November 2, 1995
Mr. T. Palmisano, General Manager
Palisades Nuclear Generating Plant
27780 Blue Star Memorial Highway
Covert, MI
49043-9530
Dear Mr. Palmisano:
SUBJECT:
INTEGRATED INSPECTION REPORT 50-255/95011
Dear Mr. Palmisano:
This refers to the routine safety inspection conducted by M. E. Parker,
P. F. Prescott and others of this office from August 22 through October 11,
1995.
The inspection included a review of activities at your Palisades
Nuclear Generating Facility. At the conclusion of the inspection, the
findings were discussed with those members of your staff identified in the
enclosed report.
Areas examined during the inspection are identified in the report. Within
these areas, the inspection consisted of a selective examination of procedures
and representative records, interviews with personnel, and observation of
activities in progress.
Based on the results of this inspection, we noted that certain of your
activities appeared tri be in violation of NRC requirements, as specified in
the enclosed Notice of Violation (Notice).
The violation is of concern
. because an alternative to the Code vibration acceptance criteria was
implemented prior to NRC approval, and in fact, the relief request was twice
denied because the limits ~stablished did not provide sufficient assurance
that pump testing would detect degradation prior to reaching the vibration
limits.
You are required to respond to this letter and should follow the instructions
specified in the enclosed Notice when preparing your response.
In your
response, you should document the specific actions taken* and any additional
actions you plan to prevent recurrence; After reviewing your response to this
Notice, including your proposed corrective actions and the results of future
inspections, the NRC will determine whether further NRC enforcement actions is
necessary to ensure compliance with NRC regulatory requirements.
In addition, you continued to exhibit weakne~ses in foreign material control
and indications of poor plant material conditions.
Cracking of the generator
isophase bus connections, failure of a wire connection on the number two
governor valve linear variable differential transformer (LVDT), and failure of
the motor operated switchyard disconnects, led to two plant shutdowns and a
power reduction.
-: r" ~, 1 ,
-'l...v~**'i*u
'-' '- \\.J
9511160349 951102
ADOCK 05000255
G
T. Palmisano
-2-
In accordance with 10 CFR 2.790 of the Commission's regulations, a copy of
this letter, the enclosures and your response to this letter will be placed in
the NRC Public Document Room.
The responses directed by this letter and the accompanying Notice are not
subject to the clearance procedures of the Office of Management and Budget as
required by the Paperwork Reduction Act of 1980, PL 96-511.
We will gladly discuss any questions you have concerning th1s inspection.
Sincerely,
/s/I. N. Jackiw for
Wayne J. Kropp, Chief
Reactor Projects Branch 3
Docket No. 50-255
License No. DPR-20
Enclosures:
2. Inspection Report
No. 50-255/950ll(DRP)
cc w/encl:
Robert A. Fenech, Vice President,
Nuclear Operations
R. W. Smedley, Manager, Licensing Dept.
James R. Padgett, Michigan Public
Service Commission
Michigan Department of
Pobl ic Health
Department of Attorney General (Ml)
Distribution:
Docket File w/encl
PUBLIC IE-01 w/encl
OC/LFDCB w/encl
SRI Palisades, Big Rock w/encl
Project Manager, NRR w/encl
Document:
R:\\insprpts\\powers\\pali\\pal95011.drp
DRP w/encl .
Riii PRR w/encl
G. E. Grant, Rill w/encl
IPAS (E-Mail) w/encl
To receive e copy of thia document, indicate in the box *c* * Copy without attach/encl *£* * Copy with attach/encl
- N* *
Ho co
OFFICE
tJ
RII I
,
NAME
Caniano
g/Creed/Haus+n
Ul
~~ /Cameron
DATE
/o .. ~}e
~l \\ ~
OFFICIAL RECORD COPY