRIPTION CORRECTIVE ACTION NO.
904017 Valves, 1188032, Support Maintenance Returned valve to normal.
1388032.
Department.
904028 Valve Operator, Will not remain open.
Adjusted close limit switch.
10VC002.
904038 Instrument,1LT0732 Out of Calibration.
Calibrated.
904055 Instrument, 1FT0530 Out of Calibration.
Calibrated.
904789 Instrument, Out of Calibration Replaced module.
1PC0514A/B.
904792 Instrument,. 1FT0640 Out of Calibration.
Calibrated.
I 904794 Instrument, 1LT0501 Out of Calibration Calibrated.
904795 Instrument, 1LT0502 Out of Calibration Calibrated.
904799 Instruments, Out of Calibration.
Calibrated.
1FM0542A, 1FM0542B, 1FM0542C.
904801 Instrument, SSAT Remove diode input leads Removed and restored.
1 Gen. Diff.
TLA685.
904801 Instrument, SSBT Remove diode input leads Removed and restored.
Gen. Diff.
TLB685.
904802 Instrument, Out of Calibration.
Calibrated 1FM0522B 1FM0522C.
904805 Instrument, 1FT0512 1FM051A/B out of Calibrated 1FM0512A/B.
calibration.
Page 9 of 16
DOCKET NO.:
50-272 RELATED.NTENANCE UNIT Nie:: Salem f/l
SUMMARY
OF SAFETY DEPARTMENT Performance DATE.: June 11, 1979 May 1979 COMPLETED BY:
L. K. Miller REPORT MONTH TELEPHONE:
609-365-7000 X507 WORK ORDER EQUIPMENT FAILURE DESCRIPTION CORRECTIVE ACTION NO.
904806 Instrument, 1FT0540 1FM0540B, 1FC0540A/B,- out Calibrated 1FM0540B, 1FC0540A/B.
of calibration.
904807 Valve Operator, Inspect/Rework/Replace Replaced positioner.
12SW008.
904807 Instrument, 1PL0311 Inspect/Rework/Replace Replaced gauges.
904807 Valve, 12SW008 Inspect/ Rework/Replace Reworked.
904807 Valve Operator, Inspect/RewO'rk/Replace Replaced control air.solenoid.
15SW024.
904807 Instrument, 1PL0310 I!!spect/Rework/Replace Replaced gauges.
904807 Valve, 15SW015.
Inspect/Rework/Replace Reworked.
904807 Valve, 15SW024.
Inspect/Rework/Replace.
Reworked.
904808 Valve, 16SW015, Inspect/Rework/Replace Reworked.
16SW024 904808 Instruments, Inspect/Rework/Replace Cleaned, Calibrated 1PL0313, 1PL0312, 1PL0260 904808 IValv.e Operator.,
Inspect/Rework/Replace Replaced control air solenoid.
16SW024.
904809 Instruments; Inspect/Rework/Replace Cleaned, Calibra.ted 1PL0309, 1PL0258, 1PL0308, 1TL3757
~O[f809 Valves, 14SW024, Inspect/Rework/Replace Reworked.
14SW015 Page 10 of 16
DOCKET NO.:
50-272 RELATED ~NTENANCE
SUMMARY
OF SAFETY UNIT Nll-:
Salem Ill DEPARTMENT Performance DATE:
June 11, 1979 REPORT MONTH May 1979 COMPLETED BY:
L. K. Miller TELEPHONE:
609-365-7000 X507 WORK ORDER EQUIPMENT FAILURE DESCRIPTION CORRECTIVE ACTION NO.
904809 Valve Operator, Inspect/Rework/Replace Replaced control air solenoid.
14SW024.
i 904812 Instrument, 1FT0510 No output from 1FM0510A Calibrated.
904814 Instrument, 1PT0506 Out of Calibration.
Calibrated.
904815 Instrument, 1PT0505 Out of Calibration Calibrated.
9.04816 Instruments, Out of Calibration.
Calibrated.
1TM0505A, 1TM0505C 904819 Instrument, 1FT0113 Out of Calibration.
Calibrated.
904884 Instrument, 1FT0435 Out of Calibration.
Calibrated.
904887 Instrument, 1FT0128 Out of Calibration.
Calibrated.
904889 Instrument, 1LT0730 Out of Calibration.
Calibrated.
904890 Instrument, 1PT0142 Erratic Output.
Calibrated.
904891 Instrument, 1LT0734 Out of Calibration.
Calibrated.
9.04892 Instrument,.1FT0511 1FM0511B Out of Calibration Calibrated 1FM0411B.
904899 Instrument, 1FT0520 1FM0520B out of Calibration Calibrated 1FM0520B 904900 Damper, lCAA031, Rework Control Air Solenoid Cleaned 1SV0690 032, 033 1SV0690.
904901 Instruments, lROllA Perform Channel Functional.
Performed Functional Sur-1R012B, 1R012A veillance.
Page 11 of 16
DOCKET NO.:
50-272 RELATED ~TENANCE UNIT N.:
Salem tfl
SUMMARY
OF SAFETY DATE:
June 11, 1979 DEPARTMENT Performance COMPLETED BY:
L. K. Miller REPORT MONTH May 1979 TELEPHONE:
609-365-7000 X507 WORK ORDER EQUIPMENT FAILURE DESCRIPTION CORRECTIVE ACTION NO.
. 904904 Valves, 12GB004, Provide Support for Provided hand sender, stroked 14GB004 Maintenance Department.
Valves.
904912 Instruments, 1R012I Perf drm Channel Functions.
Performed Functional.
lROllA,. 1R012A.
Q04918 Instruments, lROlH Perform 7 Day Channel Performed functional surveil..:.,
1R012A, 1R012B Functional Surveillance.
lance.
905070 Instrument, No alarm, 7 GPM indicated Returned retainer ring to 1FI0940.
fl.ow when 0 Flow.
positioner.
Page 12 of 16
DOCKET NO.:
50-272
&TENANCE N4:
SUMMARY
OF SAFETY RELATED UNIT Salem Ill June 11, 1979 DATE:
DEPARTMENT Maintenance May 1979 COMPLETED BY:
L. K. Miller REPORT MONTH TELEPHONE:
609-365-7000 X507 WORK ORDER EQUIPMENT FAILURE DESCRIPTION CORRECTIVE ACTION NO.
901312 Compressor, Replace compressor with Replaced compressor, unloader.
13 Chiller.
spare.
901400 Motor, 15 Serv.
Chang*e motor with spare.
Replace motor with spare.
Water Pump.
901723 Motor, 12 RC;El.
Repair bearing oil lift Repaired junction bo:X:.
pump press. device.
901726 Air Lock, l00 1:-:E;1; Repair Inner door.
Replaced failed cam follower.
Containment.*
901735 Crane, 1 Man-'-.
Repair/replace crane motor Cleaned contacts.
ipulator capacitor.
901973 Air Lock, 100' El.
Mech. Interlock is jammed/
Replaced cam follower, adjusted.
Containment broken.
901994 Valve, 10CV021.
Excessive seal leakoff.
Repacked.
902806 Valve, 10NT026.
Repair, leaks thru.
Replaced dis:c, spring, gasket.
902812 Valve, 10NT034.
Repair, leaks.
Rebuilt valve.
902850 Breaker, 11 Serv.
Repair, Replace cover and Replaced Term. Block, Repaired Water Pump 4KV.
Term. block.
Cover.
903058 Sump, 11 Cont....
Inspect, clean out.
Cleaned debris from sump..
903058 Sump, 12 Cont.
Inspect, clean out.
Cleaned debris from sump.
903286 Valve, 11RC027 Split packing gland fol-:
Replaced packing follower.
lower.
903289 Compressor, 12 Trips on oil pressure.
Added oil and set unlo.aders.
Chiller.
Page 13 of 16
DOCKET NO.:
50-272
~~----~--------------
SU~~ OF SAFETY RELATED ~TENANCE DEPARTMENT Maintenance UN IT N~:~s_a_1_em H_1 ____ ~---------
DATE:
June 11, 1979 REPORT MONTH May 1979 COMPLETED BY:__,;L;;;.-.*~K~*--M~il~l~e=r--..~~~~~
TELEPHONE:
609-365-7000 X507 WORK ORDER EQUIPMENT FAILURE DESCRIPTION CORRECTIVE ACTION NO.
903342 Screen, 14 Service Screen runs only in inch Calibrated lPD-2734 Water.
mode.
903409 Valve, 14SJ025.
Repack.
Repacked.
903417 Valve 12SJ025.
Repack.
0 Repacked.
903425 Valve, 11SJ023.
Repack.
Repacked.
903426 Valve, 11SJQ25.
R~pack.
Repacked.
903766 Valve, 12SW025.
Install new diaphragm.
Replaced diaphragm.
904870 Air lock, 100' El.'
Inner door wil_l not close.
Replaced cam follower.
~...
Containment.
Page 14 of 16
~.
..l
~
SALEM UNIT I OPERATING
SUMMARY
MAY 1979 5-1 thru 5-31 REFUELING OUTAGE.
Page 15 of 16
REFUELING INFORMATION DOCKET NO.: 50-272 UN IT: Salem #1 DATE: June 11,. 1979 COMPLETED. BY:. L. K. Miller TELEPHONE: 609-365-7000 x 5*07 MONTH:~ __
M_a_y_l_9_7_9 _____________ __
- 1.
Refueling information has changed from last month:
YES NO X
- 2.
Scheduled date of next* refueling:
March 29, 1980
- 3.
Scheduled date* for restart following. refueling:
May 2 5, 19 8 O
- 4.
A.
Will Technical. Specification changes or other. license
- amend.men ts be required'?
YES NO NOT DETERMINED TO-DATE May 19 7 9
- B-.. *- Has the* reload* fue1. -design.. been reviewed. by the Station Operat~~g Review Committee?
YES NO X
If no, when is it scheduled?
February 1980
- 5.
Scheduled date(s) for submitting proposed licensing action:
February 1980 (If required).
- 6.
Importan.t licensing considerations associated with refueling:
NONE
- 7.
Number of Fuel Assemblies:
A.
In-Core 193 B.
In Spent Fuel Storage*
0
- 8.
Present licensed spent fuel storage capacity:
264 Future spent fuel storage capacity*:
1,170
- 9.
Date of last refueling that can be discharged to the spent fuel pool assuming the present 'licensed capacity:
April 1982 Page 16 of 16 8-l-7.R4